Ohm's law
Current through a conductor is directly proportional to voltage and inversely proportional to resistance, expressed as V = I x R for DC and resistive AC circuits.
Electrical power formula
Power in watts equals voltage multiplied by current; for resistive loads also I squared times R or V squared divided by R.
Series circuit rules
The same current flows through every component, voltages add, and total resistance is the sum of individual resistances.
Parallel circuit rules
Voltage is the same across every branch, branch currents add, and total resistance is found from the reciprocal sum of branch resistances.
Voltage drop formula
For a single-phase circuit, Vd = (2 x rho x L x I) / A, with the factor two accounting for the outgoing and return conductors.
Power factor
Ratio of true power in watts to apparent power in volt-amperes; equals cosine of the phase angle between voltage and current.
RCD trip time limits
A 30 mA RCD should trip within 300 ms at rated residual current and within 40 ms at five times rated current when used for supplementary protection.
TN-C-S earthing system
Supply neutral and protective earth are combined in the distributor's network and separated at the installation origin into neutral and protective conductors.
TT earthing system
The installation has its own earth electrode independent of the supply earth, so earth fault protection normally relies on an RCD.
Main protective bonding
Connection of extraneous-conductive-parts such as water and gas pipes to the main earthing terminal to equalise potential and limit touch voltage.
Discrimination
Coordination of protective devices so the device nearest a fault operates first, preventing unnecessary loss of supply to healthy circuits.
Breaking capacity
Maximum prospective short-circuit current a protective device can safely interrupt without damage; must exceed the fault level at its point of installation.
Loop-in lighting method
Each luminaire is fed from a ceiling rose carrying permanent live, neutral, earth and switched live, with the switch drop connected at the rose.
Two-way switching
Two two-way switches connected by strapper conductors allow one lamp to be controlled from either of two positions.
Diversity in maximum demand
Assumption that not all connected load operates simultaneously; used to size the supply and consumer unit protective devices realistically.
Ring final circuit
A socket circuit where the cable forms a closed loop from the protective device, allowing smaller conductors and reducing voltage drop.
Fused connection unit
An accessory containing a fuse that supplies a fixed appliance or a spur, limiting the current the downstream cable must carry.
Insulation resistance test
Dead test at 500 V DC between live conductors and earth, with loads disconnected; acceptable result is at least 1 megohm.
Earth fault loop impedance
Total impedance of the earth fault path from the origin through the protective conductor and back to the supply; determines disconnection time.
Prospective short-circuit current
Maximum current that would flow at a point in the installation if a zero-impedance fault occurred there; used to verify breaking capacity.
Polarity test
Confirms line conductors connect to switch and to the centre pin of lamp holders, and that sockets have line, neutral and earth in correct positions.
Ring circuit continuity test
End-to-end resistance readings of line, neutral and earth are compared with cross-connected socket readings to confirm the ring is complete.
Electricity Regulations 1994
Malaysian regulations made under the Electricity Supply Act 1990 covering installation requirements, competent persons, inspection and testing.
MS IEC 60364
Malaysian standard for low-voltage electrical installations, covering design, protection, earthing, selection of equipment and verification.
Conductor colour code
Line is brown, neutral is blue, and protective earth is green-yellow; green-yellow must never be used for any other purpose.
Suruhanjaya Tenaga role
The Energy Commission regulates the electricity supply industry in Malaysia, issues competency certificates and enforces installation safety requirements.
Schematic diagram
Drawing showing electrical connections between components using standard symbols, independent of their physical position in the installation.
Wiring diagram
Drawing showing physical routing and terminal connections of conductors, including colour coding, used for installation and fault finding.
Schedule of test results
Document recording circuit details, protective device ratings, insulation resistance, loop impedance, short-circuit current, RCD times and polarity.
Circuit chart
Notice fixed at the consumer unit listing each protective device, its rating and the circuit it protects, updated whenever circuits change.
Lockout-tagout
Isolation procedure where every energy source is locked and tagged, then the circuit is proved dead before work begins.
Hierarchy of control
Order of risk reduction: eliminate the hazard, substitute, apply engineering controls, then administrative controls, with PPE as the last resort.
Cable derating factors
Correction factors for ambient temperature, grouping, thermal insulation and installation method applied to tabulated current-carrying capacity.