Vidyut Sahayak (Pareshan) Contractual · Work through your exam, one topic at a time.

All guide sections

Control Systems

Control Systems

This domain tests transfer functions, block-diagram reduction, time response, stability and frequency response. Numerical questions often ask for damping ratio, overshoot or Routh array sign changes.

Core rules

  • A transfer function is the Laplace ratio of output to input with zero initial conditions. Its poles are the roots of the denominator.
  • First-order step response: time constant τ; about 63.2% of final value at one τ and about 98% at four τ.
  • Second-order standard form: ωn²/(s² + 2ζωn s + ωn²). Peak overshoot Mp = exp(−πζ/√(1−ζ²)); peak time tp = π/(ωn√(1−ζ²)).
  • Routh-Hurwitz: the number of sign changes in the first column equals the number of right-half-plane poles. A zero row is handled with the auxiliary polynomial.
  • Steady-state error depends on system type and input. A type-0 system has finite step error; a type-1 system has finite ramp error.
  • Gain margin is the negative of the gain at the phase crossover; phase margin is measured at the gain crossover. Both must be positive for stability.
  • P action gives offset; I action removes offset; D action adds damping.

Worked example

For G(s) = 16/[s(s+4)] with unity feedback, the characteristic equation is s² + 4s + 16 = 0. Thus ωn = 4 rad/s and 2ζωn = 4, so ζ = 0.5. Overshoot = exp(−π×0.5/√0.75) = exp(−1.814) = 0.163, about 16.3%.

Traps

Do not use open-loop poles when the question asks for closed-loop stability. Check Routh special cases. Do not compute steady-state error for an unstable system. Watch the sign convention for margins.