- NEC box fill counting
- Each 14, 12, or 10 AWG conductor counts as one volume; each device yoke counts as two; each clamp counts as one; all grounding conductors together count as one.
- Working clearance depth
- NEC 110.26 requires 3 ft of depth for equipment up to 150 V to ground, 4 ft for 151 to 600 V, and 5 ft above 600 V where live parts are exposed on both sides.
- GFCI requirement locations
- NEC 210.8 requires GFCI protection for dwelling bathroom, garage, outdoor, unfinished basement, kitchen countertop, and within 6 ft of sink receptacles, among other locations.
- Equipment grounding conductor sizing
- NEC Table 250.122 sizes the equipment grounding conductor by the rating of the overcurrent device protecting the circuit, not by the ungrounded conductor size.
- Conductor ampacity correction
- Table 310.16 base ampacity is multiplied by the ambient temperature correction factor and by the adjustment factor for more than three current-carrying conductors in a raceway.
- Maine license classes
- Maine issues master, journeyman, and limited electrician licenses plus apprentice registration; each class has a defined scope, and limited licenses cover only named categories.
- Low-energy license scope
- Maine low-energy work covers circuits operating at 50 volts or less and limited-energy systems; line-voltage power wiring requires a journeyman or master license.
- Maine continuing education
- Maine requires continuing education hours per renewal cycle, including code-update content; the exact hours and cycle length are set by Board rule and should be verified.
- Apprentice supervision rule
- A Maine apprentice must be registered with the Board and work under the direct supervision of a licensed master or journeyman; the apprentice may not work unsupervised.
- Permit before electrical work
- A permit is required before installing, altering, or extending electrical wiring; fees and inspection scheduling are set by the local code enforcement officer or state inspector.
- Rough-in versus final inspection
- Rough-in inspection occurs after boxes and raceways are installed but before concealment; final inspection occurs after devices, fixtures, and panel labeling are complete.
- Stop-work order effect
- An inspector may issue a stop-work order for unpermitted or unsafe work; work stops until the defect is corrected, and appeals go to the local board of appeals.
- Utility service standards
- Service conductors, meter sockets, and point-of-delivery rules are set by the serving utility's published standards, which are enforceable in addition to the NEC.
- Ohm's law and power
- V equals I times R; power P equals V times I, also I squared times R or V squared divided by R. A 1,500 W load at 120 V draws 12.5 A.
- Series versus parallel circuits
- In series, current is common and voltage divides and resistances add; in parallel, voltage is common, current divides, and total resistance is below the smallest branch.
- Three-phase power formula
- For a balanced three-phase load, P equals 1.732 times line voltage times line current times power factor; single-phase power is voltage times current times power factor.
- Circular mils formula
- Circular mils equal the conductor diameter in mils squared; 12 AWG is 6,530 CM, 10 AWG is 10,380 CM, and 8 AWG is 16,510 CM.
- Bonding versus grounding
- Bonding connects metal parts to create an equipotential fault-current path; grounding connects the system to earth. Bonding clears faults, not the earth connection.
- Dwelling receptacle spacing
- NEC 210.52(A) requires receptacles so that no point along the floor line in any wall space is more than 6 ft from a receptacle.
- Kitchen countertop receptacle spacing
- NEC 210.52(C) requires countertop receptacles so no point along the wall line is more than 24 in from a receptacle, with one required per island or peninsula.
- Small-appliance branch circuits
- At least two 20 A small-appliance branch circuits are required for dwelling kitchen, dining, pantry, and similar areas, and they may not supply lighting outlets.
- NM cable support intervals
- Nonmetallic-sheathed cable must be secured within 12 in of boxes and at intervals not exceeding 4.5 ft along the run, per NEC 334.30.
- Master electrician authority
- A Maine master electrician may contract for and supervise electrical work; a journeyman performs electrical work under a master's supervision.
- Lapsed license practice
- Practicing on a lapsed Maine license is a violation; reinstatement may require a fee and proof of continuing education before the license is restored.
- Board disciplinary authority
- The Electricians' Examining Board may investigate complaints, hold hearings under the Maine Administrative Procedure Act, and impose fines, suspension, or revocation.
- Underground feeder depth
- NEC Table 300.5 requires 24 in for direct-buried residential branch circuits at 120/240 V, 18 in for GFCI-protected 120 V residential circuits, and 18 in under concrete.
- Available fault current marking
- NEC 110.24 requires service equipment to be field-marked with the available fault current and the date the calculation was performed.
- Construction site GFCI
- NEC 590.6 requires GFCI protection for all 125 V receptacles used on construction sites, and a separate temporary service permit may be required locally.
- Voltage divider rule
- In a series circuit, the voltage across a resistor equals the source voltage times that resistance divided by total resistance; this explains dimming from a loose neutral.
- Megohmmeter insulation test
- Insulation resistance is measured with a megohmmeter at a test voltage above the circuit rating; readings below 1 megohm generally indicate moisture or damaged insulation.
- Main bonding jumper
- NEC 250.28 requires a green screw or listed strap sized by Table 250.102(C)(1) connecting the grounded service conductor to the service equipment enclosure.
- Grounding electrode conductor sizing
- NEC Table 250.66 sizes the grounding electrode conductor from the largest ungrounded service conductor and never requires more than 3/0 copper or 250 kcmil aluminum.
- Weather-resistant receptacles
- NEC 406.9 requires listed weather-resistant receptacles in wet outdoor locations with an enclosure that maintains the rating while a cord is plugged in.
- Three-way switch common
- A three-way switch has one common terminal and two travelers; the common is marked by a different-colored screw and connects to the supply or the fixture leg.