MT Journeyman Plumber · Keep the key ideas within reach.

Quick reference

Uniform Plumbing Code (2021) Application and Installation Standards

  • UPC 2021 is the adopted model code; local amendments and the Montana Plumbing Code control where they differ, and the more restrictive provision governs.

  • Permits are required before installing, altering, repairing, or replacing plumbing systems, except for minor repairs such as stopping leaks, clearing stoppages, or replacing exposed fixture fittings.

  • Fixtures must be accessible for service; no plumbing fixture may be installed unless it is listed and complies with an approved standard recognized by the code.

  • Prohibited installations include concealed slip joints, direct connections between potable water and drainage, and installation of fixtures in rooms lacking required clearances and ventilation.

  • Testing: drainage and vent systems require a water test of 10 ft head or an air test of 5 psi for 15 minutes before concealment; water supply piping is tested at working pressure or 100 psi for 1 hour.

  • Materials must be approved and identified; dissimilar metals must be separated by dielectric fittings or approved isolation to prevent galvanic corrosion.

  • Vents must terminate outdoors at least 6 inches above the roof, and at least 10 feet from any window, door, or air intake, or 2 feet above such openings.

  • Code applies to new work and to repairs or alterations that affect the system's capacity, safety, or sanitation performance.

Quick reference

Plumbing Fixtures, Fixture Tables, and Fixture Unit Sizing

  • Fixture unit (FU) values are assigned per fixture type in the drainage fixture unit (DFU) and water supply fixture unit (WSFU) tables; use the correct table for drain vs. supply sizing.

  • Common DFU values: water closet 3, lavatory 1, bathtub 2, shower 2, kitchen sink 2, floor drain 2, washing machine 2, laundry tub 2, urinal 4 (tank-type 2 in some editions).

  • Common WSFU values (private): water closet 2.5, lavatory 1, bathtub 1.4, shower 1.4, kitchen sink 1.4, washing machine 1.4; convert to gallons per minute with the supply conversion table.

  • Water closet DFU of 3 is the standard basis; a 1.6 gpf or lower toilet still counts as 3 DFU unless the code table specifies otherwise.

  • Drainage pipe sizing uses the DFU table with slope limitations; smaller pipe sizes carry fewer fixture units and the allowable load decreases as slope decreases.

  • Water supply sizing uses total WSFU from the building supply tables; the meter and service must be sized for the total demand plus pressure loss.

  • Fixture clearances: water closets require at least 15 inches from centerline to side wall and 21 inches in front; lavatories and other fixtures have similar minimum spacing requirements.

  • Each fixture must have a trap, and each trap must have a vent unless it is a listed combination fixture; no fixture may be double-trapped or have more than one trap.

Quick reference

Piping, Materials, Joints, and Water/Drainage System Installation

  • Drainage pipe must be installed with continuous slope: 1/4 inch per foot for pipe 2-1/2 inches and smaller, and 1/8 inch per foot for 3 inches and larger.

  • Horizontal drainage lines must be supported at maximum intervals per material: plastic at 4-foot intervals, cast iron at 5-foot intervals, and copper at 10-foot intervals.

  • Vent pipe sizes: the vent must not be smaller than the drain it serves in most cases; a 1-1/2 inch vent is the minimum for a water closet, and 1-1/4 inch is minimum for other fixtures.

  • Cleanouts are required at the base of each stack, at the end of each horizontal drain, and at intervals not exceeding 100 feet in horizontal runs.

  • Water supply pipe must be protected from freezing and from backflow; an air gap or approved backflow prevention device is required at all connections to fixtures and appliances.

  • Joints: solvent cement for PVC/CPVC, lead-free solder or press fittings for copper, and mechanical couplings must be listed for the application; no lead-based solder is permitted.

  • Trap arms must be no more than 30 inches from the fixture and the trap seal must be between 2 and 4 inches deep.

  • Water hammer arrestors and expansion control are required where quick-closing valves or thermal expansion in a closed system can create excessive pressure.

  • Shower and tub/shower valves must be pressure-balancing or thermostatic, with the maximum water temperature limited to 120 degrees F at the fixture.

Quick reference

Montana Plumbing Statutes, Administrative Rules, and Licensing Requirements

  • Montana plumbing work is regulated by the Montana Department of Labor and Industry, which administers licensing and adopts the Montana Plumbing Code by administrative rule.

  • A journeyman plumber license requires a combination of documented work experience and passage of the journeyman examination; experience hours are verified by the employer or supervising master plumber.

  • A master plumber license is required to contract for plumbing work, obtain permits, and supervise journeyman plumbers and apprentices; a journeyman may work only under a master's supervision.

  • Apprentices must be registered and work under the direct supervision of a licensed journeyman or master plumber; apprentice hours are tracked toward journeyman eligibility.

  • Continuing education is required for license renewal; the number of hours and approved topics are set by department rule.

  • Plumbing permits must be obtained from the local jurisdiction before work begins, and inspections must be requested at required stages: rough-in, and final.

  • Licensees must display their license or carry it and provide it on request; unlicensed contracting is subject to civil penalties and license discipline.

  • Reciprocity or license by examination endorsement may be available for licensees from other states with comparable requirements, subject to department review.

  • Statutes and rules are amended periodically; the current Montana Plumbing Code and department rules control over outdated study materials.

Quick reference

Uniform Plumbing Code (2021) Application and Installation Standards - Testing and Approvals

  • Rough-in inspections must be approved before piping is concealed; the inspector may require a water or air test on any portion of the system.

  • A water test on drainage piping requires filling the system with water to a depth of at least 10 feet at the lowest point, or to the highest point of the system, and holding for 15 minutes.

  • An air test on drainage piping requires 5 psi of pressure held for 15 minutes with no drop; a gauge is required at the test point.

  • Water supply piping is tested with the system under working pressure or 100 psi, whichever is greater, for at least 1 hour with no leaks.

  • Final inspection requires all fixtures installed, traps primed, water heater operational, and all vents terminating properly.

  • Code sections are organized by topic: Chapter 4 fixtures, Chapter 6 water supply, Chapter 7 sanitary drainage, Chapter 8 vents, Chapter 9 traps and cleanouts, Chapter 10 joints and connections.

  • A plumbing system must be designed by a licensed engineer when the occupancy or size exceeds the prescriptive limits of the code.

Quick reference

Plumbing Fixtures, Fixture Tables, and Fixture Unit Sizing - Occupancy and Demand

  • Fixture counts are determined from the occupancy load and the fixture ratio tables; assembly, business, and residential occupancies have different ratios.

