Quick reference

General Electrical Knowledge and Code Administration

  • NEC structure (90.3): Chapters 1-4 apply generally, Chapters 5-7 supplement or modify them, Chapter 8 is independent, and Chapter 9 contains reference tables and examples.

  • Working space depth at 600 V or less (Table 110.26(A)(1)): Condition 1 = 3 ft, Condition 2 = 3.5 ft, Condition 3 = 4 ft, measured from the enclosure front.

  • Working space width and height (110.26(A)(2) and (A)(3)): 30 in minimum or the width of the equipment, whichever is greater, and 6.5 ft of headroom.

  • Dedicated equipment space (110.26(E)): the space directly above and below switchboards and panelboards is reserved for electrical equipment only.

  • Termination rule (110.14(C)): conductor ampacity is limited by the lowest temperature rating among the conductor insulation and the terminations unless listed and identified otherwise.

  • Field markings: 110.22 disconnect identification, 110.16 arc-flash hazard labels, and 110.24 available fault current marking at service equipment in other than dwelling units.

  • AHJ authority (90.4): the authority having jurisdiction enforces the Code, may interpret its provisions, approve listed materials, and grant special permission for equivalent safety.

  • Kentucky adopts the National Electrical Code by statewide regulation; permits, inspections, and amendments are administered by the state electrical inspection authority.

Quick reference

Wiring Methods and Materials

  • Chapter 3 governs wiring methods; 300.4 requires protection where conductors are within 1.25 in of the framing surface or otherwise subject to physical damage.

  • Minimum cover (Table 300.5): 24 in for direct burial in general, 12 in for residential 120/240 V branch circuits 20 A or less with GFCI, 6 in for rigid metal conduit, 18 in for PVC.

  • NM cable (334.30): secured within 12 in of every box and at intervals not exceeding 4.5 ft along the run.

  • EMT (358.30): supported within 3 ft of a box or termination and at intervals not exceeding 10 ft; running threads are not permitted on conduit couplings.

  • Free conductor (300.14): at least 6 in of free conductor at each box, with at least 3 in extending outside the box opening.

  • Box required (300.15) at every splice, termination, pull point, and outlet; conduit bodies used as pull points must be sized and supported accordingly.

  • Conductor identification (200.6, 250.119): grounded conductors white or gray; equipment grounding conductors green or green with a yellow stripe.

  • Ampacity from Table 310.16 is corrected for ambient temperature and adjusted for more than three current-carrying conductors in a raceway or cable.

Quick reference

Grounding and Bonding

  • 250.50: every grounding electrode present at the building or structure must be bonded together to form a single grounding electrode system.

  • Electrode types (250.52(A)): metal water pipe with 10 ft or more of earth contact, rod or pipe 8 ft long, concrete-encased electrode, ground ring of 20 ft of 2 AWG, and plate electrodes.

  • Rod and pipe rule (250.53(A)(2)): a single 8 ft rod must measure 25 ohms or less to earth; otherwise a second rod at least 6 ft away must be added.

  • GEC sizing (Table 250.66) is based on the largest ungrounded service conductor; the required copper conductor need not exceed 3/0 for service conductors of 1100 kcmil or larger.

  • EGC sizing (Table 250.122) is based on the rating of the overcurrent device protecting the circuit, not on the circuit conductor size.

  • Permitted equipment grounding conductors (250.118) include copper conductors, rigid metal conduit, IMC, EMT, and listed armored cable, subject to the stated restrictions.

  • Service bonding (250.24): the grounded service conductor connects to the grounding electrode conductor, the service enclosures, and the supply-side bonding jumper.

  • Where a grounding electrode conductor passes through ferrous metal enclosures it must be bonded to the enclosure at both ends (250.64(E)); grounding continuity must be maintained at boxes (250.148).

Quick reference

Overcurrent Protection and Conductors

  • 240.4(D): 14 AWG copper limited to 15 A, 12 AWG to 20 A, and 10 AWG to 30 A, except as permitted by the listed exceptions.

