Superheat
The difference between the actual suction-line temperature and the saturation temperature at the suction pressure; used to verify TXV or orifice performance and charge.
Subcooling
The difference between the saturation temperature at the condensing pressure and the liquid-line temperature; indicates liquid seal and charge condition at the condenser outlet.
TXV function
A thermostatic expansion valve modulates refrigerant flow to maintain a set evaporator superheat, responding to bulb temperature and evaporator pressure.
Sensible heat formula
Qs equals 1.08 times CFM times the dry-bulb temperature difference; used to calculate airflow or capacity at standard air conditions.
Latent heat formula
QL equals 0.68 times CFM times the moisture difference in grains per pound; used to size dehumidification and check latent capacity.
Manual J
ACCA residential load calculation method that estimates heating and cooling loads from envelope, orientation, infiltration, and internal gains.
Manual D
ACCA duct design method that sizes ducts using friction rate, equivalent length, and available static pressure from the equipment.
External static pressure
The total pressure the blower must overcome across the air handler, including filter, coil, supply, and return ductwork; must not exceed the equipment rating.
Combustion air rule
For indoor air, two permanent openings each sized at 1 square inch per 4,000 Btu/h of total appliance input; outdoor air through vertical ducts uses 1 per 2,000.
Category I venting
Negative-pressure, non-condensing appliances vented into a listed chimney or Type B vent sized per the gas code and the appliance listing.
Expansion tank
A tank that absorbs the volume increase of heated water in a hydronic system; pre-charged to system fill pressure and located near the circulator suction.
Zone valve
A motorized valve that opens or closes to direct hot water to a specific zone, controlled by a thermostat and wired to the zone control panel.
Motor branch circuit
Conductors sized at 125% of motor full-load current, with short-circuit protection sized from the nameplate or code tables.
MCA and MOP
Minimum circuit ampacity and maximum overcurrent protection printed on the equipment nameplate; wire and breaker must not exceed these values.
Disconnect location
The disconnecting means must be within sight of and within 50 feet of the motor or controller it serves.
Section 608 certification
EPA credential required to purchase, handle, or dispose of regulated refrigerants; types I, II, III, and Universal cover different equipment classes.
A2L refrigerant
A mildly flammable refrigerant class requiring ignition-source control, ventilation, and charge limits per ASHRAE 15/34 and equipment listing.
Recovery cylinder fill
Recovery cylinders are filled to 80% of capacity by weight unless equipped with a float switch and rated for liquid fill.
Venting prohibition
Intentional release of ozone-depleting refrigerant to the atmosphere is prohibited; recovered refrigerant must be recycled, reclaimed, or destroyed.
Duct gauge selection
Duct steel gauge is chosen by pressure class and duct size; typical residential trunks use 26-28 gauge and branches 28-30 gauge.
Pittsburgh seam
A folded lock seam used to join longitudinal duct edges; the flat pattern adds about 1/2 inch for the seam allowance.
Fire damper
A listed device installed where a duct penetrates a rated assembly to close on fire and maintain the assembly's fire-resistance rating.
Flex duct limits
Flexible duct must be fully extended, supported, and limited in length per manufacturer and code; it cannot be concealed where inspection is impossible.
Home Improvement Contractor
Massachusetts registration required for residential remodeling contracts; the registration number and cancellation notice must appear in the written contract.
Mechanic's lien
A statutory claim against property for unpaid labor or materials; Massachusetts requires notices and filing within deadlines measured from last furnishing.
Gross margin
Gross margin equals price minus cost divided by price; it differs from markup, which is cost times a percentage added to cost.
780 CMR
The Massachusetts State Building Code, which adopts and amends the model building code and includes energy and mechanical provisions for HVAC work.
248 CMR 5.00
The Massachusetts Gas Code regulating gas piping, appliance venting, combustion air, and pressure testing of gas systems.
Condensate disposal
Condensate must discharge through an approved air gap or trap to a receptor per the plumbing code; direct connection to a drain is restricted.
Fall protection threshold
OSHA requires fall protection in construction at 6 feet; guardrails, personal fall-arrest systems, or designated anchor points are acceptable.
Lockout/tagout
A procedure to isolate and verify zero energy state before servicing equipment; required for electrical and rotating HVAC components under OSHA rules.
Hot work permit
Authorization required before brazing or other open-flame work on many jobsites; a fire watch is maintained during and after the work.