First 50 of 200 questions. Each one lists the choices, the correct answer, and an explanation. The checker at the top of this page saves progress in this browser when it is available.
Continue in the practice tool above to load more questions, 50 at a time.
Question 1Massachusetts fire sprinkler statutes, regulations, and permitting requirements
In Massachusetts, which state agency administers the fire sprinkler contractor and journeyperson licensing program?
- The Department of Public Safety
- The Board of Building Regulations and Standards
- The Division of Professional Licensure
- The Department of Fire Services Correct answer.
Explanation
The Department of Fire Services, through its sprinkler program, issues and administers fire sprinkler contractor, journeyperson, and apprentice credentials in Massachusetts. The other bodies regulate other trades, building codes, or general public safety matters.
Question 2Massachusetts fire sprinkler statutes, regulations, and permitting requirements
Under the Massachusetts fire sprinkler licensing framework, work on a sprinkler system that requires a permit must generally be performed by or under the supervision of whom?
- A licensed fire sprinkler contractor Correct answer.
- A licensed master plumber
- A registered professional engineer
- A certified building inspector
Explanation
Sprinkler installation, alteration, and repair work is reserved to licensed fire sprinkler contractors and their licensed journeypersons and apprentices. Plumbers, engineers, and inspectors have separate roles and cannot substitute for the sprinkler license.
Question 3Massachusetts fire sprinkler statutes, regulations, and permitting requirements
A fire sprinkler contractor license in Massachusetts is issued to which of the following?
- A municipality acting through its fire department
- An individual who qualifies through examination and experience Correct answer.
- A property owner for work on their own building
- A corporation regardless of who owns it
Explanation
The license is issued to a qualifying individual who meets experience and examination requirements and serves as the licensee of record. Business entities operate through that licensed individual rather than holding the credential themselves.
Question 4Massachusetts fire sprinkler statutes, regulations, and permitting requirements
Which document typically must be obtained from the local authority before installing a new fire sprinkler system in a Massachusetts building?
- An electrical permit
- A fire sprinkler permit Correct answer.
- A plumbing permit
- A certificate of occupancy
Explanation
Installation or alteration of a sprinkler system requires a fire sprinkler permit issued by the local authority having jurisdiction, often the fire department. Other permits address different trades or certify completion rather than authorize installation.
Question 5Massachusetts fire sprinkler statutes, regulations, and permitting requirements
In many Massachusetts jurisdictions, which official issues the fire sprinkler permit and conducts the associated inspections?
- The state building commissioner
- The local authority having jurisdiction, often the fire chief or designee Correct answer.
- The local wiring inspector
- The local gas inspector
Explanation
The local authority having jurisdiction, commonly the fire department through the fire chief or a designee, issues sprinkler permits and inspects the work. Gas and wiring inspectors handle other trades, and the state building commissioner does not issue local sprinkler permits.
Question 6Massachusetts fire sprinkler statutes, regulations, and permitting requirements
Before a fire sprinkler system is placed in service, what must generally happen?
- The system must pass inspection and be accepted by the authority having jurisdiction Correct answer.
- The owner must obtain a variance from the state
- The contractor must file as-built drawings only
- The insurance carrier must issue a policy
Explanation
A new or altered sprinkler system must be inspected and accepted by the authority having jurisdiction before it is placed in service. Filing drawings or obtaining insurance may be required steps but do not substitute for inspection and acceptance.
Question 7Massachusetts fire sprinkler statutes, regulations, and permitting requirements
Which Massachusetts regulation contains the state's comprehensive fire prevention code, including provisions relevant to sprinkler systems?
- 248 CMR 10.00
- 780 CMR
- 527 CMR 1.00 Correct answer.
- 105 CMR 410.000
Explanation
527 CMR 1.00 is the Massachusetts Comprehensive Fire Safety Code, adopted by the Department of Fire Services. The other citations address plumbing, the building code, and minimum housing standards respectively.
Question 8Massachusetts fire sprinkler statutes, regulations, and permitting requirements
Which document is the Massachusetts State Building Code that governs building construction requirements, including when sprinklers are required by occupancy?
- 248 CMR 10.00
- 780 CMR Correct answer.
- 521 CMR
- 527 CMR 1.00
Explanation
780 CMR is the Massachusetts State Building Code and sets construction and occupancy requirements, including sprinkler thresholds. 527 CMR is the fire code, 248 CMR is plumbing, and 521 CMR covers architectural access.
