M.G.L. c. 146
Massachusetts statute that establishes boiler inspection, construction, and operation requirements and authorizes the Board of Boiler Rules to adopt implementing regulations.
522 CMR
Massachusetts Board of Boiler Rules regulations that implement the boiler statute and adopt ASME code requirements with state-specific amendments.
Board of Boiler Rules
Massachusetts board that administers boiler regulations, adopts code amendments, and issues licenses and variances for boiler operation and inspection.
Certificate of inspection
Document issued after a required boiler inspection showing the boiler may be operated; it must be posted and kept current.
ASME Section I
ASME Boiler and Pressure Vessel Code section governing construction of power boilers and high-pressure steam equipment.
ASME Section IV
ASME code section covering construction of heating boilers, including low-pressure steam and hot water heating boilers.
Safety valve capacity
Total relieving capacity of all safety valves must equal or exceed the boiler's maximum steam-generating capacity at allowable pressure.
Blowoff valve arrangement
Power boiler blowoff lines normally require two valves in series, one at the boiler and one downstream, to permit safe isolation.
Three T's of combustion
Temperature, turbulence, and time are the conditions needed to mix fuel and air and complete combustion with minimal unburned products.
Stoichiometric air
The exact amount of air needed to burn a fuel completely with no excess oxygen or unburned fuel.
Excess air
Air supplied beyond stoichiometric requirements to ensure complete combustion; typical excess oxygen is about 3 to 5 percent.
Forced draft
A fan supplies combustion air to the furnace under positive pressure, overcoming burner and air-side resistance.
Pre-purge
Before ignition, the burner management system forces air through the furnace for a set time to remove combustible gases.
Post-purge
After fuel shutoff, the fan continues to purge the furnace and boiler passes of unburned fuel and combustion gases.
Modulating burner
A burner that varies fuel and air input continuously to match load rather than cycling fully on and off.
Bottom blowdown
Short, frequent blows from the lowest boiler connection remove sludge and sediment; it is done at low fire.
Low-water fuel cutoff
A safety control that senses low water level and shuts off fuel to the burner before the boiler becomes unsafe.
Flame safeguard
Control system that proves pilot or main flame and closes the fuel valve if flame is lost.
High-pressure limit switch
A control that opens the fuel circuit when steam pressure reaches a set limit below the safety valve setting.
Try lever test
Manual lifting of a safety valve lever to verify the valve opens freely and reseats; done with boiler pressure at least 75 percent of set pressure.
Deaerator
Feedwater heater that removes dissolved oxygen and carbon dioxide by heating water and venting the released gases.
Conductivity blowdown
Surface blowdown controlled by boiler water conductivity or TDS to limit dissolved solids and prevent carryover.
Scale
Hard mineral deposit on boiler heating surfaces that reduces heat transfer and can overheat tubes and shell.
Steam trap
Automatic valve that discharges condensate and noncondensable gases from steam lines while preventing steam loss.
Water hammer
Pressure shock caused by rapid condensation or slug of condensate moving in a steam pipe; prevented by draining and slow valve operation.
Expansion tank
Hot water system component that absorbs the volume increase as water is heated and maintains system pressure.
Boiler log
Record of operating readings, blowdowns, water tests, and abnormal conditions kept for inspection and trend analysis.
Hydrostatic test
Pressure test using water, usually at 1.5 times design pressure, to verify strength and tightness of boiler components.
Ultrasonic thickness test
Non-destructive inspection that measures remaining metal thickness to detect corrosion or erosion in boiler parts.
Low-water emergency
If gauge glass shows no water, shut off fuel and do not add water until the boiler has cooled and been inspected.
Tube rupture
A boiler tube failure releases steam or water into the furnace; shut down, isolate fuel, and protect personnel from steam.
Carryover
Boiler water droplets or foam carried into steam lines, causing water hammer, erratic level, and contaminated steam.