MAWP
Maximum allowable working pressure is the highest pressure at the maximum allowable temperature that a boiler or vessel may legally operate, as stamped on its nameplate.
Fusible plug
A plug with a low-melting alloy installed at the lowest safe water level; when uncovered by water, it melts and releases steam to warn of low water.
Safety valve capacity
The safety valve must relieve at least the boiler's maximum steaming rate at a set pressure no higher than the maximum allowable working pressure.
Water column
A chamber connected to the boiler that stills water and holds gauge glass connections so the glass displays the true boiler water level.
Hydrostatic test
A pressure test using water, typically 1.5 times maximum allowable working pressure for a new ASME Section I boiler, to reveal leaks and weaknesses.
Stoichiometric combustion
Combustion with exactly the theoretical amount of air needed to burn all fuel, producing no excess oxygen and no unburned fuel.
Excess air
Air supplied above the theoretical amount; typical settings are about 15–20% for natural gas and 20–30% for fuel oil.
Furnace purge
A forced-air period of about 4–5 air changes before ignition that removes combustible gases from the furnace and flue passages.
Atomization
Breaking fuel oil into fine droplets so it mixes with air and burns cleanly; pressure, steam, or air atomizing burners perform this.
Turndown ratio
The maximum burner firing rate divided by the minimum stable firing rate; it shows how far a burner can reduce output without losing flame.
Low-water cutoff
A safety device that shuts off the burner when boiler water falls below the lowest safe level; steam boilers usually require manual reset.
Flame safeguard
A programmer and scanner system that proves pilot and main flame, controls purge and trial timing, and locks out fuel on flame failure.
Gauge glass blowdown
A procedure that clears the water gauge glass and connections: open drain, close lower and upper valves, then reopen to restore a true level.
Combustion analyzer
An instrument that measures oxygen, carbon monoxide, carbon dioxide, and stack temperature in flue gas to guide air-fuel tuning.
High-limit control
A safety control set above normal operating pressure or temperature that shuts down the burner if the operating control fails.
Cold boiler startup
Bring a cold boiler online slowly by checking water level, venting air, purging the furnace, and warming tubes and drums gradually to avoid thermal stress.
Water hammer
A shock caused by steam pushing a slug of condensate through piping; drain lines and open valves slowly to prevent it.
Bottom blowdown
Blowing water from the lowest point to remove sludge and suspended solids; do it at low firing rate and open the valve slowly.
Emergency shutdown
Stop fuel and burner immediately, close the main steam stop, and do not feed water to a boiler that has been overheated or lost water.
Normal shutdown
Reduce load, stop the burner, purge the furnace, and keep the boiler under observation with proper water level while it cools gradually.
Scale
A hard deposit of calcium and magnesium salts on boiler tubes that insulates metal, raises stack temperature, and can cause overheating.
Dissolved oxygen
Oxygen in feedwater that causes pitting corrosion; deaeration and an oxygen scavenger are used to remove it.
Boiler water pH
A measure of alkalinity; boiler water is typically held near 10.5–12 to limit corrosion, while excessive alkalinity can cause caustic attack.
TDS
Total dissolved solids; high TDS causes foaming and carryover, so it is controlled by surface blowdown and monitored by testing.
Ion-exchange softener
A vessel that exchanges calcium and magnesium for sodium to remove hardness; brine regeneration restores the resin's exchange capacity.
Wet layup
Storing a boiler filled with treated water and an oxygen scavenger to prevent corrosion during an outage.
Maine boiler program
Maine's boiler and pressure vessel safety program is administered by the Office of the State Fire Marshal and adopts ASME and National Board codes.
Certificate of inspection
A document showing that a boiler or pressure vessel has passed the required inspection; it must be current and posted at the equipment.
Licensed boiler operator
A person licensed by the state boiler program to operate boilers that Maine rules classify as requiring a licensed operator.
Accident reporting
Explosions, failures, or dangerous conditions must be reported to the boiler inspector, and operation may not resume until released.
NBIC repairs
Repairs and alterations to pressure parts must follow the National Board Inspection Code and be documented; uncertified welding is prohibited.
Operator log
A record kept by the operator of water level, pressure, temperature, blowdown, tests, and unusual conditions; it documents that required checks were performed.