  • 240.6(A) standard ratings include 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600 A.

  • 240.4(B) next-size-up rule applies when the device does not exceed 800 A, the conductor ampacity does not exceed 800 A, and the 240.4(D) small-conductor limits are not involved.

  • Tap rule (240.21(B)(1)): a tap up to 10 ft requires ampacity at least one-tenth the upstream device rating, enclosure in a raceway, and termination in a single breaker.

  • Ambient correction (Table 310.15(B)(2)(a)) uses a 30 degrees C base; multipliers include 0.96 (31-35 C), 0.91 (36-40 C), 0.87 (41-45 C), and 0.82 (46-50 C).

  • Adjustment (310.15(C)(1)): 4 to 6 current-carrying conductors = 80 percent, 7 to 9 = 70 percent, 10 to 20 = 50 percent of table ampacity.

  • Table 310.16 copper example: 12 AWG THHN is 20 A at 60 C, 25 A at 75 C, and 30 A at 90 C before correction or adjustment.

  • Arc energy reduction (240.87): overcurrent devices rated 1200 A or more require an approved means such as zone-selective interlocking or energy-reducing maintenance switching.

Quick reference

Branch Circuits, Feeders, and Boxes/Raceway Fill

  • 210.52(A): receptacles spaced so no point along the wall line is more than 6 ft from a receptacle, which produces the 12 ft wall-space rule.

  • 210.52(C): kitchen countertop receptacles arranged so no point along the counter wall space is more than 24 in from a receptacle.

  • Branch-circuit ampacity (210.19(A)(1)) is not less than 125 percent of the continuous load plus 100 percent of the noncontinuous load, with the device sized per 210.20.

  • GFCI (210.8) is required for 125 V, 15 and 20 A receptacles in dwelling bathrooms, garages, outdoors, basements, and within 6 ft of sinks.

  • AFCI (210.12): dwelling-unit branch circuits supplying outlets in living areas require arc-fault circuit-interrupter protection.

  • Box fill (Table 314.16(B)): 14 AWG = 2.00 cu in, 12 AWG = 2.25 cu in, 10 AWG = 2.50 cu in per conductor; a device yoke counts as two conductors and all EGCs count as one.

  • Raceway fill (Chapter 9, Table 1): 53 percent for one conductor, 31 percent for two, and 40 percent for three or more conductors.

  • Pull and junction boxes (314.28): 8 times the largest raceway for straight pulls and 6 times for angle or U pulls, measured from the raceway entry to the opposite wall.

Quick reference

Motors, Controls, and Utilization Equipment

  • 430.6(A)(1): use the full-load current tables (430.247 through 430.250) for conductor and short-circuit protection sizing, not the motor nameplate current.

  • Branch-circuit conductors (430.22) are at least 125 percent of the motor full-load current for a single continuous-duty motor.

  • Short-circuit protection (Table 430.52): inverse-time breaker 250 percent, dual-element fuse 175 percent, non-time-delay fuse 300 percent, instantaneous-trip breaker 800 percent of FLC.

  • Overload protection (430.32) is set at 125 percent of nameplate current where the service factor is 1.15 or greater, otherwise 115 percent.

  • Feeder sizing (430.24): 125 percent of the largest motor full-load current plus 100 percent of the other motor loads plus other connected loads.

  • Disconnecting means (430.102(B)) must be within sight of and readily accessible from the motor and driven machinery, and capable of being locked open.

  • Air conditioning (440.32): branch-circuit conductors are sized at 125 percent of the rated-load current or branch-circuit selection current, whichever is greater.

  • Control circuits (430.72) require overcurrent protection based on the control conductor size and source rating; appliance branch circuits follow 422.11.

Quick reference

Special Occupancies

  • 500.5 classifies locations by Class I (flammable gases or vapors), Class II (combustible dust), Class III (ignitable fibers and flyings), and by Division 1 or 2 for likelihood of the hazard.

