Minnesota Low Voltage Practice flashcards
Minnesota Low Voltage Practice · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Ohm's law
- Current equals voltage divided by resistance (I = E/R). Power equals voltage times current (P = E × I). In AC circuits, impedance Z replaces resistance R for reactive loads.
- Three-phase power formula
- For a balanced three-phase load, real power P = √3 × line voltage × line current × power factor. Single-phase power is E × I × PF.
- Voltage drop formula
- Single-phase two-wire voltage drop ≈ 2 × K × I × L ÷ circular mils, where K is about 12.9 for copper. NEC recommends total drop of 5% or less.
- Series circuit
- A circuit with only one path for current. Current is the same through every element, resistances add, and voltage divides in proportion to resistance.
- Parallel circuit
- A circuit with multiple current paths. Voltage is the same across each branch, conductances add, and total resistance is less than the smallest branch resistance.
- Minnesota electrical licensing authority
- The Minnesota Department of Labor and Industry administers electrical licensing under Minn. Stat. ch. 326B and Minn. R. ch. 3800, including exams, permits, and inspections.
- Minnesota continuing education requirement
- Master and journeyman electricians must complete 16 hours of continuing education per two-year renewal cycle, including required code-update hours.
- Minnesota license classes
- Minnesota issues master, journeyman, maintenance electrician, and registered unlicensed electrician credentials, each with a defined scope of work and supervision requirements.
- Listed versus labeled
- Listed means equipment has been evaluated by a nationally recognized testing laboratory. Labeled means it bears the listing mark. Approved means acceptable to the AHJ.
- NEC Article 90 scope
- Article 90 states that the NEC is a minimum safety standard, not a design manual. Chapters 1–4 apply generally; Chapters 5–7 modify or supplement.
- Working space requirements
- NEC 110.26 requires defined depth, width, and height of clear working space in front of electrical equipment, based on voltage and the condition of the location.
- Box fill calculation
- NEC 314.16 counts conductors, clamps, devices, and equipment grounding conductors, then applies Table 314.16(B) volume allowances to determine required box volume.
- NM-B cable restrictions
- Nonmetallic sheathed cable is permitted in dry locations only. It is prohibited in wet locations, where exposed to physical damage, and in most commercial occupancies.
- EMT support spacing
- Electrical metallic tubing must be supported within 3 ft of each box and at intervals not exceeding 10 ft, per NEC Article 358.
- Firestop requirements
- Cable and raceway penetrations of fire-rated assemblies must be sealed with a listed firestop system matching the tested assembly, restoring the assembly's fire rating.
- Class 2 circuit definition
- A circuit limited to 100 VA or less that is generally exempt from Chapter 3 wiring methods when installed per NEC Article 725.
- Class 2 separation rule
- Class 2 and 3 conductors must be separated from power conductors by at least 2 in. or a barrier, unless the cable is listed for the combined use.
- Low-voltage lighting limit
- NEC Article 411 covers lighting systems limited to 30 V and 25 A per circuit, supplied by a listed power source.
- Grounding electrode resistance
- NEC 250.53 requires a grounding electrode system resistance of 25 ohms or less. If greater, a second electrode must be installed.
- Main bonding jumper
- The main bonding jumper connects the equipment grounding conductor to the service neutral at the service equipment. It must be removed for separately derived systems.
- Overcurrent device selection
- Per NEC 240.4, the overcurrent device rating must not exceed the conductor ampacity, except where the next-size-up rule in 240.4(B) applies.
- Fire alarm cable listings
- Fire alarm cable must be listed FPL, FPLR, or FPLP. FPLP is required in plenums and air-handling spaces; FPLR is riser-rated.
- Smoke detector spacing
- NFPA 72 requires spot-type smoke detectors on smooth ceilings to be spaced no more than 30 ft apart, with adjustments for ceiling height and beam pockets.
- Manual pull station location
- NFPA 72 requires manual pull stations within 5 ft of each exit door, mounted 42–48 in. above the floor to the operating handle.
- Communications cable listings
- Communications cable must be listed CM, CMR, CMP, or CMX depending on location. CMP is required in plenums and air-handling spaces.
- Primary protector requirement
- Communications conductors entering a building and exposed to lightning or power contact must have a listed primary protector installed per NEC Article 800.
- PoE installation considerations
- Power over Ethernet installations must consider cable ampacity, bundling, and temperature. NEC Articles 725 and 800 apply to the low-voltage cabling.
- Arc flash boundary
- The arc flash boundary is the distance at which incident energy equals 1.2 cal/cm². Inside it, arc-rated PPE is required per NFPA 70E.
- Hierarchy of risk control
- NFPA 70E orders controls as elimination, substitution, engineering controls, awareness, administrative controls, and PPE as the last line of defense.
- Lockout/tagout procedure
- Before work on de-energized equipment, apply locks and tags, release stored energy, and verify absence of voltage with a tester rated for the circuit.
- Panel schedule purpose
- A panel schedule lists circuit numbers, breaker sizes, conductor sizes, and connected loads, and is used to verify load calculations and spare capacity.
- As-built drawings
- As-built drawings reflect field changes made during construction and are submitted before final inspection for future maintenance and code compliance.