  • The total WSFU is converted to gallons per minute using the supply fixture unit table; the service and meter must handle peak demand plus pressure loss.

  • Water service sizing must account for the developed length of pipe, elevation loss, and the pressure required at the highest fixture.

  • A minimum of 8 psi residual pressure is required at the fixture outlet under flow conditions; the design must account for friction loss.

  • Drainage fixture unit loads are cumulative; the building drain must be sized for the total DFU plus the slope of the run.

  • Grease interceptors are required for commercial kitchens and other fixtures discharging grease-laden waste, sized by the fixture flow rate and retention time.

  • Indirect waste connections are required for fixtures such as food service sinks, sterilizers, and dishwashers; the waste must discharge through an air gap.

Quick reference

Piping, Materials, Joints, and Water/Drainage System Installation - Vents and Traps

  • A vent stack must extend at least 6 inches above the roof and terminate with an approved vent cap; a flat roof requires a minimum height above the roof surface.

  • A common vent may serve two fixtures on the same floor if the fixtures are within the allowed distance and the vent is sized for the combined load.

  • A wet vent may serve a fixture if it is sized and installed per the code; a dry vent may not be used as a drain.

  • Each trap must be protected by a vent; a trap arm may not exceed the distance permitted by the pipe size: 5 feet for 1-1/2 inch, 6 feet for 2 inch, and 10 feet for 3 inch.

  • A trap seal must be maintained by a vent; a trap that loses its seal allows sewer gas to enter the building.

  • Backwater valves are required where the building drain is below the level of the public sewer or where flooding is possible.

  • Water supply piping must be installed with a minimum cover and protected from freezing; in Montana, freeze protection is critical and piping must be insulated or heat-traced where required.

Quick reference

Montana Plumbing Statutes, Administrative Rules, and Licensing Requirements - Enforcement

  • The department may investigate complaints, issue citations, and suspend or revoke a license for violations of the plumbing statutes or rules.

  • Work performed without a permit or by an unlicensed person may require removal and reinstallation at the owner's expense.

  • A licensed plumber must provide a written contract for work over the threshold set by statute, including scope, price, and timeline.

  • The department adopts the plumbing code by reference; the current edition and any amendments are published in the administrative rules.

  • License renewal requires payment of fees and completion of continuing education; late renewal may require a penalty or reexamination.

  • A journeyman plumber may not supervise an apprentice unless authorized; supervision ratios are set by rule.

  • Local jurisdictions may adopt additional requirements, but they may not be less restrictive than the state code.

Quick reference

Plumbing Fixtures, Fixture Tables, and Fixture Unit Sizing - Fixture Types

  • Water closets must be listed and must not exceed 1.6 gallons per flush; urinals must not exceed 1.0 gallon per flush.

  • Showerheads must not exceed 2.5 gallons per minute at 80 psi; multiple showerheads are counted together.

  • Lavatory faucets must not exceed 2.2 gallons per minute; kitchen faucets must not exceed 2.2 gallons per minute.

  • A floor drain must have a trap and a strainer; floor drains in food service areas must be sized for the expected flow.

  • A drinking fountain must be provided with a minimum number based on occupancy; the fixture must be accessible.

  • A water heater must be equipped with a temperature and pressure relief valve piped to a safe discharge point.

  • Fixture units for a water heater are based on the tank capacity and recovery rate; the supply sizing must account for the demand.

Quick reference

Piping, Materials, Joints, and Water/Drainage System Installation - Materials

  • PVC pipe is permitted for drainage and vent systems but not for hot water distribution; CPVC is permitted for hot and cold water.

  • PEX is permitted for water distribution where listed and installed with approved fittings; it must be protected from UV exposure and freezing.

  • Copper tube types K, L, and M are permitted for water supply; type M is not permitted for underground installation.

  • Cast iron soil pipe is used for drainage where required by code or for sound attenuation; hubless couplings must be listed.

  • Galvanized steel pipe is permitted for water supply but must not be used with copper in a way that causes galvanic corrosion.

  • No lead content is permitted in pipe, solder, or flux used for potable water; lead-free is defined as not more than 0.25 percent lead by weight.

  • All materials must be listed and labeled by an approved agency; unlisted materials may not be installed.

Quick reference

Uniform Plumbing Code (2021) Application and Installation Standards - Administration

  • The code official has authority to interpret the code, approve alternate materials and methods, and require tests to verify compliance.

  • An alternate material or method may be approved if it is equivalent in quality, strength, effectiveness, fire resistance, durability, and safety.

  • A permit application must include plans, specifications, and the name of the licensed contractor; work may not begin until the permit is issued.

  • The code official may revoke a permit for false statements or for work that does not comply with the approved plans.

  • A certificate of occupancy may not be issued until the plumbing final inspection is approved.

  • The code does not apply to installations in manufactured homes built to federal standards, except for connections to the utility.

  • Violations may result in stop-work orders, fines, and required correction of the installation.

Quick reference

Montana Plumbing Statutes, Administrative Rules, and Licensing Requirements - Licensing Paths

  • A person may not perform plumbing work for compensation without a license; the license must be issued by the department.

  • Apprentice registration requires an application and an employer sponsor; the apprentice must be enrolled in a training program.

  • The journeyman examination covers the plumbing code, practical knowledge, and safety; a passing score is required for licensure.

  • The master examination covers code, business, and supervision; a master license is required to own a plumbing business.

  • A license is not transferable; a licensee must notify the department of a change of address or employment.

  • The department may require a criminal background check and may deny a license for certain offenses.

  • Licenses expire on a set date and must be renewed; continuing education hours must be completed before renewal.

Quick reference

Plumbing Fixtures, Fixture Tables, and Fixture Unit Sizing - Sizing Example

  • Example: a single-family home with 2 water closets, 2 lavatories, 1 bathtub, 1 shower, 1 kitchen sink, and 1 washing machine totals 6 DFU for drainage.

  • Water supply for the same home totals about 14.5 WSFU; the service must be sized for the peak demand in gallons per minute.

  • A 1-inch water service is typically adequate for a single-family home; larger demands require a larger service.

  • The building drain must be sized for the total DFU; a 3-inch building drain carries up to 42 DFU at 1/8 inch per foot.

  • A 4-inch building drain carries up to 216 DFU at 1/8 inch per foot; the slope and size must be selected together.

