KS Water Operator flashcards
KS Water Operator · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- CT value
- Product of disinfectant residual concentration in mg/L and contact time in minutes; used to demonstrate required log inactivation of Giardia, viruses, and other pathogens.
- Jar test purpose
- Bench-scale test that simulates coagulation, flocculation, and settling to determine optimum coagulant dose, pH, and mixing conditions before full-scale adjustment.
- Breakpoint chlorination
- Point where applied chlorine has oxidized ammonia and other demand; beyond it, additional chlorine produces a free chlorine residual that increases almost linearly with dose.
- Combined filter effluent turbidity
- Under the Surface Water Treatment Rule, must be 0.3 NTU or less in at least 95 percent of monthly measurements and never exceed 1 NTU.
- Chlorine demand
- Difference between the chlorine dose applied and the residual remaining after a specified contact time; reflects consumption by organics, ammonia, iron, and other reducing agents.
- Fluoride MCL
- Primary maximum contaminant level is 4.0 mg/L; the secondary standard is 2.0 mg/L, and many systems target about 0.7 mg/L for dental benefits.
- Filter backwash triggers
- Backwash is initiated by terminal head loss, typically 6 to 8 feet, or by turbidity breakthrough, or by run time limits set in the plant operating plan.
- Minimum distribution residual
- Typical requirement is 0.2 mg/L free chlorine or 0.5 mg/L chloramine at the farthest sampling point; primacy states may set stricter values.
- Air gap
- Physical separation between a potable water outlet and the flood level rim of a receiving vessel; provides the highest level of backflow protection.
- Hazen-Williams formula
- Empirical head loss equation: hL = 4.52 Q raised to 1.85 divided by C raised to 1.85 times d raised to 4.87, with Q in gpm and d in inches.
- Main repair disinfection
- After repair, the main is chlorinated, typically to 25 mg/L for 24 hours or 50 mg/L for 24 hours, then flushed and sampled for bacteriological clearance.
- Dead-end main flushing
- Periodic or automatic flushing prevents stagnation, sediment buildup, and loss of disinfectant residual at the ends of distribution branches.
- Specific capacity of well
- Pumping rate in gallons per minute divided by drawdown in feet; indicates well efficiency and declines as the aquifer or screen becomes clogged.
- Cone of depression
- Drawdown shape around a pumping well; overlapping cones from nearby wells can cause interference and reduce yield.
- Confined aquifer
- Groundwater unit bounded above and below by low-permeability layers; water is under pressure and wells may flow without pumping.
- Nitrate MCL
- Maximum contaminant level is 10 mg/L measured as nitrogen; common sources are fertilizer, manure, and septic systems, and it causes methemoglobinemia in infants.
- Arsenic MCL
- Maximum contaminant level is 0.010 mg/L; treatment includes coagulation with filtration, ion exchange, and adsorptive media such as granular ferric hydroxide.
- E. coli significance
- Indicator of fecal contamination in drinking water; a positive result triggers repeat sampling, investigation, and public notification requirements.
- Wellhead protection area
- Land surface and subsurface area through which contaminants could reach a public water supply well; delineated by fixed radius or hydrogeologic methods.
- Primary versus secondary standards
- Primary standards are enforceable health-based limits such as MCLs; secondary standards are non-enforceable aesthetic guidelines for color, odor, and similar qualities.
- Public notice tiers
- Tier 1 requires notice within 24 hours for acute violations; Tier 2 within 30 days; Tier 3 in the annual report or as state rules specify.
- Consumer Confidence Report
- Annual water quality report that community water systems must deliver to customers by July 1, listing contaminants detected, sources, and health information.
- Lead action level
- 0.015 mg/L based on the 90th percentile of first-draw samples; exceedance triggers corrosion control, source water treatment, and public education requirements.
- TTHM and HAA5 limits
- Disinfection byproduct MCLs are 0.080 mg/L for total trihalomethanes and 0.060 mg/L for five haloacetic acids, evaluated as locational running annual averages.
- Total coliform positive limit
- For systems collecting 40 or more routine samples monthly, no more than 5 percent may be total coliform positive; smaller systems have fixed maximums.
- Confined space oxygen range
- Acceptable entry atmosphere is 19.5 to 23.5 percent oxygen; outside this range, ventilation and reassessment are required before entry.
- Chlorine gas hazard
- Chlorine gas is heavier than air and accumulates in low areas; it requires supplied-air respiratory protection and immediate evacuation when leaks occur.
- Trench protective systems
- At 5 feet or deeper, protective systems such as sloping, shoring, or shielding are required; spoil and equipment must be kept at least 2 feet from the edge.
- Lockout tagout purpose
- Hazardous energy control procedure that isolates pumps, blowers, and electrical equipment before maintenance to prevent unexpected startup or release of stored energy.
- Cost per thousand gallons
- Total annual cost divided by annual production in thousands of gallons; used to compare treatment or distribution options and to support rate setting.
- Water loss percentage
- Produced water minus billed water divided by produced water, times 100; values above roughly 10 to 15 percent suggest leakage or metering problems.
- Asset criticality
- Ranking of assets by consequence of failure and likelihood of failure; used to prioritize maintenance, repair, and capital replacement spending.