MAWP
Maximum allowable working pressure is the highest pressure at which a boiler may be operated; it is stamped on the nameplate and set by the thinnest pressure part at design temperature.
Joint efficiency
A factor in shell thickness formulas that accounts for the strength of welded seams; it is 1.0 for seamless or fully radiographed seams and lower for partially inspected welds.
Lowest permissible water level
The lowest water level at which a boiler may be safely operated; the gauge glass and low-water cutoff must be arranged so this level is visible and protected.
Staybolt
A threaded rod connecting opposite flat plates of a boiler to resist pressure loads; its diameter and pitch are sized so the load per bolt stays within allowable stress.
Fusible plug
A plug with a low-melting alloy core installed in a firetube boiler; it melts when the tube is uncovered, releasing steam as a warning of low water.
Safety valve
A pressure-relief device that opens at set pressure and reseats after blowdown; its capacity must equal or exceed the boiler's maximum evaporating capacity.
Low-water fuel cutoff
A safety control that shuts off the burner before the water level drops below the lowest permissible level; it is not an operating control and must be tested regularly.
Water column
A chamber connected to the boiler that supports the gauge glass and low-water cutoff; its connections must be at least 1 inch and must be blown down to prevent plugging.
Flame scanner
A UV or IR sensor that proves main flame within the trial-for-ignition period; loss of signal closes the fuel valve within 4 seconds or less on small burners.
High-pressure limit switch
A safety control that shuts down the burner at a pressure below the safety valve set pressure, preventing the valve from lifting during normal operation.
Economizer
A heat recovery device that preheats feedwater using flue gas; it improves efficiency and must have a bypass for startup and low-flow protection.
Excess air
Air supplied above the theoretical amount needed for complete combustion; typical values are 15-20 percent for gas and 20-30 percent for oil firing.
Stoichiometric combustion
Combustion with exactly the theoretical air required; for methane it is CH4 + 2O2 producing CO2 and water, with no excess oxygen remaining.
Trial for ignition
The timed period during which the burner may attempt to establish flame; if the flame scanner does not prove flame, the fuel valve closes and a lockout occurs.
Purge
A flow of air through the furnace and flue before ignition to remove unburned fuel; typically four to five air changes are required to prevent explosive accumulation.
Turndown ratio
The maximum firing rate divided by the minimum stable firing rate of a burner; a high turndown reduces cycling and improves efficiency at part load.
LEL
The lower explosive limit is the minimum fuel concentration in air that will ignite; methane's LEL is about 5 percent by volume, and meters read in percent LEL.
Deaerator
A device that heats feedwater to saturation temperature at its pressure and vents released gases, removing oxygen and carbon dioxide that cause corrosion.
Oxygen scavenger
A chemical such as sulfite added to feedwater to remove residual dissolved oxygen; a residual of about 20-40 ppm is maintained in the boiler water.
Blowdown
The controlled removal of boiler water to limit dissolved solids and sludge; the rate is set by the allowable TDS and the feedwater TDS.
Scale
A hard deposit of calcium and magnesium salts on heat transfer surfaces; it insulates the surface, raises fuel consumption, and can cause overheating.
Water softener
An ion exchange unit that replaces calcium and magnesium with sodium; it is regenerated with salt brine, and hardness leakage indicates resin exhaustion.
Hydrostatic test
A pressure test with water at typically 1.25 to 1.5 times MAWP for in-service boilers; the boiler is held at test pressure and inspected for leaks.
Ultrasonic thickness testing
A non-destructive method that measures wall loss from corrosion and erosion; readings are compared to the minimum required thickness for the pressure part.
Magnetic particle testing
A non-destructive method that detects surface and near-surface cracks in ferromagnetic materials by attracting magnetic particles to flux leakage at defects.
ASME Section I
The section of the ASME Boiler and Pressure Vessel Code that governs power boilers, including design, materials, and required safety valves.
ASME Section IV
The section of the ASME Boiler and Pressure Vessel Code that governs heating boilers; it covers construction and required safety devices for low-pressure heating units.
NBIC
The National Board Inspection Code governs in-service inspection, repairs, and alterations of boilers and pressure vessels; it is often adopted by the authority having jurisdiction.
Authority having jurisdiction
The regulatory body that enforces boiler codes, sets inspection intervals, and issues operating permits and operator certifications.
Lockout/tagout
A procedure that isolates and locks energy sources before maintenance; stored steam and water energy must be released and verified before work begins.
Confined space entry
Entry into a boiler or vessel requires atmospheric testing for oxygen and combustibles, ventilation, and an attendant stationed outside the space.
Fired-dry boiler
A boiler that has lost water while firing; water must never be added until it has cooled, because sudden water contact can cause a violent steam explosion.