Occupant load factor
The floor area per occupant used to compute design occupancy; IBC Table 1004.5 lists values such as 150 gross sq ft for business and 15 net sq ft for tables and chairs.
Class A interior finish
A finish material with a flame spread index of 0-25 and smoke-developed index of 450 or less when tested per ASTM E84, permitted in the most restrictive locations.
Smoke-developed index
A number from ASTM E84 tunnel testing that rates how much smoke a material produces; values above 450 are not permitted for interior wall and ceiling finishes in most occupancies.
Egress width factor
The inches of egress width required per occupant: 0.2 in. for level components and ramps, and 0.15 in. for stairways, per IBC 1005.3.1.
Travel distance limit
The maximum distance from the most remote point in a space to an exit; commonly 250 ft unsprinklered and 300 ft sprinklered in non-industrial occupancies.
Fire door label rating
The fire-resistance rating assigned to a door assembly, such as 20, 45, 60, 90, or 180 minutes, which must match or exceed the rating of the wall opening it protects.
Panic hardware threshold
Egress doors in assembly and educational occupancies serving 50 or more occupants must have panic hardware that releases with one motion without a key or special knowledge.
Fireblocking
Approved material installed in concealed spaces, such as at floor levels and soffits, to stop the spread of flame and hot gases through wall and floor cavities.
Firestopping
A listed system used to seal penetrations and joints in fire-rated assemblies, tested per ASTM E814 or UL 1479, to maintain the assembly's fire-resistance rating.
Smoke barrier rating
A continuous membrane with a minimum 1-hour fire-resistance rating and smoke-tight joints, used to limit smoke migration between areas of a building.
Accessible route width
A continuous path with a clear width of at least 36 in.; a 32 in. clear width is permitted at a single point such as a doorway.
Ramp maximum slope
The steepest permitted running slope for an accessible ramp is 1:12 (8.33%); steeper slopes require approval and are limited to existing site conditions with landings.
Handrail height range
Handrails on stairs and ramps must be 34 to 38 in. above the walking surface, measured vertically to the top of the gripping surface.
Stair riser and tread
Riser heights must be 4 to 7 in. and tread depths at least 11 in.; all risers and treads in a flight must be uniform within code tolerance.
Door maneuvering clearance
The clear floor space required on each side of an accessible door: 60 in. on the pull side and 36 in. on the push side, measured from the door face.
Van-accessible parking
A parking space at least 11 ft wide with a 5 ft access aisle, required for one of every six accessible spaces, providing room for a side lift or ramp.
Type X gypsum board
Gypsum board with special core additives that improve fire-resistance; used in rated wall and ceiling assemblies such as 1-hour and 2-hour partitions.
Gypsum board screw spacing
Screws are typically spaced 12 in. on center on ceilings and 16 in. on center on walls for single-layer installation, with joints staggered between layers.
Ceiling grid hanger spacing
Main runners are supported by hangers at 4 ft on center and within 8 in. of the boundary; cross tees are spaced at 2 ft to carry the acoustical panels.
Concrete vapor emission limit
Resilient and adhesive flooring generally requires vapor emission of 3 lb or less per 1000 sq ft per 24 hours by calcium chloride test before installation.
Tile mortar coverage
Large-format tile on interior floors requires at least 95% mortar coverage; wet areas and exterior installations require 100% coverage to prevent debonding.
AWI quality grade
The Architectural Woodwork Institute defines Economy, Custom, and Premium grades that govern joinery, panel matching, and finish quality for interior millwork.
STC 50 demising wall
A sound transmission class of 50 for walls between dwelling units, typically achieved with double studs, resilient channels, and insulated cavities.
Finish schedule coordination
A document listing room finishes by code; it must match the reflected ceiling plan and door schedule to avoid conflicts during construction.
Pre-cover inspection
An inspection of framing, fireblocking, firestopping, and MEP rough-in performed before gypsum board is installed, documented with photos and signed reports.
Firestop inspection standard
ASTM E2174 covers field inspection of through-penetration firestops, and ASTM E2393 covers inspection of fire-resistive joint systems.
Substantial completion
The stage when the work is sufficiently complete for its intended use; documented on AIA G704, which states the date, incomplete items, and warranty start.
Moisture test record
Documentation of test method, date, location, and results for concrete moisture; retained for the project record and provided to the flooring manufacturer for warranty.
Mockup requirement
A full-scale sample assembly built and tested before installation, often required for exterior walls and finish systems to verify appearance, water, and air performance.
Change of occupancy
A change in a building's use classification that triggers evaluation under IEBC Chapter 10 for egress, fire protection, and accessibility compliance.
Sprinkler finish credit
In fully sprinklered buildings, IBC 803.1.2 permits Class B or C wall and ceiling finishes in many locations that would otherwise require Class A.
Corridor fire rating
Corridor walls generally require a 1-hour fire-resistance rating; 0.5-hour is permitted in sprinklered Group R-2 and certain business occupancies.