NATE Hydronics Gas Service flashcards
NATE Hydronics Gas Service · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Sensible heat equation
- Q (Btu/h) = 500 × gpm × ΔT for water at standard density. Use it to relate flow, temperature drop, and heat delivered in any hydronic loop.
- Average water temperature
- AWT = (supply temperature + return temperature) / 2. Emitter output tables are based on AWT, so lower supply temperatures on condensing systems reduce radiator and baseboard output.
- Pickup allowance
- Extra capacity added to the calculated heat loss to recover from setback and warm a cold building. Common residential values are 1.10 to 1.25 times the design load.
- Design outdoor temperature
- The winter dry-bulb temperature exceeded for 99% of annual hours at the site. Equipment and radiation are sized to this value, not to record low temperatures.
- Combination gas valve
- A single body containing two safety shutoff operators in series, a pressure regulator, and often a servo. Both operators must open and prove before gas reaches the burner.
- Flame rectification
- The control applies AC to the flame rod; the flame conducts current one direction only, producing a DC microamp signal that proves flame presence to the ignition control.
- Hot-surface igniter
- A silicon nitride or silicon carbide element that glows to ignite the burner. Its resistance changes with temperature, and the control times ignition rather than measuring igniter heat.
- Condensing heat exchanger
- A secondary stainless or aluminum exchanger that cools flue gas below the water dew point, recovering latent heat. Condensate must drain to a neutralizer or suitable receptor.
- Stoichiometric air
- The exact air volume needed for complete combustion of a fuel, about 10 cubic feet of air per cubic foot of natural gas. Real appliances add excess air above this ratio.
- Excess air
- Air supplied beyond stoichiometric requirement, usually 15-50% for atmospheric burners and 5-15% for power burners. Measured as flue O₂, typically 4-8%.
- Category IV appliance
- A condensing, positive-pressure appliance that vents with listed plastic pipe and must be sealed. It cannot share a common chimney with natural-draft appliances.
- Combustion air openings
- For a confined space using outdoor air, two openings are required: one near the ceiling and one near the floor, each sized 1 square inch per 1,000 Btu/h input.
- Sediment trap
- A tee with a capped drip leg installed at the appliance inlet so dirt and pipe scale collect below the gas valve instead of fouling the internal seats and orifices.
- Manifold pressure
- Gas pressure measured at the burner manifold while firing. Typical natural gas value is 3.5 inches water column; LP is usually 10 to 11 inches water column.
- Leak test pressure
- For new gas piping, test at not less than 3 psi or 1.5 times working pressure, whichever is greater, for at least 10 minutes, with the appliance isolated.
- LP versus natural gas input
- LP gas carries about 2,500 Btu per cubic foot versus about 1,030 for natural gas, so LP orifices are smaller and manifold pressures higher for the same rated input.
- Low-water cutoff
- A safety control that opens the burner circuit when boiler water falls below a safe level. It must be tested annually and mounted above the lowest safe water line.
- High-limit aquastat
- A safety temperature switch set above normal operating temperature, typically 180 to 200 degrees Fahrenheit. It opens the burner circuit to prevent overheating or steaming.
- Trial for ignition
- The timed period after the gas valve opens during which the control looks for a flame signal. No signal within that period causes lockout and valve closure.
- Zone valve end switch
- A switch inside the zone valve that closes when the valve opens fully, completing the circuit to start the boiler and circulator on a call for heat.
- Closely spaced tees
- Two tees piped no more than four pipe diameters apart that hydraulically separate the boiler loop from the distribution loop, allowing each to run at its own flow rate.
- Point of no pressure change
- The location where the expansion tank connects to the system, usually the pump suction. Pressure there stays constant, so the tank must connect at that point to work correctly.
- Pump curve
- A graph of a circulator's flow versus head. The actual operating point is where the pump curve crosses the system curve, which determines real gpm delivered.
- Air separator
- A device at the hottest, lowest-pressure point of the system that releases entrained air. It is paired with the expansion tank connection to keep air out of loops.
- Combustion efficiency
- Calculated from flue oxygen or carbon dioxide and stack temperature. Condensing boilers in condensing mode reach above 90% with stack temperatures near 100 to 130 degrees Fahrenheit.
- Delta-T verification
- Measured supply minus return temperature at design flow. Low delta-T with high flow suggests excess flow or a fouled exchanger; high delta-T suggests restricted flow.
- High-fire and low-fire readings
- Combustion measurements taken at both maximum and minimum modulation. A modulating boiler must stay within carbon monoxide and oxygen limits across the whole firing range.
- Startup documentation
- A record of inlet and manifold gas pressures, combustion readings, and safety-device test results left with the equipment so future service can compare against baseline values.
- Flame signal microamps
- The DC current a flame rod returns to the control, typically several microamps. Low or unstable readings point to a dirty rod, poor ground, or wrong flame position.
- Rollout switch trip
- A safety switch that opens when flame escapes the burner area. Causes include blocked flue, downdraft, or dirty burners; correct the cause before resetting.
- Waterlogged expansion tank
- A tank whose bladder has failed and filled with water, eliminating the air cushion. System pressure rises quickly when hot and relief valve may weep.
- Short cycling
- Rapid on-off burner operation from oversizing, low water volume, high limit set too low, trapped air, or zone flow mismatch. Check cycle time and boiler delta-T.