Question 9Massachusetts fire sprinkler statutes, regulations, and permitting requirements
A contractor plans to install a sprinkler system in a building. Which set of plans and specifications typically must be submitted with the permit application?
- Only a one-page summary
- A verbal description given to the inspector
- Complete plans and specifications prepared in accordance with applicable codes Correct answer.
- A photograph of a similar building
Explanation
Permit applications must be accompanied by complete plans and specifications that demonstrate code compliance, including hydraulic and layout information. Summaries, photographs, or verbal descriptions do not provide the required technical basis for review.
Question 10Massachusetts fire sprinkler statutes, regulations, and permitting requirements
Who may generally prepare the working plans for a fire sprinkler system submitted for a Massachusetts permit?
- Only the property owner
- Only the general contractor
- A licensed fire sprinkler contractor or qualified designer acceptable to the authority Correct answer.
- Any building occupant
Explanation
Working plans are prepared by the licensed sprinkler contractor or a qualified designer acceptable to the authority having jurisdiction. Occupants, owners, or general contractors without sprinkler qualifications do not prepare these plans.
Question 11Massachusetts fire sprinkler statutes, regulations, and permitting requirements
A sprinkler contractor wants to begin installation before the permit is issued. What is the correct approach under Massachusetts permitting practice?
- Begin work and obtain the permit within 30 days
- Start work if the plans are already drawn
- Wait for the permit before starting permitted work Correct answer.
- Start work if the owner signs a waiver
Explanation
Permitted sprinkler work may not begin until the permit has been issued. Starting early, even with plans prepared or an owner waiver, does not satisfy the permit requirement.
Question 12Massachusetts fire sprinkler statutes, regulations, and permitting requirements
Which of the following best describes the role of the authority having jurisdiction during a sprinkler system final inspection?
- To verify the installation matches approved plans and applicable code Correct answer.
- To issue the contractor license
- To set the contract price for the work
- To design the system's hydraulics
Explanation
The authority having jurisdiction inspects to confirm the installation conforms to approved plans and code requirements. Pricing, hydraulic design, and contractor licensing are outside the inspection function.
Question 13Massachusetts fire sprinkler statutes, regulations, and permitting requirements
Under Massachusetts law, a person performing fire sprinkler work without the required license is subject to which of the following?
- Enforcement action and penalties under the licensing statute Correct answer.
- No consequence if the work passes inspection
- A warning only for a first offense
- Automatic licensure after the work is complete
Explanation
Unlicensed sprinkler work is subject to enforcement and penalties under the state licensing law, regardless of whether the installation later passes inspection. Passing inspection does not cure the licensing violation.
Question 14Massachusetts fire sprinkler statutes, regulations, and permitting requirements
Which of the following is a typical responsibility of the licensed fire sprinkler contractor of record on a permitted project?
- Ensuring work is performed by properly licensed personnel Correct answer.
- Setting the local fire alarm response plan
- Approving the building's occupancy classification
- Issuing the certificate of occupancy
Explanation
The contractor of record is responsible for ensuring the permitted work is performed by properly licensed journeypersons and apprentices under appropriate supervision. Occupancy approval, certificates of occupancy, and fire response planning belong to other parties.
Question 15Massachusetts fire sprinkler statutes, regulations, and permitting requirements
A journeyperson fire sprinkler license in Massachusetts authorizes the holder to do which of the following?
- Operate a sprinkler contracting business independently
- Certify occupancy of a completed building
- Approve sprinkler plans for the fire department
- Perform sprinkler work under a licensed contractor Correct answer.
Explanation
A journeyperson performs sprinkler work under a licensed fire sprinkler contractor. Operating a contracting business requires the contractor license, while plan approval and occupancy certification are governmental functions.
Question 16Massachusetts fire sprinkler statutes, regulations, and permitting requirements
An apprentice fire sprinkler fitter in Massachusetts must generally work under what condition?
- Supervision by any licensed tradesperson
- Direct supervision by a licensed journeyperson or contractor Correct answer.
- Supervision by the building owner
- No supervision once registered
Explanation
Apprentices must work under the supervision of a licensed journeyperson or contractor as required by the licensing program. Registration alone does not permit unsupervised sprinkler work, and supervision by unrelated tradespersons is not sufficient.
Question 17Massachusetts fire sprinkler statutes, regulations, and permitting requirements
Which of the following situations would most likely require a new or amended fire sprinkler permit?