  • Vent sizing depends on the fixture units served; a 1-1/2 inch vent is the minimum for a water closet.

  • The water heater must be sized for the peak hot water demand; a 40-gallon tank is typical for a small home.

Quick reference

Piping, Materials, Joints, and Water/Drainage System Installation - Water Heaters

  • A water heater must be installed with a temperature and pressure relief valve; the discharge pipe must terminate within 6 inches of the floor or at a safe point.

  • A water heater must be seismically restrained where required; in Montana, freeze protection and venting are the primary concerns.

  • A water heater must be vented to the outdoors; a draft hood or power vent must be installed per the manufacturer's instructions.

  • A water heater installed in a garage must be elevated so the ignition source is at least 18 inches above the floor.

  • A thermal expansion tank is required where a backflow preventer creates a closed system.

  • A water heater must be accessible for service and inspection; clearance to combustibles must be maintained.

  • A tankless water heater must be sized for the peak flow and temperature rise; the gas supply must be sized for the input rating.

Quick reference

Uniform Plumbing Code (2021) Application and Installation Standards - Definitions

  • A fixture unit is a measure of the probable discharge into the drainage system by a fixture; it is based on the fixture's flow rate and duration.

  • A trap seal is the vertical distance between the crown weir and the top of the trap dip; it must be between 2 and 4 inches.

  • A vent is a pipe that provides air to the drainage system; a stack is a vertical pipe that carries waste or soil.

  • A building drain is the lowest pipe of the drainage system; a building sewer is the pipe from the building drain to the public sewer.

  • A cleanout is an access opening for clearing stoppages; it must be accessible and have a removable cover.

  • A backflow preventer is a device that prevents the reverse flow of water; it must be approved for the application.

  • A potable water supply is water that is safe for drinking; it must be protected from contamination by backflow or cross-connection.

Quick reference

Montana Plumbing Statutes, Administrative Rules, and Licensing Requirements - Statutes

  • The Montana plumbing statutes are found in Title 37, Chapter 69 of the Montana Code Annotated; the department administers them.

  • The statutes define plumbing work, licensing requirements, and enforcement authority.

  • The department may adopt rules to implement the statutes, including the plumbing code and licensing procedures.

  • The statutes provide for penalties for unlicensed work, including fines and injunctions.

  • The statutes require that plumbing work be performed by a licensed plumber or a registered apprentice under supervision.

  • The statutes authorize the department to inspect plumbing work and require corrections.

  • The statutes provide for reciprocity with other states that have comparable licensing requirements.

Quick reference

Plumbing Fixtures, Fixture Tables, and Fixture Unit Sizing - Trap and Vent Requirements

  • Each fixture must have a trap; a trap must be of the type and size specified in the code.

  • A trap must be installed level and must have a cleanout if it is not accessible.

  • A trap may not be double-trapped; two fixtures may not share a trap unless listed as a combination fixture.

  • A trap arm must be installed with a slope of 1/4 inch per foot and must not exceed the allowed length.

  • A vent must be installed on each trap; a vent may be a common vent or a wet vent if permitted.

  • A vent must terminate outdoors and must not be obstructed; a vent cap must be installed.

  • A vent must be sized for the fixture units served; an undersized vent can cause trap seal loss.

Quick reference

Piping, Materials, Joints, and Water/Drainage System Installation - Drainage

  • Drainage piping must be installed with a slope of 1/4 inch per foot for 2-1/2 inch and smaller, and 1/8 inch per foot for 3 inch and larger.

  • Drainage piping must be supported at intervals per material; plastic at 4 feet, cast iron at 5 feet, copper at 10 feet.

  • Drainage piping must be protected from freezing; in Montana, insulation and heat tracing may be required.

  • A building drain must be installed below the building or in a crawl space; it must be accessible for inspection.

  • A cleanout must be installed at the base of each stack and at the end of each horizontal drain.

  • A backwater valve must be installed where the building drain is below the public sewer.

  • A drainage system must be tested with water or air before it is concealed.

Quick reference

Uniform Plumbing Code (2021) Application and Installation Standards - Fixture Clearances

  • A water closet must have at least 15 inches from the centerline to a side wall and 21 inches in front of the bowl.

  • A lavatory must have at least 15 inches from the centerline to a side wall and 21 inches in front.

  • A bathtub must have at least 15 inches from the centerline to a side wall and 21 inches in front.

  • A shower must have at least 15 inches from the centerline to a side wall and 21 inches in front.

  • A kitchen sink must have at least 15 inches from the centerline to a side wall and 21 inches in front.

  • A floor drain must be accessible and must have a strainer; it must not be installed under a fixture.

  • A fixture must be accessible for service; a fixture installed in a closet or cabinet must have a removable panel.

Quick reference

Montana Plumbing Statutes, Administrative Rules, and Licensing Requirements - Continuing Education

  • Continuing education is required for license renewal; the number of hours is set by department rule.

  • Approved topics include code updates, safety, and technical training.

  • A licensee must keep records of continuing education and provide them on request.

  • Failure to complete continuing education may result in a late fee or license suspension.

  • The department may audit continuing education records and require proof of completion.

  • Continuing education must be completed before the license expiration date.

  • Some courses may be offered online if approved by the department.

Quick reference

Plumbing Fixtures, Fixture Tables, and Fixture Unit Sizing - Water Supply Fixture Units

  • WSFU values are assigned per fixture type; a water closet is 2.5, a lavatory is 1, a bathtub is 1.4, a shower is 1.4, and a kitchen sink is 1.4.

  • A washing machine is 1.4 WSFU; a laundry tub is 1.4 WSFU.

  • A hose bibb is 2.5 WSFU; a sill cock is 2.5 WSFU.

  • The total WSFU is converted to gallons per minute using the supply fixture unit table.

  • The service and meter must be sized for the peak demand plus pressure loss.

  • A minimum of 8 psi residual pressure is required at the fixture outlet.

  • The developed length of pipe and elevation loss must be included in the sizing calculation.

Quick reference

Piping, Materials, Joints, and Water/Drainage System Installation - Water Supply

  • Water supply piping must be installed with a minimum cover and protected from freezing.

  • Water supply piping must be tested at working pressure or 100 psi for 1 hour.

  • Water supply piping must be protected from backflow by an air gap or approved device.

  • Water supply piping must be sized for the peak demand plus pressure loss.

  • Water supply piping must be supported at intervals per material; copper at 10 feet, plastic at 4 feet.

  • Water supply piping must be insulated where required to prevent condensation or freezing.

