Orphaned Water Heater on an Oversized Common Vent
Basement mechanical room, 12 ft by 10 ft by 7.5 ft (900 cu ft), drywalled and spray-foamed, with a solid door to a finished basement. Equipment: a 5-year-old 40,000 Btu/h natural-draft gas water heater and, until last week, a 100,000 Btu/h natural-draft furnace. Both were common-vented into one 5 in. Type B vent, 22 ft total height, with a 4 ft connector. The furnace was replaced with a 96% AFUE condensing unit vented in 2 in. PVC through the sidewall. The water heater is now alone on the 5 in. vent. Gas is 7 in. w.c., 1,000 Btu/cu ft. The local vent table, at 20 ft of rise, lists: 3 in. = 60,000 Btu/h, 4 in. = 110,000 Btu/h, 5 in. = 200,000 Btu/h.
1. Is the water heater's combustion air arrangement acceptable as it stands? Show the numbers.
Read the worked answer
Room volume test.
- All-air-from-inside allowance is 50 cu ft of space per 1,000 Btu/h of input.
- Required: 40,000 / 1,000 x 50 = 2,000 cu ft.
- Available: 12 x 10 x 7.5 = 900 cu ft.
- 900 < 2,000, so the room is a confined space. It must have permanent openings, and because the basement was spray-foamed it cannot be treated as a leaky space.
Makeup air requirement.
- Two permanent openings, one within 12 in. of the top and one within 12 in. of the bottom of the enclosure.
- All-air-from-outdoors: 1 sq in. free area per 1,000 Btu/h = 40 sq in. each.
- Vertical ducts to outdoors: 1 sq in. per 2,000 Btu/h = 20 sq in. each.
- Horizontal ducts to outdoors: 1 sq in. per 4,000 Btu/h = 10 sq in. each.
- Louvers and grilles get sized on free area, not frame size, so a 40 sq in. requirement is often a much larger grille.
Conclusion: as it stands the room is a confined space with a solid door and no openings. That is a violation and, with a draft hood appliance, a spillage and CO hazard. Correct it before anything else.
2. Evaluate the 5 in. vent now that the water heater is alone, and state the corrective work and how you verify it.
Read the worked answer
The vent problem.
- The table shows 5 in. at 20 ft of rise is good for 200,000 Btu/h. The connected load is now 40,000 Btu/h.
- A vent that oversized never warms up enough to establish a steady draft. Flue gases cool, the water vapor condenses, and the condensate is acidic - it eats the vent from the inside and drips at the joints. During warm-up and standby the draft hood spills into the room.
- The 4 ft connector is also now sized for the old combined load; the connector may not be smaller than the appliance draft hood outlet, but it should be sized for the new single load.
Corrective work:
- Reline the existing chase with a listed 3 in. liner - the table gives 3 in. = 60,000 Btu/h at 20 ft, comfortably above 40,000 Btu/h - or install a 3 in. vent, properly supported and terminated.
- Keep the connector as short and as direct as possible, sloping at least 1/4 in. per ft upward toward the vent, with a listed thimble at the wall.
- Provide the combustion air openings from the previous step.
- Cap or seal the old furnace breeching so it cannot leak flue gas into the room.
Verification:
- Draft gauge at the connector, smoke test at the draft hood, and CO readings in the flue and in the room after the unit has run 10-15 minutes.
- Spillage test at the draft hood at start-up and again after steady state. If the hood spills, the vent or the air supply is still wrong.
3. The owner wants to move the water heater into a 4 ft by 4 ft closet that opens into a bedroom. What do you tell them?
Read the worked answer
Refuse the location as proposed.
- Appliances with draft hoods cannot take combustion air from a bedroom or bathroom, and a closet opening directly into a bedroom is treated the same way for air-supply purposes.
- The closet volume is 4 x 4 x 8 = 128 cu ft against the 2,000 cu ft the 40,000 Btu/h input requires. It would be a confined space with no acceptable air source.
- A solid or louvered door to a bedroom is not a compliant air path, and a bedroom cannot be the relief path for spillage.
Options that do work:
- A direct-vent or sealed-combustion water heater, which takes air from outdoors through a two-pipe system and is not dependent on room volume.
- A power-vented unit vented through the sidewall with outdoor air piped to the appliance.
- Keeping the atmospheric unit where it is, with proper openings and a correctly sized vent.
Also mention: if the appliance is converted to a sealed-combustion or direct-vent type, the venting and air-supply analysis changes entirely - rerun the vent sizing for the new appliance and keep the CO and draft testing at final.