- Replacing a sprinkler head with an identical listed head
- Painting the ceiling below existing sprinklers
- Adding sprinkler coverage to a newly finished room Correct answer.
- Changing the building's custodial service
Explanation
Adding coverage to a new room is an alteration of the system and requires a permit or amendment reflecting the changed scope. Like-for-like head replacement, cosmetic painting, and custodial changes do not generally add scope requiring a new permit.
Question 18Massachusetts fire sprinkler statutes, regulations, and permitting requirements
Massachusetts fire sprinkler licensing requirements are established primarily to serve which public purpose?
- Reducing the number of contractors
- Protecting public safety through qualified installation and maintenance Correct answer.
- Standardizing contractor advertising
- Increasing permit fee revenue
Explanation
Licensing exists to protect public safety by ensuring sprinkler systems are designed, installed, and maintained by qualified persons. Revenue, competition limits, and advertising are not the statutory purpose.
Question 19Massachusetts fire sprinkler statutes, regulations, and permitting requirements
Which standard is commonly referenced by Massachusetts codes as the installation standard for automatic sprinkler systems?
- NFPA 54
- NFPA 70
- NFPA 10
- NFPA 13 Correct answer.
Explanation
NFPA 13 is the standard for the installation of sprinkler systems and is referenced by the fire and building codes. NFPA 70 is the electrical code, NFPA 10 covers portable extinguishers, and NFPA 54 covers fuel gas.
Question 20Massachusetts fire sprinkler statutes, regulations, and permitting requirements
For a residential occupancy, which standard is typically referenced for the installation of residential sprinkler systems?
- NFPA 13R
- NFPA 20
- NFPA 13D Correct answer.
- NFPA 14
Explanation
NFPA 13D governs sprinkler systems in one- and two-family dwellings and manufactured homes. NFPA 13R applies to low-rise residential occupancies up to four stories, NFPA 14 covers standpipes, and NFPA 20 covers fire pumps.
Question 21Massachusetts fire sprinkler statutes, regulations, and permitting requirements
A contractor is unsure whether a proposed sprinkler modification requires a permit. What is the most appropriate action?
- Proceed because modifications are always exempt
- Contact the authority having jurisdiction before proceeding Correct answer.
- Wait until after installation to ask
- Assume the owner will handle permitting
Explanation
When permit applicability is unclear, the contractor should consult the authority having jurisdiction before starting work. Proceeding on an assumption or deferring to the owner risks unpermitted work and enforcement.
Question 22Massachusetts fire sprinkler statutes, regulations, and permitting requirements
Which of the following records should a licensed sprinkler contractor typically maintain for permitted work?
- Permit records, approved plans, and inspection documentation Correct answer.
- Only the original bid
- Marketing materials
- Employee timecards only
Explanation
Contractors should retain permit records, approved plans, and inspection documentation to demonstrate compliance and support future service. Bids, marketing materials, and timecards do not document code compliance.
Question 23Massachusetts fire sprinkler statutes, regulations, and permitting requirements
A building owner wants to change the use of a space in a way that increases its occupant load. What is the sprinkler contractor's most appropriate first step regarding code compliance?
- Wait for a fire to test the system
- Evaluate whether the new use triggers different sprinkler requirements Correct answer.
- Ignore it because the sprinkler system is unchanged
- Remove sprinklers to save cost
Explanation
A change of use or occupancy can trigger different sprinkler requirements under the building and fire codes, so the contractor should evaluate the new classification before proceeding. Ignoring the change, removing sprinklers, or waiting for an incident is inappropriate.
Question 24Massachusetts fire sprinkler statutes, regulations, and permitting requirements
Which entity typically maintains the official record that a licensed fire sprinkler contractor is in good standing?
- The property insurer
- The local library
- The contractor's bank
- The Department of Fire Services Correct answer.
Explanation
The Department of Fire Services maintains licensing records and can confirm whether a contractor is licensed and in good standing. Libraries, banks, and insurers do not maintain the official licensing record.
Question 25Massachusetts fire sprinkler statutes, regulations, and permitting requirements
A contractor completes a sprinkler installation and the authority having jurisdiction finds deficiencies at final inspection. What generally happens next?
- The permit is automatically voided permanently
- The deficiencies must be corrected and the work reinspected Correct answer.