  • Water supply piping must be installed with valves for shutoff and isolation.

Quick reference

Uniform Plumbing Code (2021) Application and Installation Standards - Permit Requirements

  • A permit is required before installing, altering, repairing, or replacing a plumbing system.

  • A permit is not required for minor repairs such as stopping leaks, clearing stoppages, or replacing exposed fixture fittings.

  • A permit application must include plans, specifications, and the name of the licensed contractor.

  • Work may not begin until the permit is issued.

  • The code official may revoke a permit for false statements or noncompliance.

  • A certificate of occupancy may not be issued until the plumbing final inspection is approved.

  • Violations may result in stop-work orders, fines, and required corrections.

Quick reference

Montana Plumbing Statutes, Administrative Rules, and Licensing Requirements - Supervision

  • A journeyman plumber may work only under the supervision of a master plumber.

  • A master plumber is required to contract for plumbing work and obtain permits.

  • An apprentice must work under the direct supervision of a licensed journeyman or master plumber.

  • The supervision ratio for apprentices is set by department rule.

  • A journeyman may not supervise an apprentice unless authorized by rule.

  • A master plumber is responsible for the work performed under their license.

  • Violations of supervision requirements may result in license discipline.

Quick reference

Plumbing Fixtures, Fixture Tables, and Fixture Unit Sizing - Fixture Unit Tables

  • Drainage fixture unit values are listed in the code table; use the correct table for the fixture type.

  • Water supply fixture unit values are listed in a separate table; use the correct table for the fixture type.

  • The total DFU determines the drainage pipe size and slope.

  • The total WSFU determines the water supply pipe size and meter size.

  • Fixture units are cumulative; add the values for all fixtures on the system.

  • A fixture unit is based on the probable discharge and duration of use.

  • The code tables must be used as published; do not estimate fixture units.

Quick reference

Piping, Materials, Joints, and Water/Drainage System Installation - Venting

  • A vent must terminate outdoors at least 6 inches above the roof.

  • A vent must be at least 10 feet from any window, door, or air intake, or 2 feet above such openings.

  • A vent must be sized for the fixture units served.

  • A vent must be installed on each trap unless a common vent or wet vent is permitted.

  • A wet vent must be sized and installed per the code.

  • A dry vent may not be used as a drain.

  • A vent must not be obstructed and must have an approved vent cap.

Quick reference

Uniform Plumbing Code (2021) Application and Installation Standards - Inspections

  • Rough-in inspection must be approved before piping is concealed.

  • The inspector may require a water or air test on any portion of the system.

  • Final inspection requires all fixtures installed, traps primed, and water heater operational.

  • The inspector may require corrections before approving the work.

  • A stop-work order may be issued for work without a permit or noncompliant work.

  • A certificate of occupancy may not be issued until the final inspection is approved.

  • Inspections must be requested at the required stages.

Quick reference

Montana Plumbing Statutes, Administrative Rules, and Licensing Requirements - Enforcement and Penalties

  • The department may investigate complaints and issue citations for violations.

  • The department may suspend or revoke a license for violations of the statutes or rules.

  • Unlicensed work may require removal and reinstallation at the owner's expense.

  • Fines may be imposed for unlicensed work or code violations.

  • The department may seek an injunction to stop unlicensed work.

  • A licensee must notify the department of a change of address or employment.

  • A license is not transferable.

Quick reference

Plumbing Fixtures, Fixture Tables, and Fixture Unit Sizing - Fixture Efficiency

  • Water closets must not exceed 1.6 gallons per flush.

  • Urinals must not exceed 1.0 gallon per flush.

  • Showerheads must not exceed 2.5 gallons per minute at 80 psi.

  • Lavatory faucets must not exceed 2.2 gallons per minute.

  • Kitchen faucets must not exceed 2.2 gallons per minute.

  • Multiple showerheads are counted together for the flow limit.

  • Fixture efficiency standards are set by federal law and adopted by the code.

Quick reference

Piping, Materials, Joints, and Water/Drainage System Installation - Joints

  • Solvent cement must be used for PVC and CPVC joints; the cement must be listed for the application.

  • Lead-free solder or press fittings must be used for copper joints.

  • Mechanical couplings must be listed for the application.

  • No lead-based solder is permitted for potable water.

  • Joints must be installed per the manufacturer's instructions.

  • Dissimilar metals must be separated by dielectric fittings.

  • Joints must be tested for leaks before concealment.

Quick reference

Uniform Plumbing Code (2021) Application and Installation Standards - Alternate Materials

  • An alternate material or method may be approved if it is equivalent in quality, strength, effectiveness, fire resistance, durability, and safety.

  • The code official has authority to approve alternate materials and methods.

  • The code official may require tests to verify compliance.

  • Unlisted materials may not be installed.

  • All materials must be listed and labeled by an approved agency.

  • The code official may interpret the code and require corrections.

  • Alternate materials must be approved before installation.

Quick reference

Montana Plumbing Statutes, Administrative Rules, and Licensing Requirements - Reciprocity

  • Reciprocity may be available for licensees from other states with comparable requirements.

  • The department reviews reciprocity applications and may require an examination.

  • A licensee must provide proof of licensure and experience.

  • Reciprocity is subject to department approval.

  • The department may impose additional requirements for reciprocity.

  • Reciprocity does not exempt a licensee from Montana statutes and rules.

  • A licensee must comply with Montana continuing education requirements.

Quick reference

Plumbing Fixtures, Fixture Tables, and Fixture Unit Sizing - Grease and Indirect Waste

  • Grease interceptors are required for commercial kitchens and fixtures discharging grease-laden waste.

  • Grease interceptors are sized by flow rate and retention time.

  • Indirect waste connections are required for food service sinks, sterilizers, and dishwashers.

  • Indirect waste must discharge through an air gap.

  • An air gap must be at least twice the diameter of the waste pipe.

  • Indirect waste must not be connected directly to the drainage system.

  • Grease interceptors must be accessible for cleaning.

Quick reference

Piping, Materials, Joints, and Water/Drainage System Installation - Backflow

  • Backflow prevention is required at all connections to fixtures and appliances.

  • An air gap is the preferred backflow prevention method.

  • An approved backflow prevention device must be installed where an air gap is not possible.

  • Backflow preventers must be tested annually where required.

  • A cross-connection must be eliminated or protected by an approved device.

  • Backflow prevention devices must be accessible for testing and service.

