ME Fire Alarm study materials
ME Fire Alarm study resources

ME Fire Alarm flashcards

ME Fire Alarm · Build recall with a focused review session.

32 cards. Read the term and the definition here. The deck at the top of this page is optional.

Class A pathway
A signaling circuit with redundant paths that continues to operate all devices after a single open, ground, or short fault, and must be monitored for these faults.
Class B pathway
A signaling circuit with a single path where one fault causes loss of that portion; must be monitored for opens and, for initiating circuits, for shorts.
PLFA cable marking
Power-limited fire alarm cable is marked FPLP for plenum, FPLR for riser, and FPL for general use; these listings are required in fire alarm systems.
NPLFA wiring method
Non-power-limited fire alarm circuits must follow Chapter 3 wiring methods, typically in metal raceway, and cannot share a raceway with PLFA without a barrier.
Article 800 separation
Communications conductors must be separated from power conductors by at least 2 inches (50 mm) or a barrier, and cannot share a raceway with Class 1 or power circuits.
Smoke detector spacing
On smooth ceilings, spot-type smoke detectors are spaced no more than 30 feet (9.1 m) apart and within 21 feet (6.4 m) of any wall.
Heat detector spacing
Fixed-temperature heat detectors are spaced no more than 50 feet (15.2 m) on smooth ceilings and within 25 feet (7.6 m) of walls.
Pull station location
Manual pull stations must be within 5 feet (1.5 m) of each exit door, mounted 42 to 48 inches above the floor, with at least one per floor.
Duct detector threshold
Duct smoke detectors are required for air handling systems with a capacity greater than 2,000 cfm and are installed in the return air duct.
Public mode audibility
Audible alarms in public mode must be at least 15 dBA above ambient, measured 5 feet above the floor, with a minimum of 65 dBA in occupied areas.
Private mode audibility
In sleeping rooms and patient rooms, alarms must be at least 10 dBA above ambient or 75 dBA minimum, measured at the pillow level.
Visible appliance mounting
Visible notification appliances are mounted 80 to 96 inches above the finished floor, and corridor spacing is 15 feet maximum between appliances.
Temporal-3 pattern
The standard evacuation signal: three 0.5-second pulses separated by 0.5-second off periods, followed by a 1.5-second pause, repeated.
Annual ITM requirement
All initiating devices, notification appliances, and control equipment must be inspected and tested at least annually, with results documented in writing.
Battery capacity test
Sealed lead-acid batteries must deliver at least 70 percent of rated capacity after the calculated standby and alarm load, tested annually.
Record of completion
A document completed at system acceptance listing the system description, device inventory, and installer certification, required by NFPA 72.
Central station redundancy
A central station must have at least two independent means of communication, such as two phone lines or a phone line plus a radio path.
Alarm transmission time
Automatic alarm to notification must occur within 10 seconds; transmission to a supervising station within 60 seconds; proprietary station within 90 seconds.
Voice intelligibility
Emergency voice systems must achieve a Speech Transmission Index of at least 0.50 in occupied areas to be considered intelligible.
Occupant load factor
Floor area divided by the occupant load factor: 100 ft² per person for business, 15 ft² for unconcentrated assembly, 5 ft² for concentrated assembly.
Egress width factor
Means of egress width is 0.2 inch per person on level components and 0.3 inch per person on stairs, or less in sprinklered buildings.
Two-exit threshold
Two exits are generally required when the occupant load exceeds 49 persons or when travel distance exceeds the single-exit limit.
R-2 smoke alarms
Group R-2 residential occupancies require smoke alarms in each sleeping room and outside each sleeping area, plus corridor detection.
Maine alarm contractor license
Maine requires a Fire Alarm Systems Contractor license from the State Fire Marshal, with individual technician licensing and continuing education for renewal.
Maine plan review
Fire alarm plans must be submitted to the State Fire Marshal or local AHJ for review before installation in most commercial occupancies.
Maine certificate of completion
After installation and testing, a certificate of completion must be filed with the AHJ, and the AHJ must be notified before testing.
Battery sizing formula
Required capacity equals (standby current times standby hours plus alarm current times alarm hours) multiplied by 1.25 for derating.
Standby power duration
NFPA 72 requires 24 hours of standby followed by 5 minutes of alarm for commercial systems, or 4 hours standby with a backup generator.
Voltage drop formula
Voltage drop equals (2 times K times current times one-way length) divided by circular mils, where K is 12.9 for copper conductors.
Cable support spacing
Power-limited fire alarm cable must be supported at intervals not exceeding 4.5 feet (1.4 m) and within 12 inches of boxes.
NAC current budget
The total current of all notification appliances on a circuit must not exceed the circuit rating, and voltage at the last device must meet its minimum.
Supervisory signal priority
Alarm signals have highest priority, followed by supervisory signals, then trouble signals; supervisory signals must annunciate within 90 seconds.