- The system is accepted with no further action
- The contractor's license is immediately revoked
Explanation
Deficiencies identified at inspection must be corrected and the work reinspected before acceptance. Acceptance without correction, automatic permanent voiding of the permit, or immediate license revocation are not the standard outcome for correctable deficiencies.
Question 26Massachusetts fire sprinkler statutes, regulations, and permitting requirements
In Massachusetts, which state agency holds the primary statutory authority for administering and enforcing the fire safety code, including sprinkler provisions, at the state level?
- The Division of Insurance
- The Department of Public Health
- The Registry of Motor Vehicles
- The Department of Fire Services Correct answer.
Explanation
The Department of Fire Services, through its regulatory arm, administers and enforces the statewide fire safety code, including provisions affecting automatic sprinkler systems. Local fire departments enforce the code within their jurisdictions under that framework.
Question 27Massachusetts fire sprinkler statutes, regulations, and permitting requirements
A property owner is told that a sprinkler plan must be reviewed by the head of the fire department where the building is located. What is this local official commonly called in Massachusetts code language?
- The plumbing inspector
- The authority having jurisdiction Correct answer.
- The building commissioner
- The wiring inspector
Explanation
The local fire chief or designee serves as the authority having jurisdiction for fire safety matters, including review and inspection of sprinkler installations. Building, plumbing, and wiring officials have separate scopes of authority.
Question 28Massachusetts fire sprinkler statutes, regulations, and permitting requirements
Massachusetts fire sprinkler work is regulated at the state level through which type of legal instrument that establishes licensing categories and scope of practice?
- A voluntary trade association standard
- A statute enacted by the Legislature with implementing regulations Correct answer.
- A municipal ordinance adopted town by town
- A federal occupational safety rule
Explanation
Sprinkler licensing in Massachusetts rests on state statute, with detailed requirements carried out through regulations. Municipalities do not create their own sprinkler license categories, and trade standards or federal rules do not establish state licensure.
Question 29Massachusetts fire sprinkler statutes, regulations, and permitting requirements
A designer is preparing sprinkler drawings for a new commercial building in Massachusetts. Which code is the primary state document addressing fire prevention requirements that the sprinkler design must satisfy?
- The Massachusetts Plumbing Code
- The Massachusetts Electrical Code
- The Massachusetts Sanitary Code
- The Massachusetts Comprehensive Fire Safety Code Correct answer.
Explanation
The Massachusetts Comprehensive Fire Safety Code is the statewide fire prevention regulation and incorporates requirements affecting sprinkler systems. The electrical, plumbing, and sanitary codes govern unrelated disciplines.
Question 30Massachusetts fire sprinkler statutes, regulations, and permitting requirements
A contractor is installing a sprinkler system in a building where the local fire department has adopted local amendments stricter than the state baseline. Which requirements govern the installation?
- The building owner's written preference
- Only the state baseline, because local rules cannot affect sprinklers
- The stricter applicable local amendments, provided they are validly adopted Correct answer.
- Only the manufacturer's published installation instructions
Explanation
Where a municipality has validly adopted more stringent local requirements, those requirements apply in addition to the state code. State law allows local amendments that are at least as strict as the statewide baseline.
Question 31Massachusetts fire sprinkler statutes, regulations, and permitting requirements
Before a sprinkler contractor submits plans for a permit, the contractor discovers the building's occupancy classification may change. Why does occupancy classification matter for the sprinkler submittal?
- It controls the building's zoning district
- It determines the applicable design criteria and whether sprinklers are required Correct answer.
- It determines the property tax assessment
- It sets the contractor's license fee schedule
Explanation
Occupancy classification drives hazard classification, design density, and whether sprinkler protection is mandated, so it directly shapes the submittal. License fees, taxes, and zoning are governed by separate processes.
Question 32Massachusetts fire sprinkler statutes, regulations, and permitting requirements
A sprinkler contractor is asked to perform work in a municipality and wants to confirm the local fire department's permit process. What is the most appropriate first step?
- Rely on the general contractor to obtain all approvals
- Begin work and notify the fire department afterward
- Contact the local fire department to confirm its permit and inspection procedures Correct answer.
- Submit plans directly to the state agency and skip local review
Explanation
Permit procedures are administered locally, so confirming requirements with the local fire department before starting avoids noncompliant work. Working first and notifying later, bypassing local review, or shifting responsibility to another party are not acceptable.