  • A thermal expansion tank is required where a backflow preventer creates a closed system.

Quick reference

Uniform Plumbing Code (2021) Application and Installation Standards - Code Organization

  • Chapter 4 covers fixtures, fixture clearances, and fixture units.

  • Chapter 6 covers water supply and sizing.

  • Chapter 7 covers sanitary drainage.

  • Chapter 8 covers vents.

  • Chapter 9 covers traps and cleanouts.

  • Chapter 10 covers joints and connections.

  • The code must be used with local amendments and the Montana Plumbing Code.

Quick reference

Montana Plumbing Statutes, Administrative Rules, and Licensing Requirements - License Display

  • A licensee must display their license or carry it and provide it on request.

  • A license is not transferable.

  • A licensee must notify the department of a change of address or employment.

  • A licensee must comply with continuing education requirements.

  • A licensee must comply with the plumbing code and statutes.

  • A licensee must obtain permits before work begins.

  • A licensee must request inspections at required stages.

Quick reference

Plumbing Fixtures, Fixture Tables, and Fixture Unit Sizing - Water Heaters and Fixtures

  • A water heater must be equipped with a temperature and pressure relief valve.

  • The relief valve discharge pipe must terminate within 6 inches of the floor or at a safe point.

  • A water heater in a garage must be elevated so the ignition source is at least 18 inches above the floor.

  • A thermal expansion tank is required where a backflow preventer creates a closed system.

  • A water heater must be vented to the outdoors.

  • A water heater must be accessible for service and inspection.

  • A tankless water heater must be sized for the peak flow and temperature rise.

Quick reference

Piping, Materials, Joints, and Water/Drainage System Installation - Traps

  • Each fixture must have a trap.

  • A trap must be installed level and must have a cleanout if it is not accessible.

  • A trap may not be double-trapped.

  • A trap seal must be between 2 and 4 inches deep.

  • A trap arm must be installed with a slope of 1/4 inch per foot.

  • A trap arm may not exceed the allowed length for the pipe size.

  • A trap must be protected by a vent.

Quick reference

Uniform Plumbing Code (2021) Application and Installation Standards - Prohibited Installations

  • Concealed slip joints are prohibited.

  • Direct connections between potable water and drainage are prohibited.

  • Fixtures installed in rooms lacking required clearances and ventilation are prohibited.

  • Unlisted materials are prohibited.

  • Lead-based solder is prohibited for potable water.

  • Double-trapping is prohibited.

  • A dry vent used as a drain is prohibited.

Quick reference

Montana Plumbing Statutes, Administrative Rules, and Licensing Requirements - Apprenticeship

  • An apprentice must be registered with the department.

  • An apprentice must work under the direct supervision of a licensed journeyman or master plumber.

  • An apprentice must be enrolled in a training program.

  • Apprentice hours are tracked toward journeyman eligibility.

  • The supervision ratio for apprentices is set by department rule.

  • An apprentice may not perform plumbing work without supervision.

  • Apprentice registration requires an employer sponsor.

Quick reference

Plumbing Fixtures, Fixture Tables, and Fixture Unit Sizing - Fixture Unit Calculation

  • Add the DFU values for all fixtures on the drainage system.

  • Add the WSFU values for all fixtures on the water supply system.

  • Use the total DFU to size the building drain and sewer.

  • Use the total WSFU to size the water service and meter.

  • Include the slope of the drainage run in the sizing calculation.

  • Include the developed length and elevation loss in the water supply sizing.

  • Use the code tables as published; do not estimate fixture units.

Quick reference

Piping, Materials, Joints, and Water/Drainage System Installation - Support and Protection

  • Drainage piping must be supported at intervals per material.

  • Water supply piping must be supported at intervals per material.

  • Piping must be protected from freezing.

  • Piping must be protected from corrosion.

  • Piping must be protected from physical damage.

  • Piping must be installed with valves for shutoff and isolation.

  • Piping must be tested before concealment.

Quick reference

Uniform Plumbing Code (2021) Application and Installation Standards - Testing Procedures

  • Drainage and vent systems require a water test of 10 ft head or an air test of 5 psi for 15 minutes.

  • Water supply piping is tested at working pressure or 100 psi for 1 hour.

  • The inspector may require a test on any portion of the system.

  • Tests must be conducted before piping is concealed.

  • Test results must be documented and available for inspection.

  • A failed test must be corrected and retested.

  • Testing must be performed in the presence of the inspector where required.

Quick reference

Montana Plumbing Statutes, Administrative Rules, and Licensing Requirements - Business Requirements

  • A master plumber license is required to own a plumbing business.

  • A licensed plumber must provide a written contract for work over the threshold set by statute.

  • The contract must include scope, price, and timeline.

  • A plumbing business must comply with state and local licensing requirements.

  • A plumbing business must carry insurance as required by statute.

  • A plumbing business must obtain permits before work begins.

  • A plumbing business must comply with the plumbing code and statutes.

Quick reference

Plumbing Fixtures, Fixture Tables, and Fixture Unit Sizing - Fixture Clearances and Accessibility

  • A water closet must have at least 15 inches from the centerline to a side wall and 21 inches in front.

  • A lavatory must have at least 15 inches from the centerline to a side wall and 21 inches in front.

  • A bathtub must have at least 15 inches from the centerline to a side wall and 21 inches in front.

  • A shower must have at least 15 inches from the centerline to a side wall and 21 inches in front.

  • A kitchen sink must have at least 15 inches from the centerline to a side wall and 21 inches in front.

  • A fixture must be accessible for service.

  • A fixture installed in a closet or cabinet must have a removable panel.

Quick reference

Piping, Materials, Joints, and Water/Drainage System Installation - Cleanouts

  • Cleanouts are required at the base of each stack.

  • Cleanouts are required at the end of each horizontal drain.

  • Cleanouts are required at intervals not exceeding 100 feet in horizontal runs.

  • Cleanouts must be accessible and have a removable cover.

  • Cleanouts must be sized per the code.

  • Cleanouts must be installed with a watertight seal.

  • Cleanouts must be tested for leaks.

Quick reference

Uniform Plumbing Code (2021) Application and Installation Standards - Vent Termination

  • A vent must terminate outdoors at least 6 inches above the roof.

  • A vent must be at least 10 feet from any window, door, or air intake, or 2 feet above such openings.

  • A vent must have an approved vent cap.

  • A vent must not be obstructed.

  • A vent must be sized for the fixture units served.

  • A vent must be installed on each trap unless a common vent or wet vent is permitted.

