Journeyman Electrician flashcards
Journeyman Electrician · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Ohm's Law
- The current in a circuit equals the voltage divided by the resistance, written I = E ÷ R. Rearranged, E = I × R and R = E ÷ I.
- Power Formula
- True power in watts equals voltage times current in a resistive circuit, P = E × I, and may also be written as I²R or E² ÷ R.
- Series Circuit Current
- In a series circuit the current is identical through every component, total resistance is the sum of the resistances, and the voltage divides in proportion to resistance.
- Nonmetallic-Sheathed Cable Uses
- Type NM cable is permitted in normally dry locations such as dwellings, but not in wet locations, in masonry voids, or where subject to physical damage.
- Conduit as Grounding Means
- Rigid metal conduit, IMC, and EMT are recognized equipment grounding conductors, while PVC conduit is not, so a separate equipment grounding conductor must be installed.
- Box Fill for 12 AWG
- Each 12 AWG conductor counts as 2.25 cubic inches of box volume, and each yoke-mounted device counts as two conductors when sizing boxes under NEC 314.16.
- Grounding Electrode Conductor Sizing
- The conductor connecting the grounded service point to the grounding electrode is sized from NEC Table 250.66 using the largest ungrounded service conductor.
- Equipment Grounding Conductor Sizing
- The equipment grounding conductor provides a low-impedance fault path and is sized from NEC Table 250.122 using the rating of the overcurrent device ahead of the equipment.
- Class A GFCI Threshold
- A Class A ground-fault circuit interrupter trips at 4 to 6 milliamperes of ground-fault current and provides personnel protection on 120/240 volt circuits.
- Small Conductor Rule
- NEC 240.4(D) limits overcurrent protection to 15 amperes for 14 AWG, 20 amperes for 12 AWG, and 30 amperes for 10 AWG copper conductors.
- Interrupting Rating Requirement
- An overcurrent device's interrupting rating must equal or exceed the available fault current at its line terminals, otherwise the device may fail violently during a short circuit.
- Next Size Up Rule
- For devices rated 800 amperes or less, the next higher standard overcurrent rating may be used when the conductor ampacity does not match a standard rating and the circuit is not multioutlet.
- Continuous Load 125 Percent
- A continuous load operates for 3 hours or more, and branch-circuit conductors plus overcurrent devices must be sized at not less than 125 percent of it.
- Dwelling Lighting Load
- Dwelling general lighting load is calculated at 3 volt-amperes per square foot, with small-appliance and laundry branch circuits added separately at 1500 VA each.
- Commercial Receptacle Load
- Each receptacle outlet on a commercial branch circuit is calculated at 180 volt-amperes, so ten outlets equal 1800 VA on a 20 ampere circuit.
- Ampacity Correction and Adjustment
- Conductor ampacity from Table 310.16 must be corrected for ambient temperature and adjusted for the number of current-carrying conductors sharing a raceway.
- Bundled Conductor Derating
- Four to six current-carrying conductors in one raceway require 80 percent adjustment, seven to nine require 70 percent, and ten to twenty require 50 percent.
- Parallel Conductor Minimum Size
- Parallel conductors must be 1/0 AWG or larger and identical in length, conductor material, size, insulation type, and termination method.
- Working Space Depth
- NEC 110.26 requires clear working space at least 3 feet deep, 30 inches wide, and 6.5 feet high, with depth increasing for higher voltages.
- Straight Pull Box Length
- A box or conduit body used for a straight pull must be at least eight times the trade size of the largest raceway entering it.
- Panelboard Location Restrictions
- Overcurrent devices must not be installed in bathrooms or clothes closets and must not be located over steps; they must remain readily accessible.
- Motor Conductor Sizing
- Motor branch-circuit conductors must have an ampacity of at least 125 percent of the motor full-load current taken from the NEC motor tables.
- Motor Overload Protection
- Overload protection for a motor with a marked service factor of 1.15 is typically set at 125 percent of the nameplate full-load current.
- Transformer Primary Protection
- For transformers with a primary current over 9 amperes, primary overcurrent protection is set at not more than 125 percent of rated primary current.
- Hazardous Location Classes
- Class I locations contain flammable gases or vapors, Class II locations contain combustible dust, and Class III locations contain ignitable fibers or flyings.
- Division 1 Versus Division 2
- Division 1 covers hazardous conditions that exist under normal operation, while Division 2 covers conditions that occur only under abnormal or fault conditions.
- Pool Equipotential Bonding
- Around permanently installed pools, metal parts, forming shells, and reinforcing steel must be bonded together into an equipotential grid per NEC 680.26.
- Test Before Touch
- Circuits must be verified de-energized with a tester rated for the voltage before work begins, and all conductors are treated as energized until tested.
- Lockout Tagout Verification
- Each worker applies a personal lock and tag to the energy-isolating device, then verifies isolation by attempting to start the equipment.
- Limited Approach Boundary
- The limited approach boundary is the distance from exposed energized parts that unqualified persons must not cross, and it increases with system voltage.
- Construction Site GFCI
- Temporary 125 volt, 15 and 20 ampere receptacles on construction sites require Class A ground-fault circuit interrupter protection under NEC 590.6.
- Conduit Bend Limit
- No more than 360 degrees of total bends is permitted between pull points in a conduit run, counting all offsets, saddles, and elbows.