Question 33Massachusetts fire sprinkler statutes, regulations, and permitting requirements
A building owner plans to install a new sprinkler system and asks who bears the responsibility for ensuring the installation complies with the approved plans. Who is responsible?
- The insurance carrier
- The licensed sprinkler contractor performing the work Correct answer.
- The equipment supplier
- The building's tenants
Explanation
The licensed contractor of record is accountable for installing in accordance with approved plans and applicable code. Suppliers, tenants, and insurers do not carry that installation responsibility.
Question 34Massachusetts fire sprinkler statutes, regulations, and permitting requirements
A contractor proposes to use an alternative sprinkler design approach that differs from the prescriptive code requirements. Under Massachusetts practice, what must generally occur before that approach is used?
- The contractor may proceed if the owner signs a waiver
- The supplier may certify the alternative without review
- The authority having jurisdiction must approve the alternative in writing Correct answer.
- The alternative is permitted whenever it costs less
Explanation
Alternatives to prescriptive requirements require approval by the authority having jurisdiction, typically documented, before installation. Owner waivers, supplier certification, or cost savings do not substitute for that approval.
Question 35Massachusetts fire sprinkler statutes, regulations, and permitting requirements
A contractor's license is suspended by the state. What is the effect on the contractor's ability to pull sprinkler permits and perform permitted sprinkler work during the suspension?
- The contractor may not perform permitted sprinkler work until the license is restored Correct answer.
- The contractor may continue work already under permit without restriction
- The contractor may perform work if the owner supervises
- The contractor may delegate the work to an unlicensed helper
Explanation
A suspended license removes the authority to perform or contract for sprinkler work, including work under existing permits, until reinstated. Continuing work, relying on owner supervision, or using unlicensed helpers does not cure the suspension.
Question 36Massachusetts fire sprinkler statutes, regulations, and permitting requirements
When a sprinkler installation is complete, which party typically conducts the inspection and issues approval that allows the system to be placed in service?
- The general contractor's safety officer
- The local authority having jurisdiction Correct answer.
- The equipment manufacturer
- The property insurer's agent
Explanation
The local authority having jurisdiction inspects the completed installation and approves it for service. Manufacturers, safety officers, and insurer agents do not hold that regulatory approval authority.
Question 37NFPA 13 automatic sprinkler system design and installation
Under NFPA 13, what is the minimum design density for a light hazard occupancy when using a density/area method?
- 0.05 gpm/ft²
- 0.20 gpm/ft²
- 0.10 gpm/ft² Correct answer.
- 0.15 gpm/ft²
Explanation
NFPA 13 density/area curves for light hazard begin at 0.10 gpm/ft² over 1,500 ft², with the density increasing as the design area decreases. The 0.05 gpm/ft² value is below the minimum permitted for any hazard class.
Question 38NFPA 13 automatic sprinkler system design and installation
What is the maximum allowable spacing between standard spray sprinklers on a branch line for a light hazard occupancy with unobstructed construction?
- 15 ft Correct answer.
- 12 ft
- 18 ft
- 20 ft
Explanation
For light hazard, standard spray sprinklers are limited to a maximum spacing of 15 ft on branch lines and a maximum protection area of 225 ft² per sprinkler. Larger spacings apply only to specific sprinkler types or higher densities.
Question 39NFPA 13 automatic sprinkler system design and installation
What is the minimum clearance required between the deflector of a standard upright or pendent sprinkler and the ceiling?
- 12 in
- 6 in
- 1 in Correct answer.
- 18 in
Explanation
NFPA 13 requires a minimum 1 in. clearance between the sprinkler deflector and the ceiling for standard spray sprinklers to allow the spray pattern to develop. Greater clearances are required only in special conditions such as combustible concealed spaces.
Question 40NFPA 13 automatic sprinkler system design and installation
Which component is required at the top of a riser to allow air to escape during filling?
- Automatic air vent Correct answer.
- Waterflow switch
- Pressure relief valve
- Check valve
Explanation
An automatic air vent releases trapped air from the top of the riser so that water fills the system properly and alarms and pressure readings remain accurate. Check valves prevent backflow, and relief valves limit overpressure.
Question 41NFPA 13 automatic sprinkler system design and installation
What is the minimum required diameter for a fire department connection supplying a sprinkler system?
- 6 in.
- 3 in.
- 4 in. Correct answer.
- 2 in.
