NATE Oil Service cheat sheet
NATE Oil Service · Keep the key ideas within reach.
Oil Heating Fundamentals
Heat content of No. 2 fuel oil is about 138,000–140,000 Btu per gallon; use 140,000 Btu/gal for rough load estimates.
1 gallon of No. 2 oil weighs about 7.0 lb at 60°F; specific gravity is roughly 0.82–0.85 relative to water.
Heat output Btu/h = nozzle firing rate (gal/h) × 140,000 × steady-state efficiency. A 1.00 gph nozzle at 80% efficiency delivers about 112,000 Btu/h.
Degree-day method: annual Btu ≈ (design heat loss Btu/h) × 24 × heating degree days ÷ (design indoor–outdoor temperature difference), then divide by seasonal efficiency.
Heat loss by conduction: Q = U × A × ΔT, where U is in Btu/(h·ft²·°F); add infiltration and ventilation loads separately.
Hydronic systems use 1 Btu per pound per °F; water weighs 8.33 lb/gal, so 1 gal raised 1°F absorbs about 8.33 Btu.
No. 2 oil pour point is typically around 0°F to 15°F; gelling and waxing below that range starve the pump and nozzle.
Steady-state efficiency = (stack temperature rise ÷ CO₂) × a constant; higher stack rise or lower CO₂ signals lower combustion efficiency.
Stack dew point of oil flue gas is roughly 250°F–300°F; keeping net stack temperature below that range risks acidic condensation and corrosion.
Oil Burners and Combustion
Stoichiometric air for No. 2 oil is about 14.4 lb air per lb fuel, roughly 1,920 ft³ of air per gallon; burners run 1.2–1.5× that (about 12–15% CO₂).
Target smoke is a No. 0–1 Bacharach smoke spot with 11.5–13.5% CO₂ for retention-head burners; smoke above No. 2 indicates incomplete combustion.
Nozzle ratings are stamped in gph at 100 psi; actual flow varies with the square root of pressure: new gph = rated gph × √(actual psi ÷ 100).
Nozzle spray angle: 70°–80° for most flame-retention burners; 45° for narrow combustion chambers; hollow cone for retention heads, solid cone for older chambers.
Electrode gap is typically 1/8 in (0.125 in) with tips 5/16–7/16 in ahead of the nozzle face; misalignment causes delayed ignition and puffback.
Flame retention head swirls air and recirculates hot gas to stabilize ignition; head position and air shutter setting control CO₂ and smoke.
Delayed ignition and puffback commonly trace to weak ignition transformer (10,000–15,000 V), wet oil, or carbon-bridged electrode insulators.
Draft overfire target is about −0.02 in w.c. for conventional burners; flue draft after the barometric damper is typically −0.02 to −0.06 in w.c.
Combustion air requirement: roughly 1,920 ft³ per gallon at stoichiometric; at 50% excess air, plan about 2,900 ft³ per gallon.
Oil Storage and Fuel Delivery
Tank capacity in gallons: rectangular = L × W × H (ft) × 7.48; cylindrical = π × r² × length (ft) × 7.48.
A full 275-gal oval tank holds about 266 gal usable; a 330-gal tank about 300 gal; keep fill level at 80% or less for expansion and gauge accuracy.
Tank slope: pitch toward the drain/outlet end at about 1/4 in per foot so water and sludge collect at the low point for removal.
Fuel line sizing: 3/8 in OD copper is typical for one-pipe runs under about 50 ft; 1/2 in OD for longer runs or two-pipe systems.
Two-pipe system: supply and return from the pump, with a bypass plug removed; one-pipe systems require the bypass plug installed and rely on gravity return.
Lift limit for a single-stage pump is about 8–10 ft; two-stage pumps handle lifts up to about 15–17 ft with adequate vacuum.
Vacuum at the pump should not exceed about 12 in Hg (roughly 6 in Hg for two-stage); higher vacuum signals a restricted line, clogged filter, or air leak.
Tank vent must be at least 1-1/4 in and unobstructed; a plugged vent causes slow fill, tank pressurization, and oil spill during delivery.
Oil filter (10–50 micron) should be installed on the supply line ahead of the pump; a clogged filter causes low pressure, noisy pump, and nozzle starvation.
OSHA/NFPA 31 requires tanks to be on stable supports, with fill and vent outside, and a gauge or whistle to prevent overfill.
Electrical and Controls
Primary control (cad cell) sequence: thermostat calls → burner motor and ignition start → cad cell senses flame → control holds flame; if no flame in 15–45 s, lockout occurs.
Cad cell resistance: below about 1,600 ohms indicates flame present; above about 1,600 ohms (often 10,000+ with no flame) the control drops out and locks out.
Ignition transformer output is typically 10,000–15,000 V at 10–23 mA; a weak transformer causes delayed ignition and puffback.
Limit control (high-limit aquastat) breaks the burner circuit at a set high temperature; set typically 180°F–200°F for hydronic systems.
Circulator control: low-limit aquastat holds the circulator off until boiler water reaches about 120°F–140°F to prevent cold-start condensation.
Thermostat wiring: R to W calls for heat on a 24 V system; C is common; a heat-only system uses R and W only.
Blower motor and burner motor are typically 120 V single-phase; verify supply voltage and amp draw against nameplate before diagnosing.
Lockout reset: press the reset button once after correcting the fault; repeated resets without diagnosis risk flooding the combustion chamber with oil.