NATE Oil Service · Put your knowledge to work in context.

All case studies

Nozzle Pressure Change on a Cast-Iron Boiler

A service technician is called to a 1.25 gph oil-fired cast-iron boiler rated 175,000 Btu/h input at 100 psi pump pressure. The existing nozzle is a 1.25 gph, 80° B hollow pattern. The technician installs a 1.00 gph, 80° B nozzle and raises pump pressure to 140 psi because the supply house was out of the original size. After the change, the technician records 12.2% CO2, 0 smoke, 430°F stack temperature, 68°F ambient, and -0.03 in. w.c. overfire draft. The homeowner says the boiler now short-cycles and the rooms heat more slowly than before. The pump is a standard 1725 rpm unit, and the oil line is a two-pipe return. The technician did not measure nozzle flow or heat input after the change. The boiler has a fixed high limit and a domestic hot-water coil.

1. Calculate the actual firing rate and input of the new nozzle at 140 psi. Compare it with the original boiler input and state whether the change is acceptable as a permanent repair.

Read the worked answer

Use the nozzle flow law: actual gph = rated gph × √(actual pressure / 100). For the new 1.00 gph nozzle at 140 psi, actual flow is 1.00 × √1.40 = 1.183 gph. At 140,000 Btu/gal for No. 2 oil, input is 1.183 × 140,000 = 165,700 Btu/h. The original 1.25 gph nozzle at 100 psi was 1.25 × 140,000 = 175,000 Btu/h. The new setup is about 9,300 Btu/h, or 5.3%, lower. That derating is not automatically acceptable: the boiler data plate and listing call for 1.25 gph, and the lower input plus altered spray pattern can change the heat-exchanger match, draft, and limit cycling. As a temporary heat source it might run, but as a permanent repair it should be corrected to the listed nozzle and pressure.

2. The combustion readings look clean, yet the homeowner reports short cycling. List three plausible causes and describe a measurement or test that separates them.

Read the worked answer

Clean CO2 and smoke readings do not rule out a mechanical or control problem. Three plausible causes are: (1) the high limit is opening because boiler water temperature overshoots, perhaps from low circulator flow or a limit set too low; (2) the nozzle pattern is impinging on a surface or the flame is longer than the chamber allows, causing localized heating; (3) the thermostat anticipator or cycle rate is misadjusted, or the thermostat is in a poor location. Separate them by measuring boiler water temperature and limit continuity at the moment of shutdown, checking circulator flow and amp draw, and observing flame shape and chamber impingement. Also verify the nozzle angle and pattern against the manufacturer specification. A lower input alone would usually lengthen run time, not shorten it.

3. What nozzle and pressure combination would restore the original input using the available 1.25 gph or 1.00 gph nozzles? Explain why simply raising pressure is not a substitute for correct nozzle sizing.

Read the worked answer

To restore 1.25 gph with a 1.00 gph nozzle, pressure would need to be P = 100 × (1.25/1.00)^2 = 156 psi. That is above many residential pump and nozzle ratings and changes atomization, spray angle, and pattern; it is not a substitute for the correct nozzle. The proper repair is to install the listed 1.25 gph nozzle at 100 psi, or the manufacturer-approved equivalent, then verify pump pressure, draft, CO2, smoke, and stack temperature. If the exact nozzle is unavailable, use a manufacturer-approved alternate with the same flow, angle, and pattern, not a smaller nozzle over-pressurized. Recheck the high limit and airflow after restoring input.