  • A dry vent may not be used as a drain.

Quick reference

Montana Plumbing Statutes, Administrative Rules, and Licensing Requirements - Code Adoption

  • The department adopts the plumbing code by reference.

  • The current edition and any amendments are published in the administrative rules.

  • Local jurisdictions may adopt additional requirements but may not be less restrictive than the state code.

  • The Montana Plumbing Code controls over outdated study materials.

  • The department may amend the code by rule.

  • The code must be used with local amendments.

  • The code official has authority to interpret the code.

Quick reference

Plumbing Fixtures, Fixture Tables, and Fixture Unit Sizing - Backwater and Floor Drains

  • A backwater valve is required where the building drain is below the level of the public sewer.

  • A backwater valve is required where flooding is possible.

  • A floor drain must have a trap and a strainer.

  • A floor drain in a food service area must be sized for the expected flow.

  • A floor drain must not be installed under a fixture.

  • A floor drain must be accessible for cleaning.

  • A floor drain must be tested for leaks.

Quick reference

Piping, Materials, Joints, and Water/Drainage System Installation - Pressure and Temperature

  • Shower and tub/shower valves must be pressure-balancing or thermostatic.

  • The maximum water temperature at the fixture must be limited to 120 degrees F.

  • A water heater must be equipped with a temperature and pressure relief valve.

  • The relief valve discharge pipe must terminate within 6 inches of the floor or at a safe point.

  • Water hammer arrestors are required where quick-closing valves can create excessive pressure.

  • A thermal expansion tank is required where a backflow preventer creates a closed system.

  • Piping must be protected from excessive pressure.

Quick reference

Uniform Plumbing Code (2021) Application and Installation Standards - Fixture Units

  • A fixture unit is a measure of the probable discharge into the drainage system by a fixture.

  • Fixture units are based on the fixture's flow rate and duration.

  • DFU values are used for drainage sizing.

  • WSFU values are used for water supply sizing.

  • Fixture units are cumulative.

  • The code tables must be used as published.

  • Do not estimate fixture units.

Quick reference

Montana Plumbing Statutes, Administrative Rules, and Licensing Requirements - Examination

  • The journeyman examination covers the plumbing code, practical knowledge, and safety.

  • A passing score is required for licensure.

  • The master examination covers code, business, and supervision.

  • The department may require a criminal background check.

  • The department may deny a license for certain offenses.

  • Examination results are valid for a limited time.

  • A licensee must comply with continuing education requirements.

Quick reference

Plumbing Fixtures, Fixture Tables, and Fixture Unit Sizing - Fixture Types and Standards

  • Fixtures must be listed and comply with an approved standard.

  • Water closets must not exceed 1.6 gallons per flush.

  • Urinals must not exceed 1.0 gallon per flush.

  • Showerheads must not exceed 2.5 gallons per minute at 80 psi.

  • Lavatory faucets must not exceed 2.2 gallons per minute.

  • Kitchen faucets must not exceed 2.2 gallons per minute.

  • Multiple showerheads are counted together for the flow limit.

Quick reference

Piping, Materials, Joints, and Water/Drainage System Installation - Slope and Sizing

  • Drainage pipe must have a slope of 1/4 inch per foot for 2-1/2 inch and smaller.

  • Drainage pipe must have a slope of 1/8 inch per foot for 3 inch and larger.

  • The building drain must be sized for the total DFU.

  • A 3-inch building drain carries up to 42 DFU at 1/8 inch per foot.

  • A 4-inch building drain carries up to 216 DFU at 1/8 inch per foot.

  • The slope and size must be selected together.

  • The building sewer must be sized for the total DFU.

Quick reference

Uniform Plumbing Code (2021) Application and Installation Standards - Definitions and Terms

  • A trap seal is the vertical distance between the crown weir and the top of the trap dip.

  • A trap seal must be between 2 and 4 inches deep.

  • A vent is a pipe that provides air to the drainage system.

  • A stack is a vertical pipe that carries waste or soil.

  • A building drain is the lowest pipe of the drainage system.

  • A building sewer is the pipe from the building drain to the public sewer.

  • A cleanout is an access opening for clearing stoppages.

Quick reference

Montana Plumbing Statutes, Administrative Rules, and Licensing Requirements - Renewal

  • Licenses expire on a set date and must be renewed.

  • Continuing education hours must be completed before renewal.

  • Late renewal may require a penalty or reexamination.

  • A licensee must notify the department of a change of address or employment.

  • A license is not transferable.

  • A licensee must keep records of continuing education.

  • The department may audit continuing education records.

Quick reference

Plumbing Fixtures, Fixture Tables, and Fixture Unit Sizing - Fixture Unit Examples

  • A single-family home with 2 water closets, 2 lavatories, 1 bathtub, 1 shower, 1 kitchen sink, and 1 washing machine totals 6 DFU for drainage.

  • Water supply for the same home totals about 14.5 WSFU.

  • A 1-inch water service is typically adequate for a single-family home.

  • A 40-gallon water heater is typical for a small home.

  • The water heater must be sized for the peak hot water demand.

  • The building drain must be sized for the total DFU.

  • The vent must be sized for the fixture units served.

Quick reference

Piping, Materials, Joints, and Water/Drainage System Installation - Material Restrictions

  • PVC is permitted for drainage and vent systems but not for hot water distribution.

  • CPVC is permitted for hot and cold water.

  • PEX is permitted for water distribution where listed.

  • Copper types K, L, and M are permitted for water supply.

  • Type M copper is not permitted for underground installation.

  • Galvanized steel must not be used with copper in a way that causes galvanic corrosion.

  • No lead content is permitted in pipe, solder, or flux used for potable water.

Quick reference

Uniform Plumbing Code (2021) Application and Installation Standards - Approvals

  • The code official has authority to approve alternate materials and methods.

  • An alternate material may be approved if it is equivalent in quality, strength, effectiveness, fire resistance, durability, and safety.

  • The code official may require tests to verify compliance.

  • Unlisted materials may not be installed.

  • All materials must be listed and labeled by an approved agency.

  • The code official may interpret the code and require corrections.

  • Alternate materials must be approved before installation.

Quick reference

Montana Plumbing Statutes, Administrative Rules, and Licensing Requirements - Permits

  • Plumbing permits must be obtained from the local jurisdiction before work begins.

  • Inspections must be requested at required stages: rough-in and final.

  • A permit application must include plans and the name of the licensed contractor.

