Watershed protection
Land-use controls and buffer zones to prevent contaminants from entering source water, protecting public health and reducing treatment costs.
Sanitary survey
On-site inspection of water system to identify potential contamination risks and ensure compliance with regulations.
GWUDI
Groundwater under direct influence of surface water; requires additional treatment to meet surface water treatment rules.
Coagulation
Process of adding chemicals to destabilize particles and allow them to clump together for removal.
Flocculation
Gentle mixing to promote particle collisions and formation of larger floc particles for settling.
Sedimentation
Gravity settling of floc and particles in a basin; design based on surface overflow rate and detention time.
Filtration
Passing water through porous media to remove residual particles; monitored by turbidity and headloss.
Backwashing
Reverse flow of water through a filter to clean it; criteria include bed expansion and backwash rate.
CT concept
Disinfectant concentration multiplied by contact time; used to determine disinfection efficacy for pathogen inactivation.
Chlorine demand
Difference between applied chlorine dose and residual after contact time; must be satisfied before free residual appears.
Breakpoint chlorination
Point where chlorine demand is satisfied and free chlorine residual begins to increase, shown on a chlorination curve.
Trihalomethanes
Disinfection byproducts formed when chlorine reacts with natural organic matter; regulated with MCLs.
Haloacetic acids
Disinfection byproducts formed during chlorination; regulated with maximum contaminant levels.
UV disinfection
Inactivates pathogens by damaging DNA; does not provide residual; often used with chlorine.
Ozone disinfection
Strong disinfectant and oxidant; no residual; can form bromate in bromide-containing waters.
Turbidity
Measure of water clarity; regulatory limit typically 0.3 NTU in filtered water; monitored continuously.
DPD method
Common method for measuring chlorine residual using DPD indicator; results compared to color standards.
Bacteriological sampling
Testing for total coliform and E. coli; presence indicates potential contamination and triggers repeat sampling.
Chain of custody
Documentation tracking sample possession from collection to analysis; ensures legal defensibility.
Safe Drinking Water Act
Federal law governing public water systems; EPA sets national standards for drinking water quality.
Total Coliform Rule
Requires monitoring for total coliform; repeat sampling and corrective actions if positive.
Surface Water Treatment Rule
Requires filtration and disinfection for surface water systems; includes CT requirements.
Lead and Copper Rule
Requires corrosion control, monitoring, and public education if action levels exceeded.
Consumer Confidence Report
Annual report to customers summarizing water quality and compliance; required by EPA.
Public notification
Required for violations (e.g., MCL exceedance, monitoring failure) within specified timeframes.
Confined space entry
Requires permit, atmospheric testing, ventilation, attendant, and rescue plan; ensures safety.
Lockout/tagout
Isolate energy sources before maintenance; follow written procedures to prevent accidental startup.
Emergency response plan
Includes vulnerability assessment, communication, and coordination with local emergency services.
Flow rate formula
Q = V × A (velocity × cross-sectional area); units must be consistent (e.g., ft³/s, gpm).
Detention time
t = V / Q (volume divided by flow rate); convert units carefully to match.
Pressure and head
1 psi = 2.31 ft of water; head (ft) = pressure (psi) × 2.31.
Water horsepower
WHP = (Q (gpm) × head (ft)) / 3960; brake horsepower = WHP / efficiency.