MT Fire Alarm flashcards
MT Fire Alarm · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Smoke detector 30-foot rule
- On smooth ceilings up to 10 ft high, spot-type smoke detectors are spaced no more than 30 ft (9.1 m) apart, with the first detector within 15 ft of any wall.
- Pull station mounting height
- Manual fire alarm pull stations must be mounted 42 to 48 inches above the finished floor to the operating handle, and located within 5 ft of each exit door.
- NAC supervision
- Notification appliance circuits are supervised for opens, shorts, and grounds; a listed end-of-line resistor matching the panel value terminates the circuit.
- Alarm signal priority
- NFPA 72 requires alarm signals to take precedence over supervisory and trouble signals; trouble signals must not be silenced by alarm silence functions.
- Audible 15 dBA rule
- Audible notification must exceed ambient by 15 dBA or exceed the maximum 60-second ambient by 5 dBA, whichever is greater (NFPA 72 18.4.1.1).
- Voice intelligibility STI
- Voice evacuation requires STI of at least 0.50 (0.45 in rooms with 0.20-0.80 s reverberation), or CIS of at least 0.70, per NFPA 72.
- Addressable SLC
- A signaling line circuit is a supervised addressable loop where each device reports individually; capacity is set by the panel listing, often 99 to 318 devices.
- Four-wire detector circuit
- Four-wire detectors receive power on an unsupervised or separately supervised power circuit and report alarm via a supervised relay contact on the signal circuit.
- Ohm's law
- Voltage equals current times resistance (E = I × R). Power equals voltage times current (P = E × I), also expressed as I²R or E²/R.
- Voltage drop formula
- For a two-wire circuit, VD = 2 × K × I × L / CM, where K is about 12.9 for copper, I is amperes, L is one-way length, and CM is circular mils.
- NEC Article 760
- Article 760 governs fire alarm systems, dividing requirements into Part I general, Part II non-power-limited, and Part III power-limited circuits, including cable listing rules.
- Class 2 circuit limit
- Class 2 circuits are power-limited to 100 VA and specific voltage-current tables under NEC 725.121; Class 3 exceeds those limits but remains power-limited.
- Copper ampacity 12 AWG
- Per NEC 310.16 at 60°C, 14 AWG copper is 15 A, 12 AWG is 20 A, and 10 AWG is 30 A for small conductors.
- Battery standby calculation
- NFPA 72 requires standby capacity of 24 hours (60 hours for voice) plus 5 minutes of alarm, with manufacturer derating, typically to 80% end-of-life capacity.
- NAC voltage drop limit
- Notification appliance circuits should not drop more than 10% of nominal voltage from the panel terminals to the last appliance, per NFPA 72 and listings.
- Parallel resistance
- In parallel circuits, the reciprocal of total resistance equals the sum of reciprocals of each branch (1/R_T = 1/R1 + 1/R2), and voltage is equal across branches.
- Ground fault detection
- A ground fault on a supervised circuit creates a current imbalance detected by the panel; typical detection thresholds range from 10 to 50 kΩ depending on the panel.
- Montana Electrical Board
- Fire alarm installation in Montana is regulated under Title 37, Chapter 68, MCA by the State Electrical Board within the Department of Labor and Industry.
- Montana license types
- The Montana Electrical Board issues journeyman, master, and electrical contractor licenses; fire alarm work is performed under a licensed electrical contractor.
- Montana CE requirement
- Montana electricians renew every three years and must complete 24 hours of approved continuing education, including code update hours; verify the current cycle.
- Montana NEC adoption
- Montana adopts the National Electrical Code by administrative rule; the adopted edition is updated periodically, so confirm the current edition before design.
- Unlicensed practice penalty
- Under 37-68-201, MCA, practicing without a license is a violation subject to fines and possible misdemeanor prosecution by the State Electrical Board.
- Montana apprentice registration
- Apprentices must be registered with the Montana Department of Labor and Industry and work under direct supervision of a licensed journeyman or master electrician.
- Montana permit authority
- Fire alarm permits and plan review are obtained through the local jurisdiction and AHJ, not the State Electrical Board, which handles licensing and inspections.
- Montana reciprocity
- Montana has limited reciprocity with certain states for electricians; verify eligibility with the State Electrical Board before relying on an out-of-state license.
- Lockout/tagout
- OSHA 29 CFR 1910.147 requires disconnecting and locking the fire alarm control panel primary and battery power, then verifying zero energy before service.
- Arc flash PPE
- NFPA 70E requires an incident energy analysis or PPE category selection; energized work needs an energized electrical work permit and appropriate arc-rated PPE.
- Lead-acid battery hazards
- Lead-acid batteries emit hydrogen gas, so no open flames or sparks are allowed; use insulated tools and eye protection, and recycle batteries per EPA and DOT rules.
- Ladder 4-to-1 rule
- Extension ladders are set with the base 1 ft out for every 4 ft of working height, maintain three-point contact, and are inspected before each use.
- Fall protection threshold
- OSHA requires fall protection at 4 ft or more in general industry (29 CFR 1910.28) and at 6 ft in construction work.
- Hearing protection threshold
- Hearing protection is required when noise exceeds 85 dBA as an 8-hour time-weighted average; fire alarm horns can exceed 110 dBA at close range.
- Smoke detector test method
- Detectors are tested with canned smoke or manufacturer-approved aerosol; notify the monitoring company and building occupants before any test to avoid false dispatch.