NC Fire Alarm: Notification Appliances and Circuits

NC Fire Alarm · Work through your exam, one topic at a time.

All guide sections

Notification Appliances and Circuits

Domain 4 covers audible and visible notification, circuit classes, and the voltage-drop checks that keep appliances operating. The exam asks you to apply performance rules, not just identify a horn or strobe.

Core rules

  • Public-mode audible appliances must produce 15 dBA above average ambient or 5 dBA above maximum ambient, whichever is greater, measured at 5 ft above the floor.
  • Sleeping areas require 75 dBA at the pillow and 15 dBA above ambient.
  • Visible appliances are selected from the NFPA 72 candela table based on room dimensions and mounting height; higher candela is required in sleeping areas.
  • Visible appliances in the same view must be synchronized.
  • Class B notification appliance circuits are supervised with an end-of-line resistor; Class A circuits return to the panel and survive a single open.
  • Verify voltage drop so the last appliance receives at least its listed minimum operating voltage.

Worked example

A corridor has an average ambient of 55 dBA and a maximum ambient of 68 dBA. Fifteen above average is 70 dBA; five above maximum is 73 dBA. The greater value, 73 dBA, governs. Measure at 5 ft above the floor and confirm the appliance is listed to produce that output at the expected voltage.

Traps

  • Using only 15 dBA above ambient when the maximum ambient is higher.
  • Forgetting the 75 dBA pillow requirement in sleeping rooms.
  • Mixing synchronized and unsynchronized strobes in one view.
  • Ignoring voltage drop on a long Class B circuit.