NFPA 72
The National Fire Alarm and Signaling Code, which establishes minimum requirements for the design, installation, testing, and maintenance of fire alarm systems.
Addressable system
A fire alarm system in which each initiating or notification device has a unique address, allowing the control unit to identify the specific device in alarm or trouble.
Conventional system
A fire alarm system that groups devices into zones; the control unit annunciates the zone rather than the individual device, and devices are not individually addressed.
Class A circuit
A supervised circuit that survives a single open or ground fault because it returns to the control unit; it does not require an end-of-line device.
Class B circuit
A supervised circuit that does not return to the control unit and requires an end-of-line device; a single open fault may disable part of the circuit.
Supervisory signal
A signal indicating a condition that could impair the ability of the fire alarm system to operate, such as a valve tamper or a circuit trouble.
Smoke detector spacing
On a smooth ceiling, smoke detectors are spaced at 30 ft (9.1 m) intervals, with the first detector within 15 ft (4.6 m) of any wall or partition.
Heat detector spacing
For ordinary temperature-rated heat detectors on a smooth ceiling, spacing is 50 ft (15.2 m), with the first detector within 25 ft (7.6 m) of any wall.
Pull station mounting height
Manual fire alarm pull stations must be mounted 42 to 48 inches (1.07 to 1.22 m) above the finished floor, within 5 ft (1.5 m) of the exit door.
Battery backup sizing
Calculate standby current times required standby hours plus alarm current times required alarm minutes, then add a 20% aging factor to determine battery capacity.
Plenum-rated cable
Fire alarm cable listed for use in environmental air spaces (plenums), such as FPLP, required by NEC Article 760 when installed in those spaces.
End-of-line device
A resistor or other device installed at the end of a Class B circuit that allows the control unit to supervise the circuit for opens and shorts.
Ionization smoke detector
A smoke detector that uses a radioactive source to ionize air and responds best to small, fast-flaming fires with little visible smoke.
Photoelectric smoke detector
A smoke detector that uses a light source and sensor to detect scattered light and responds best to smoldering fires with larger smoke particles.
Duct smoke detector
A detector installed in an HVAC duct to sample airflow and initiate an alarm or supervisory signal; required for systems over 2,000 cfm per NFPA 90A.
Signaling line circuit
The circuit that connects addressable devices to the fire alarm control unit and carries digital communication for individual device status and control.
Waterflow switch
A supervisory device that detects water flow in a sprinkler system and initiates an alarm signal at the fire alarm control unit when flow occurs.
Valve tamper switch
A supervisory device that monitors the position of a sprinkler control valve and initiates a supervisory signal when the valve is not fully open.
Detector sensitivity testing
A test required by NFPA 72 to verify that smoke detectors operate within their listed sensitivity range; typically performed annually and after cleaning.
Audible notification level
Audible appliances must produce at least 15 dBA above ambient or 5 dBA above the maximum sound lasting 60 seconds, whichever is greater, measured at 10 ft.
Sleeping area audibility
In sleeping areas, alarm sound must be at least 75 dBA at the pillow or 15 dBA above ambient, whichever is greater, with a minimum of 75 dBA.
Strobe synchronization
Visible notification appliances in the same field of view must flash in synchronization to prevent seizure hazards, as required by NFPA 72 and ADA.
Strobe candela rating
The intensity of a visible notification appliance, selected based on room size and mounting height per NFPA 72 tables to ensure adequate visibility.
Voice evacuation system
A notification system that delivers voice messages; it must meet intelligibility and audibility requirements of NFPA 72 for the occupied space.
ADA visible alarm requirement
The Americans with Disabilities Act requires visible alarm notification in public and common areas of covered occupancies and in certain sleeping rooms.
Notification appliance circuit
A supervised circuit that supplies power to notification appliances; it must be calculated for voltage drop and not exceed the power supply rating.
Annual device testing
NFPA 72 requires annual functional testing of initiating devices and notification appliances, including verification of alarm annunciation at the control unit.
Battery inspection frequency
Batteries must be inspected monthly for corrosion and terminal tightness, load tested annually, and replaced per manufacturer recommendations, often every 4 to 5 years.
Waterflow switch testing
Waterflow switches must be tested semiannually (or quarterly per some codes) by opening the test valve to verify alarm initiation at the control unit.
Pre-test notification
Before testing, the monitoring company and building occupants must be notified to prevent false alarms and unnecessary emergency response.
Minnesota fire alarm license
A credential issued by the Minnesota State Fire Marshal Division that authorizes an individual or contractor to install, modify, or service fire alarm systems.
Minnesota plan review
Fire alarm system plans must be submitted to the State Fire Marshal or local AHJ for review and approval before installation, with fees set by rule.