32 cards. Read the term and the definition here. The deck at the top of this page is optional.

Superheat definition
The difference between the measured suction-line temperature and the saturated evaporating temperature at the same pressure, showing how far the vapor has risen above saturation.
One ton of refrigeration
A cooling rate equal to 12,000 Btu per hour or 200 Btu per minute, the heat removal needed to freeze one ton of ice in 24 hours.
Ohm's law
Voltage equals current times resistance, written E = I × R. For example, 240 volts across 24 ohms produces 10 amps of current flow.
Nitrogen purge while brazing
A slow flow of dry nitrogen through the tubing during brazing displaces oxygen so carbon and oxide scale cannot form inside the refrigerant circuit.
Target superheat fixed orifice
With a fixed orifice or piston, charge is correct when measured superheat matches the manufacturer chart, commonly 10 to 15°F at design indoor wet bulb and outdoor temperature.
Subcooling TXV target
On a thermostatic expansion valve system, liquid-line subcooling of roughly 8 to 12°F indicates a full liquid column and correct refrigerant charge.
Sensible heat equation
Sensible Btu per hour equals 1.08 times standard airflow in cubic feet per minute times the dry-bulb temperature difference across the coil.
R-410A characteristics
A near-azeotropic blend running roughly 50 to 60 percent higher pressures than R-22, using POE oil, and requiring gauges and hoses rated for its pressure.
Velocity pressure formula
Air velocity in feet per minute equals 4005 times the square root of velocity pressure measured in inches of water column with a pitot tube.
Typical branch duct velocity
Supply branch ducts are usually sized for 400 to 700 feet per minute, while trunk lines run 600 to 900 feet per minute to limit noise and friction.
External static pressure
The sum of supply and return duct pressure drops measured at the air handler, typically limited to about 0.5 inch water column in residential systems.
Clocking the gas meter
Input Btu per hour equals 3600 divided by the seconds for one cubic foot of meter rotation, multiplied by the gas heating value in Btu per cubic foot.
Natural gas manifold pressure
Most natural gas appliances are set near 3.5 inches water column manifold pressure, with about 5 to 7 inches inlet supply pressure while firing.
Temperature rise check
Temperature rise in degrees Fahrenheit equals furnace output Btu per hour divided by 1.08 times blower cfm, and must fall within the nameplate rise range.
Balance point
The outdoor temperature at which heat pump heating capacity exactly equals building heat loss; below that point supplemental or auxiliary heat must make up the difference.
Defrost cycle
A timed or demand-initiated reverse-cycle operation that melts frost from the outdoor coil, typically terminating on coil temperature or a time limit.
Emergency heat mode
A control setting that locks out the compressor and uses only electric resistance or other backup heat, often selected manually after a compressor failure.
Reversing valve operation
On most residential heat pumps the solenoid is energized in heating, routing discharge gas to the indoor coil; it is de-energized for cooling mode.
Nozzle flow versus pressure
Oil nozzle flow varies with the square root of pressure, so a nozzle rated 1.00 gph at 100 psi delivers less than rated flow at a lower pump pressure.
Cad cell resistance
A cadmium sulfide flame sensor reads roughly 400 to 1000 ohms when flame is present; the primary control locks out when resistance climbs above about 1600 ohms.
Number two fuel oil heat content
A gallon of number two heating oil contains about 140,000 Btu, so a 1.00 gph nozzle firing at 100 psi releases roughly 140,000 Btu per hour.
Hydronic gpm formula
Gallons per minute equals Btu per hour divided by 500 times the temperature drop, because one gallon per minute carries 500 Btu per hour per degree.
Boiler relief valve setting
Residential hot water boilers use a pressure relief valve typically set at 30 psi, protecting the boiler and piping from overpressurization and unsafe conditions.
Diaphragm expansion tank precharge
The tank air charge is set to the system cold fill pressure, commonly 12 to 15 psi, and checked before the tank is connected to the loop.
Three-phase power formula
Three-phase watts equal volts times amps times 1.732 times power factor, used to estimate motor input power from measured current and voltage.
Economizer changeover
Rooftop economizers admit outdoor air for free cooling when outdoor enthalpy or dry-bulb temperature falls below the return air condition.
TEV superheat setting
Commercial evaporators using a thermostatic expansion valve are typically set for 4 to 6°F superheat at the coil outlet to fill the coil without floodback.
Refrigerant safety group A2L
A classification for mildly flammable, low-toxicity refrigerants such as R-32 and R-454B, carrying charge limits and ignition-source precautions in the mechanical code.
Suction riser velocity
Vertical suction risers must maintain at least 700 to 1500 feet per minute so entrained oil can be carried back up to the compressor.
Reach-in cooler temperature
Product space in a reach-in cooler is held near 35 to 38°F, with a coil temperature roughly 10 to 12°F colder than the box.
Defrost termination temperature
Electric defrost on a walk-in freezer terminates when the coil sensor reaches about 45 to 55°F, after which fans restart following a delay.
Capillary tube critical charge
Capillary tube systems have no receiver and are charged by weight; adding refrigerant to correct a partial frost pattern usually overcharges the system.