  • Work may not begin until the permit is issued.

  • The code official may revoke a permit for false statements or noncompliance.

  • A certificate of occupancy may not be issued until the final inspection is approved.

  • Violations may result in stop-work orders and fines.

Quick reference

Plumbing Fixtures, Fixture Tables, and Fixture Unit Sizing - Fixture Unit Tables and Slope

  • Drainage pipe sizing uses the DFU table with slope limitations.

  • Smaller pipe sizes carry fewer fixture units.

  • The allowable load decreases as slope decreases.

  • A 3-inch building drain carries up to 42 DFU at 1/8 inch per foot.

  • A 4-inch building drain carries up to 216 DFU at 1/8 inch per foot.

  • The slope and size must be selected together.

  • The building sewer must be sized for the total DFU.

Quick reference

Piping, Materials, Joints, and Water/Drainage System Installation - Water Supply Sizing

  • Water supply sizing uses total WSFU from the building supply tables.

  • The meter and service must be sized for the total demand plus pressure loss.

  • A minimum of 8 psi residual pressure is required at the fixture outlet.

  • The developed length of pipe and elevation loss must be included in the sizing calculation.

  • A 1-inch water service is typically adequate for a single-family home.

  • Larger demands require a larger service.

  • The water heater must be sized for the peak hot water demand.

Quick reference

Uniform Plumbing Code (2021) Application and Installation Standards - Fixture Installation

  • Fixtures must be accessible for service.

  • No plumbing fixture may be installed unless it is listed and complies with an approved standard.

  • Fixtures must be installed with required clearances.

  • Fixtures must be installed in rooms with required ventilation.

  • Fixtures must be installed with traps and vents.

  • Fixtures must be installed with backflow protection.

  • Fixtures must be tested for leaks.

Quick reference

Montana Plumbing Statutes, Administrative Rules, and Licensing Requirements - Supervision Ratios

  • The supervision ratio for apprentices is set by department rule.

  • A journeyman may not supervise an apprentice unless authorized by rule.

  • A master plumber is responsible for the work performed under their license.

  • An apprentice must work under the direct supervision of a licensed journeyman or master plumber.

  • A journeyman may work only under the supervision of a master plumber.

  • A master plumber is required to contract for plumbing work and obtain permits.

  • Violations of supervision requirements may result in license discipline.

Quick reference

Plumbing Fixtures, Fixture Tables, and Fixture Unit Sizing - Fixture Unit Values

  • Water closet DFU is 3.

  • Lavatory DFU is 1.

  • Bathtub DFU is 2.

  • Shower DFU is 2.

  • Kitchen sink DFU is 2.

  • Floor drain DFU is 2.

  • Washing machine DFU is 2.

Quick reference

Piping, Materials, Joints, and Water/Drainage System Installation - Vent Sizing

  • The vent must not be smaller than the drain it serves in most cases.

  • A 1-1/2 inch vent is the minimum for a water closet.

  • A 1-1/4 inch vent is the minimum for other fixtures.

  • The vent must be sized for the fixture units served.

  • An undersized vent can cause trap seal loss.

  • A vent must terminate outdoors.

  • A vent must have an approved vent cap.

Quick reference

Uniform Plumbing Code (2021) Application and Installation Standards - System Design

  • A plumbing system must be designed by a licensed engineer when the occupancy or size exceeds the prescriptive limits of the code.

  • The code official may require engineering calculations for complex systems.

  • The system must be designed for the expected load.

  • The system must be designed for the available pressure.

  • The system must be designed for freeze protection.

  • The system must be designed for backflow prevention.

  • The system must be designed for accessibility.

Quick reference

Montana Plumbing Statutes, Administrative Rules, and Licensing Requirements - Definitions

  • Plumbing work includes the installation, alteration, repair, and replacement of plumbing systems.

  • A journeyman plumber is licensed to perform plumbing work under a master plumber.

  • A master plumber is licensed to contract for plumbing work and supervise journeymen.

  • An apprentice is registered and works under supervision.

  • A plumbing contractor is a business licensed to perform plumbing work.

  • The department administers licensing and enforcement.

  • The statutes and rules define the scope of plumbing work.

Quick reference

Plumbing Fixtures, Fixture Tables, and Fixture Unit Sizing - Fixture Unit Conversion

  • WSFU values are converted to gallons per minute using the supply fixture unit table.

  • The total WSFU determines the water supply pipe size.

  • The total DFU determines the drainage pipe size.

  • The meter and service must be sized for the peak demand.

  • The developed length and elevation loss must be included.

  • A minimum of 8 psi residual pressure is required at the fixture outlet.

  • The water heater must be sized for the peak hot water demand.

Quick reference

Piping, Materials, Joints, and Water/Drainage System Installation - Testing

  • Drainage and vent systems require a water test of 10 ft head or an air test of 5 psi for 15 minutes.

  • Water supply piping is tested at working pressure or 100 psi for 1 hour.

  • Tests must be conducted before piping is concealed.

  • Test results must be documented and available for inspection.

  • A failed test must be corrected and retested.

  • The inspector may require a test on any portion of the system.

  • Testing must be performed in the presence of the inspector where required.

Quick reference

Uniform Plumbing Code (2021) Application and Installation Standards - Local Amendments

  • Local jurisdictions may adopt additional requirements.

  • Local requirements may not be less restrictive than the state code.

  • The more restrictive provision governs where codes differ.

  • The Montana Plumbing Code controls over outdated study materials.

  • The department adopts the plumbing code by reference.

  • The current edition and amendments are published in the administrative rules.

  • The code official has authority to interpret the code.

Quick reference

Montana Plumbing Statutes, Administrative Rules, and Licensing Requirements - Insurance

  • A plumbing business must carry insurance as required by statute.

  • A licensed plumber must provide a written contract for work over the threshold set by statute.

  • The contract must include scope, price, and timeline.

  • A plumbing business must comply with state and local licensing requirements.

  • A plumbing business must obtain permits before work begins.

  • A plumbing business must comply with the plumbing code and statutes.

  • A plumbing business must maintain records of work performed.

Quick reference

Plumbing Fixtures, Fixture Tables, and Fixture Unit Sizing - Fixture Unit Table Use

  • Use the drainage fixture unit table for drainage sizing.

  • Use the water supply fixture unit table for water supply sizing.

  • Do not use one table for the other purpose.

  • Fixture units are cumulative.

  • The code tables must be used as published.

  • Do not estimate fixture units.