Explanation
NFPA 13 requires the fire department connection to be at least 4 in. in size for sprinkler systems. Smaller connections cannot deliver the required supplementary flow from fire department pumpers.
Question 42NFPA 13 automatic sprinkler system design and installation
In a wet pipe system, what is the primary purpose of the alarm check valve?
- To drain the system after testing
- To regulate system pressure during filling
- To prevent water from flowing backward into the supply
- To sound the alarm when water flows into the system Correct answer.
Explanation
The alarm check valve is designed to allow water to flow into the system while directing flow to the alarm device when a sprinkler operates. It may also serve a check function, but its alarm-triggering role is the defining purpose.
Question 43NFPA 13 automatic sprinkler system design and installation
What is the minimum water supply duration required for a light hazard sprinkler system when using a density/area method?
- 90 minutes
- 30 minutes Correct answer.
- 45 minutes
- 60 minutes
Explanation
NFPA 13 requires a minimum 30-minute water supply duration for light hazard systems. Longer durations apply to higher hazard occupancies and certain storage arrangements.
Question 44NFPA 13 automatic sprinkler system design and installation
Which type of sprinkler is designed to be installed in a concealed space with the deflector below the ceiling surface?
- Concealed sprinkler Correct answer.
- Sidewall sprinkler
- Pendent sprinkler
- Upright sprinkler
Explanation
A concealed sprinkler uses a cover plate that hides the sprinkler body above the ceiling and drops free when the fusible element operates. Upright, pendent, and sidewall sprinklers are exposed below the ceiling.
Question 45NFPA 13 automatic sprinkler system design and installation
A light hazard occupancy has 1,600 ft² of floor area protected by standard spray sprinklers. What is the minimum number of sprinklers that must be provided if each protects no more than 225 ft²?
- 9
- 6
- 8 Correct answer.
- 7
Explanation
Dividing 1,600 ft² by the 225 ft² maximum protection area per sprinkler gives 7.11, which must be rounded up to 8 sprinklers. The maximum area per sprinkler governs the count rather than the actual layout.
Question 46NFPA 13 automatic sprinkler system design and installation
A branch line in an ordinary hazard occupancy is 84 ft long with sprinklers spaced 12 ft apart. How many sprinklers are on the branch line, assuming one is placed at each end?
- 7
- 6
- 9
- 8 Correct answer.
Explanation
With 84 ft of length and 12 ft spacing, the number of intervals is 84 ÷ 12 = 7, which means 8 sprinklers when one is at each end. The count is intervals plus one.
Question 47NFPA 13 automatic sprinkler system design and installation
What is the maximum allowable area of coverage per sprinkler for a light hazard occupancy using standard spray sprinklers?
- 300 ft²
- 130 ft²
- 200 ft²
- 225 ft² Correct answer.
Explanation
NFPA 13 limits standard spray sprinklers in light hazard to a maximum protection area of 225 ft² per sprinkler. This limit works together with the maximum spacing limits on branch lines and between lines.
Question 48NFPA 13 automatic sprinkler system design and installation
A designer must protect an ordinary hazard area of 3,000 ft² using a density of 0.20 gpm/ft². What is the minimum design flow required?
- 750 gpm
- 500 gpm
- 600 gpm Correct answer.
- 400 gpm
Explanation
Multiplying the density by the design area gives 0.20 gpm/ft² × 3,000 ft² = 600 gpm. The design area used must be at least the minimum required for the hazard and may be adjusted for the density/area curve.
Question 49NFPA 13 automatic sprinkler system design and installation
What is the maximum distance a sprinkler may be located from a wall in a light hazard occupancy with standard spray sprinklers?
- One-quarter the allowable spacing
- Equal to the allowable spacing
- Half the allowable spacing between sprinklers Correct answer.
- One-third the allowable spacing
Explanation
NFPA 13 requires sprinklers to be located no more than half the allowable spacing from a wall. This ensures the wall area receives adequate coverage and avoids dry spots near the perimeter.
Question 50NFPA 13 automatic sprinkler system design and installation
Which condition requires the installation of a dry pipe system rather than a wet pipe system?
- The occupancy is classified as light hazard.
- The protected space is subject to freezing temperatures. Correct answer.
- The water supply has high pressure.
- The building has a high ceiling.
Explanation
Dry pipe systems are used where piping may be exposed to freezing conditions, since the piping is normally filled with air or nitrogen and water enters only when a sprinkler operates. Wet pipe systems are preferred where freezing is not a concern.