MI Boiler Operator flashcards
MI Boiler Operator · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- ASME Section I scope
- Covers power boilers and high-temperature water boilers exceeding 15 psig steam or 160 psig water, including their appurtenances, and sets construction, material, and stamping requirements.
- ASME Section IV scope
- Covers heating boilers limited to 15 psig steam and 160 psig water at 250 degrees Fahrenheit, plus potable water heaters and related controls and relief devices.
- MAWP definition
- Maximum allowable working pressure is the highest pressure at which the weakest pressure part of the boiler may lawfully operate, based on design thickness and material strength.
- Hydrostatic test pressure
- For new construction the hydrostatic test is generally 1.5 times the maximum allowable working pressure, with air vented, safety valves isolated, and all joints visible for leak inspection.
- Firetube vs watertube
- In a firetube boiler hot gases pass through tubes surrounded by water; in a watertube boiler water passes through tubes surrounded by hot gases, allowing higher pressure and faster response.
- Bottom blowdown purpose
- Bottom blowdown discharges water from the lowest point to remove sludge and suspended solids, and is performed as short frequent blows with the burner firing only as permitted.
- Surface blowdown purpose
- Surface or continuous blowdown draws water from the steam-water interface to control dissolved solids, alkalinity, and foaming, with rate set by conductivity or chloride testing.
- Low-water cutoff test
- The low-water fuel cutoff is tested with the burner firing to confirm it shuts off fuel, not just alarms, and that the water column and gauge glass connections are clear.
- Warm-up thermal stress
- A cold boiler is warmed with limited firing rate so shell, tube sheet, and drum temperatures rise gradually, avoiding differential expansion that cracks seams and tube joints.
- Water hammer cause
- Water hammer is the banging caused by steam contacting accumulated condensate; drip legs, traps, and draining lines during warm-up prevent it and protect piping and fittings.
- Safety valve pop test
- A pop test verifies the safety valve opens at its set pressure and reseats; the valve is lifted by raising boiler pressure under controlled conditions and the result is logged.
- Flame failure response
- On loss of the flame signal the flame safeguard must close the fuel valves within the code flame-failure response time and require a full purge before any restart attempt.
- Trial for ignition
- The trial for ignition is the limited time the pilot or main burner may receive fuel while proving flame; exceeding it without a signal requires fuel shutoff and purge.
- Pre-purge requirement
- Before ignition, the furnace and passes are purged with air at the required flow for a set time to clear combustible gases, preventing furnace explosion on lightoff.
- Operating vs limit control
- Operating controls modulate firing within the normal range; limit controls are independent high-limit devices set above operating range and below safety valve setpoint to force shutdown.
- Combustion air proving switch
- A pressure or flow switch proves combustion air before and during firing, interlocked with the programmer so no fuel can enter the furnace without adequate airflow.
- Gauge glass blowdown
- Blowing the gauge glass confirms both upper and lower connections are open; a closed connection gives a false level and can hide a dangerous low-water condition.
- NBIC R-stamp
- The National Board Inspection Code governs in-service repairs and alterations; an R-stamp holder is authorized to repair or alter pressure parts and register the work.
- ASME CSD-1 purpose
- CSD-1 sets requirements for controls and safety devices on automatically fired boilers, covering flame safeguard, low-water cutoff, and limit controls, and is often adopted locally.
- NFPA 85 scope
- NFPA 85 addresses combustion system hazards for boilers over 12.5 million Btu per hour, covering fuel trains, purge, interlocks, and furnace explosion prevention.
- National Board registration
- Boilers built to ASME code are registered with the National Board and stamped with the code symbol and registration number, enabling traceable inspection history.
- Jurisdictional authority
- State or local boiler inspection authorities set operating certificate requirements, inspection intervals, and operator licensing, which may exceed but cannot relax ASME construction rules.
- Stoichiometric methane reaction
- Complete combustion of methane is CH4 plus 2 O2 giving CO2 plus 2 H2O; theoretical air is about 9.5 pounds of air per pound of natural gas.
- Excess air and O2
- Excess air beyond theoretical ensures complete combustion; for natural gas about 15 percent excess air corresponds to roughly 3 percent oxygen in the flue gas.
- Three T's of combustion
- Temperature, turbulence, and time must all be sufficient; short residence time, poor mixing, or low temperature produces carbon monoxide and smoke instead of complete combustion.
- Draft definition
- Draft is the small pressure difference that moves combustion air into the furnace and flue gases out the stack, produced by stack effect or by forced or induced draft fans.
- Gas train order
- A typical gas train runs manual shutoff, regulator, low and high gas pressure switches, safety shutoff valves, and a leak test valve, all listed and sized for firing rate.
- Combustion analyzer tuning
- Firing rate is set at low, mid, and high fire using an analyzer; oxygen, carbon monoxide, and stack temperature confirm safe, efficient air-fuel ratio at each point.
- Scale formation cause
- Scale is precipitated calcium and magnesium hardness baked onto heating surfaces; it insulates tubes, raises metal temperature, and leads to overheating and tube failure.
- Deaerator function
- A deaerator heats feedwater and strips dissolved oxygen and carbon dioxide to limit corrosion; an oxygen scavenger such as sodium sulfite removes the remainder.
- Cycles of concentration
- Cycles of concentration express how many times makeup solids are concentrated in boiler water; blowdown is adjusted to hold dissolved solids below the established limit.
- Caustic embrittlement
- Caustic embrittlement is stress-corrosion cracking of stressed seams from concentrated alkaline boiler water; controlled pH, alkalinity, and phosphate treatment plus good circulation limit it.