Spill Switch Trips After Basement Depressurization

NATE Hydronics Gas Service · Put your knowledge to work in context.

All case studies

Spill Switch Trips After Basement Depressurization

An atmospheric cast-iron boiler in a basement serves baseboard radiation. After a basement remodel tightened the house, added a bath fan and a clothes dryer, the boiler's manual-reset spill switch trips after 10 to 15 minutes of operation. The boiler is common-vented with a 40-gallon natural-draft water heater into a 6-inch Type B vent that runs 30 feet up an interior chase with two 90-degree elbows. The draft hood is hot to the touch. A hand-held CO meter reads 35 ppm in the basement near the draft hood. The homeowner has already reset the spill switch twice. The spill switch is wired in series with the 24-volt gas valve circuit. The technician measures -1.5 Pa pressure at the draft hood with the boiler and water heater running, and -3.0 Pa in the basement relative to outdoors. The vent connector has a 2-inch rise over 4 feet.

1. Explain the likely cause of the spill switch trips. Include the significance of the -1.5 Pa draft hood reading and the -3.0 Pa basement pressure.

Read the worked answer

The spill switch is doing its job. A -1.5 Pa draft hood reading is very weak; atmospheric boilers need enough draft to pull flue gases up the vent, and a draft hood is designed to spill if draft is insufficient. The basement is -3.0 Pa relative to outdoors, so the house is depressurized and the boiler is competing with exhaust fans for air. The 6-inch Type B vent may also be blocked, undersized, or improperly common-vented with the water heater. The hot draft hood and 35 ppm CO near it confirm spillage. The manual-reset switch is a safety device, not a nuisance. Do not reset it repeatedly or bypass it. Likely causes are depressurization, a vent obstruction, or both; the 2-inch rise over 4 feet is minimal and should be checked against the vent manufacturer's requirements.

2. What tests and measurements would you perform before allowing the boiler to operate again?

Read the worked answer

Perform a draft and spillage test at the draft hood with the boiler and water heater operating, using a draft gauge and smoke or flame test. Measure CO in the flue and in the basement, before and after the draft hood. Inspect the entire vent for blockage, corrosion, sagging, and correct connector slope. Verify vent capacity for the combined appliance input and the chimney height and liner. Measure the pressure difference between basement and outdoors with all exhaust fans operating. Check combustion air openings and whether the remodel sealed them. Verify the water heater and boiler are correctly common-vented and that the smaller appliance connects above the larger. Do not relight until draft is established and CO is controlled.

3. What corrections and wiring safety checks are required?

Read the worked answer

Correct the cause: provide adequate combustion air, relieve basement depressurization, and repair or resize the vent. Options include a dedicated combustion air duct sized to code, a power-vented or sealed-combustion boiler, or a properly lined chimney. Keep the spill switch in series with the gas valve control circuit. Never jumper it, remove it, or replace it with a fixed temperature switch. Verify the switch opens and resets correctly, the wiring is not damaged, and a working CO alarm is nearby. After corrections, perform a spillage test at the draft hood and confirm the switch does not trip during normal operation. Document draft, CO, and pressure readings.