High-Pressure Trips on One of Two Identical Chillers

NVQ L4 Refrigeration & AC · Put your knowledge to work in context.

All case studies

High-Pressure Trips on One of Two Identical Chillers

Two identical air-cooled chillers sit side by side on a roof deck, each with two R-410A circuits (11 kg per circuit) and three vertical-discharge EC condenser fans. A 3 m acoustic screen surrounds the plant and stands 800 mm from the discharge face of chiller 1; a 2.5 m parapet completes the enclosure. In July, chiller 1 trips on its high-pressure cut-out (27.5 barg) whenever ambient exceeds 30 °C and both circuits run; chiller 2 has never tripped. At 31 °C ambient and equal load the engineer records: chiller 1 circuit A at 27.0 barg with 13 K subcooling; chiller 2 at 24.8 barg with 7 K subcooling. Coils on both machines were cleaned last month, all fans run at 100%, suction pressures match, and chilled water flow and leaving temperature are identical.

1. What is the most likely cause, and what single measurement would confirm or eliminate it?

Read the worked answer

Most likely cause: hot air recirculation from chiller 1's own discharge, trapped by the acoustic screen and parapet. The screen sits 800 mm from the discharge face - far less than the manufacturer's clearance, which is normally expressed in fan diameters and is usually two or more - so the discharge plume curls back over the parapet and re-enters the coil.

The confirming measurement is air-on temperature at the condenser coil face, taken at several points across each machine at the same moment.

  • If chiller 1 reads 38–42 °C while ambient is 31 °C and chiller 2 reads close to ambient, recirculation is proven.
  • If both read ambient and chiller 1 still condenses 2 bar higher, recirculation is eliminated and I move to overcharge, non-condensables or a coil/fan fault on that machine.

Supporting checks: a smoke or anemometer traverse across the discharge to see the plume, and a repeat reading after temporarily removing a screen panel. That test costs an hour and settles the argument before anyone spends money on refrigerant or parts. Note the pattern already fits: it only happens above 30 °C and only when both circuits run, because that is when the heat load on the enclosure is greatest.

2. Explain why the clean coils, the fans at 100% and the high subcooling are all consistent with recirculation - and how you would distinguish it from overcharge and from non-condensables.

Read the worked answer

Clean coil and full fan speed are exactly what you would expect - the machine's heat-transfer capability is intact. It is being fed air that is already warm, so it behaves like a condenser operating in a hotter climate. Cleaning and fan checks were reasonable first steps but they only ever eliminate half the problem; the air side includes what the air is, not just how much of it moves.

High subcooling (13 K against 7 K) fits. With the condensing pressure pushed up, more liquid stacks in the bottom of the condenser; on a fixed charging method the subcooling rises with it. It is a symptom of the condenser being unable to reject, not evidence of too much refrigerant.

Distinguishing the three:

  • Recirculation - effect scales with ambient and load, affects the machine nearest the obstruction far more than its neighbour, and the air-on temperature is elevated.
  • Overcharge - present at all ambients and loads, usually on both machines if they were charged the same way, and air-on is normal; the subcooling stays high even at 20 °C ambient.
  • Non-condensables - condensing pressure high even at low ambient, condenser approach roughly normal, subcooling high, and the pressure does not track ambient; a standing pressure test against temperature after a long off-period confirms it.

The differentiator in every case is air-on temperature plus how the fault varies with ambient.

3. What would you do about the root cause, what interim measure would you take, and who carries the responsibility?

Read the worked answer

Root cause is an installation/design defect, not a refrigeration fault. The acoustic screen was installed to a clearance the chiller manufacturer does not permit. That responsibility sits with whoever designed and installed the screen - and my evidence is the manufacturer's clearance drawing against the 800 mm as-built.

Permanent fix, options in order:

  1. Relocate the screen to the manufacturer's minimum clearance and re-check noise compliance - the screen exists for a reason, so this needs the acoustic consultant.
  2. Fit a discharge plenum or deflector to lift the plume clear of the parapet.
  3. Reduce the screen height so it does not cap the discharge.

Only after the air-on temperature is back near ambient do I revisit refrigerant charge - and then only to confirm the original charge is correct, not to add more.

Interim: run a single circuit where the load allows, add a temporary deflector panel, and set a lower condensing setpoint with the client's agreement, logging the readings daily. Make it clear in writing that this is a temporary measure with a cost and a risk.

Responsibility: raise it formally to the principal contractor, with photographs, the air-on readings and the clearance drawing, before any of my own labour goes into it.