NATE Gas Heating Service: Venting and Combustion Air

NATE Gas Heating Service · Work through your exam, one topic at a time.

All guide sections

Venting and Combustion Air

Domain 2, Venting and Combustion Air, tests vent categories, draft, termination, and the air supply needed for safe combustion and dilution.

Vent categories

Category I appliances operate under negative pressure and are non-condensing; they commonly use Type B vent. Category II is negative pressure and condensing. Category III is positive pressure and non-condensing. Category IV is positive pressure and condensing, typical of high-efficiency furnaces with PVC/CPVC vent. Draft hoods dilute flue gases and stabilize draft on Category I equipment.

Draft and termination

Vent connectors slope upward about 1/4 in. per foot toward the chimney. Type B vent needs 1 in. clearance to combustibles; single-wall vent needs 6 in. Follow the 2-10 rule: the vent should terminate at least 2 ft above any roof surface within 10 ft and at least 3 ft above the roof penetration. Keep terminations away from windows, doors, and fresh-air intakes. Spillage at a draft hood is a red flag for backdrafting.

Combustion air

For a confined space using indoor air, allow 50 ft3 per 1,000 BTU/hr input and provide two permanent openings, one near the floor and one near the ceiling. With outdoor air through vertical ducts, each opening needs 1 in2 free area per 4,000 BTU/hr. Horizontal ducts need 1 in2 per 2,000 BTU/hr. Use free area, not the gross louver size.

Worked example

A 100,000 BTU/hr furnace uses outdoor air through vertical ducts. Each opening: 100,000 ÷ 4,000 = 25 in2 free area. If the ducts are horizontal: 100,000 ÷ 2,000 = 50 in2 per opening. A 25 in2 louver with 50% free area provides only 12.5 in2 and is undersized.

Traps

Do not count a bedroom door or a ceiling joist space as a permanent opening. Do not ignore exhaust fans, dryers, and tight construction, which can depressurize the space. A blocked-vent switch is a backup, not a substitute for correct vent sizing.