  • Class I Division 1 (500.5(B)(1)): ignitable concentrations exist under normal conditions or frequently because of repair, maintenance, or leakage.

  • Articles 511 (commercial garages), 513 (aircraft hangars), 514 (motor fuel dispensing), and 515 (bulk storage plants) impose specific area classifications and wiring methods.

  • 517.30 divides the health care essential electrical system into the life safety branch, the critical branch, and the equipment branch.

  • Articles 518 and 520 add requirements for assembly occupancies and theaters, including emergency lighting and specialized wiring methods.

  • 547.10: agricultural buildings with livestock confinement require an equipotential plane bonded to reduce voltage gradients that could shock animals.

  • Article 550 covers mobile homes, Article 551 recreational vehicles, and Article 555 marinas and boatyards including shore power ground-fault protection.

Quick reference

Special Equipment

  • 690.8: photovoltaic circuit conductors and overcurrent devices are sized at 125 percent of the calculated maximum current.

  • 690.12: PV systems on buildings require rapid shutdown that limits conductors outside the array boundary upon activation.

  • 700.10(A): emergency system wiring must be entirely independent of all other wiring and installed in separate raceways, boxes, and cabinets.

  • 680.26: pool, spa, and fountain metal parts, the water, and specified perimeter surfaces must be bonded to a common equipotential bonding grid.

  • 620.51 and 620.62: elevators require a disconnecting means, and where multiple driving machines are supplied the disconnects must be selectively coordinated.

  • 625 covers electric vehicle supply equipment; 625.40 requires an individual branch circuit for each outlet and 625.54 requires GFCI protection for the receptacle.

  • 695: fire pump supply conductors and overcurrent protection must be arranged to avoid accidental interruption of power to the fire pump.

Quick reference

Special Equipment, and Low-Voltage/Communications Systems

  • Article 725 covers Class 1, Class 2, and Class 3 remote-control and signaling circuits; Class 2 and 3 power limits appear in Chapter 9 Tables 11(A) and 11(B).

  • 725.136: Class 2 and Class 3 conductors must be separated from light and power conductors by spacing or a barrier unless a specific exception permits otherwise.

  • Article 760 covers fire alarm systems: Part II governs non-power-limited fire alarm circuits (NPLFA) and Part III governs power-limited fire alarm circuits (PLFA).

  • Article 800 covers communications circuits; 800.100 requires a grounding conductor of at least 14 AWG copper, no longer than 20 ft, run to the grounding electrode system.

  • Article 770 covers optical fiber cable, Article 820 community antenna television and radio distribution, and Article 830 network-powered broadband.

  • Cable substitution follows the hierarchy CMP over CMR over CM, with comparable ordering among CL3P, CL3R, and CL3 cables.

  • 725.121: Class 2 and Class 3 power supplies must be listed for the purpose or supplied from a listed source with inherently limited output.

Quick reference

Electrical Safety, Inspection, and Fire/Life Safety Requirements

  • 110.24: service equipment in other than dwelling units must be field-marked with the available fault current and the date the calculation was performed.

  • 110.16: arc-flash hazard warning labels are required on equipment likely to be examined, adjusted, serviced, or maintained while energized.

  • 110.26(D): working space illumination must be provided and must not be controlled only by automatic means.

  • 300.21: openings around electrical penetrations through fire-rated walls, floors, and ceilings must be firestopped with approved materials.

  • 590.6(A): temporary wiring on construction sites requires GFCI protection for all 125 V, 15 and 20 A receptacle outlets.

  • NFPA 70E requires establishing an electrically safe work condition: de-energize, lock and tag, and verify the absence of voltage before work begins.

  • Article 700 emergency systems and Article 701 legally required standby systems must be inspected and tested periodically, with records retained.

  • Items verified before energizing a new service typically include box fill, grounding and bonding continuity, overcurrent device ratings, and 110.26 working-space clearances.