  • The total DFU and WSFU determine pipe sizes.

Quick reference

Piping, Materials, Joints, and Water/Drainage System Installation - Freeze Protection

  • Water supply piping must be protected from freezing.

  • Drainage piping must be protected from freezing.

  • In Montana, insulation and heat tracing may be required.

  • Piping must be installed with a minimum cover.

  • Piping must be protected from physical damage.

  • Piping must be protected from corrosion.

  • Piping must be tested before concealment.

Quick reference

Uniform Plumbing Code (2021) Application and Installation Standards - Fixture Unit Definition

  • A fixture unit is a measure of the probable discharge into the drainage system by a fixture.

  • Fixture units are based on the fixture's flow rate and duration.

  • DFU values are used for drainage sizing.

  • WSFU values are used for water supply sizing.

  • Fixture units are cumulative.

  • The code tables must be used as published.

  • Do not estimate fixture units.

Quick reference

Montana Plumbing Statutes, Administrative Rules, and Licensing Requirements - Complaints

  • The department may investigate complaints against licensees.

  • The department may issue citations for violations.

  • The department may suspend or revoke a license.

  • A licensee must respond to department inquiries.

  • A licensee must provide records on request.

  • A licensee must comply with the statutes and rules.

  • Violations may result in fines and license discipline.

Quick reference

Plumbing Fixtures, Fixture Tables, and Fixture Unit Sizing - Fixture Unit Examples and Tables

  • A water closet is 3 DFU and 2.5 WSFU.

  • A lavatory is 1 DFU and 1 WSFU.

  • A bathtub is 2 DFU and 1.4 WSFU.

  • A shower is 2 DFU and 1.4 WSFU.

  • A kitchen sink is 2 DFU and 1.4 WSFU.

  • A washing machine is 2 DFU and 1.4 WSFU.

  • A floor drain is 2 DFU.

Quick reference

Piping, Materials, Joints, and Water/Drainage System Installation - Valves

  • Water supply piping must be installed with valves for shutoff and isolation.

  • A main shutoff valve must be installed near the point of entry.

  • A valve must be accessible.

  • A valve must be listed for the application.

  • A valve must be tested for leaks.

  • A valve must be protected from freezing.

  • A valve must be installed per the manufacturer's instructions.

Quick reference

Uniform Plumbing Code (2021) Application and Installation Standards - Fixture Unit and Sizing

  • Fixture units are used to size drainage and water supply systems.

  • DFU values are used for drainage sizing.

  • WSFU values are used for water supply sizing.

  • The total DFU determines the drainage pipe size.

  • The total WSFU determines the water supply pipe size.

  • The code tables must be used as published.

  • Do not estimate fixture units.

Quick reference

Montana Plumbing Statutes, Administrative Rules, and Licensing Requirements - Records

  • A plumbing business must maintain records of work performed.

  • A licensee must keep records of continuing education.

  • The department may audit records.

  • A licensee must provide records on request.

  • Records must be kept for the period set by rule.

  • Records must be accurate and complete.

  • Failure to maintain records may result in discipline.

Quick reference

Plumbing Fixtures, Fixture Tables, and Fixture Unit Sizing - Fixture Unit Sizing Summary

  • DFU values are used for drainage sizing.

  • WSFU values are used for water supply sizing.

  • The total DFU determines the drainage pipe size.

  • The total WSFU determines the water supply pipe size.

  • The code tables must be used as published.

  • Do not estimate fixture units.

  • The slope and size must be selected together.

Quick reference

Piping, Materials, Joints, and Water/Drainage System Installation - Installation Summary

  • Drainage pipe must have a slope of 1/4 inch per foot for 2-1/2 inch and smaller.

  • Drainage pipe must have a slope of 1/8 inch per foot for 3 inch and larger.

  • Drainage piping must be supported at intervals per material.

  • Water supply piping must be supported at intervals per material.

  • Piping must be protected from freezing.

  • Piping must be protected from backflow.

  • Piping must be tested before concealment.

Quick reference

Uniform Plumbing Code (2021) Application and Installation Standards - Summary

  • The code applies to new work and to repairs or alterations that affect the system's capacity, safety, or sanitation performance.

  • Permits are required before work begins.

  • Inspections must be requested at required stages.

  • Materials must be approved and identified.

  • Fixtures must be accessible for service.

  • Systems must be tested before concealment.

  • The code official has authority to interpret the code.

Quick reference

Montana Plumbing Statutes, Administrative Rules, and Licensing Requirements - Summary

  • A license is required to perform plumbing work for compensation.

  • A master plumber is required to contract for plumbing work.

  • An apprentice must work under supervision.

  • Continuing education is required for renewal.

  • Permits must be obtained before work begins.

  • Inspections must be requested at required stages.

  • The department may investigate complaints and issue penalties.

Quick reference

Plumbing Fixtures, Fixture Tables, and Fixture Unit Sizing - Summary

  • DFU values are used for drainage sizing.

  • WSFU values are used for water supply sizing.

  • The total DFU determines the drainage pipe size.

  • The total WSFU determines the water supply pipe size.

  • The code tables must be used as published.

  • Do not estimate fixture units.

  • The slope and size must be selected together.

Quick reference

Piping, Materials, Joints, and Water/Drainage System Installation - Summary

  • Drainage pipe must have a slope of 1/4 inch per foot for 2-1/2 inch and smaller.

  • Drainage pipe must have a slope of 1/8 inch per foot for 3 inch and larger.

  • Drainage piping must be supported at intervals per material.

  • Water supply piping must be supported at intervals per material.

  • Piping must be protected from freezing.

  • Piping must be protected from backflow.

  • Piping must be tested before concealment.

Quick reference

Uniform Plumbing Code (2021) Application and Installation Standards - Summary

  • The code applies to new work and to repairs or alterations that affect the system's capacity, safety, or sanitation performance.

  • Permits are required before work begins.

  • Inspections must be requested at required stages.

  • Materials must be approved and identified.

  • Fixtures must be accessible for service.

  • Systems must be tested before concealment.

  • The code official has authority to interpret the code.

Quick reference

Montana Plumbing Statutes, Administrative Rules, and Licensing Requirements - Summary

  • A license is required to perform plumbing work for compensation.

  • A master plumber is required to contract for plumbing work.

  • An apprentice must work under supervision.

  • Continuing education is required for renewal.

  • Permits must be obtained before work begins.

  • Inspections must be requested at required stages.

  • The department may investigate complaints and issue penalties.