Quick reference

Heating, Ventilation, and HVAC Systems and Equipment

  • Sensible heat equation for air: Q = 1.08 × CFM × ΔT (BTU/h), where 1.08 derives from 60 min/h × 0.075 lb/ft³ × 0.24 BTU/lb·°F.

  • Total heat equation for air: Q = 4.5 × CFM × Δh, using enthalpy difference in BTU/lb of dry air.

  • Latent heat equation: Q = 4,840 × CFM × Δgrains/7,000, or approximately Q = 0.68 × CFM × Δgrains.

  • Gas furnace AFUE is the ratio of annual heat output to annual fuel energy input; 90%+ AFUE units are condensing and require PVC venting with condensate disposal.

  • Heat pump balance point is the outdoor temperature where heat pump capacity equals building load; below it, supplemental resistance or fossil heat is needed.

  • Electric resistance heat produces 3.412 BTU per watt-hour; COP of 1.0 equals 3.412 BTU/Wh.

  • Ventilation rate for residential dwellings per ASHRAE 62.2: Q = 0.01 × floor area (ft²) + 7.5 × (bedrooms + 1) CFM.

  • A direct-expansion evaporator coil superheat target is typically 8–12°F at design conditions for fixed-orifice systems; TXV systems target 6–10°F.

Quick reference

Refrigeration Principles and Components

  • The vapor-compression cycle order is compressor → condenser → metering device → evaporator → back to compressor.

  • Superheat = actual suction line temperature minus evaporator saturation temperature; subcooling = condenser saturation temperature minus liquid line temperature.

  • Pressure-enthalpy diagram: compressor work is the enthalpy rise from suction to discharge; refrigerating effect is the enthalpy difference across the evaporator.

  • Common refrigerants: R-410A operates at roughly 60% higher pressure than R-22; R-134a is a medium-pressure HFC used in chillers and medium-temp equipment.

  • A TXV maintains constant superheat by modulating refrigerant flow; a fixed orifice meters flow based on pressure difference only.

  • Low superheat with high suction pressure suggests an overfeeding metering device; high superheat with low suction pressure suggests undercharge or restriction.

  • Non-condensables in a system raise discharge pressure and subcooling while causing high head temperatures; purge with recovery equipment, never vent refrigerant.

  • Recovery cylinder fill limit is 80% of capacity by weight; cylinders must be DOT-approved and hydrostatically tested.

Quick reference

Load Calculations and System Sizing

  • Manual J residential load calculation accounts for envelope conduction, infiltration, internal gains, and duct losses; Manual S handles equipment selection and sensible/latent split.

  • Design temperature difference drives transmission load: Q = U × A × ΔT, where U is assembly conductance in BTU/h·ft²·°F.

  • Sensible heat ratio (SHR) = sensible load ÷ total load; equipment SHR must match or be below the calculated SHR to avoid excess latent capacity.

  • Infiltration estimation via the crack method: Q = A × L × ΔT or air-change method using CFM = volume × ACH ÷ 60.

  • Duct load in unconditioned space typically adds 10–30% to equipment sizing; Manual J applies a duct loss multiplier.

  • Oversizing causes short cycling, poor latent removal, higher humidity, and reduced equipment life; avoid oversizing by more than 15–20%.

  • Cooling equipment nominal tonnage: 1 ton = 12,000 BTU/h; verify sensible and latent capacities at design indoor and outdoor conditions.

  • Altitude and outdoor design conditions alter equipment capacity; use ACCA or ASHRAE design data for the specific North Carolina location.

Quick reference

Ductwork and Air Distribution

  • Duct sizing methods include equal friction, static regain, and velocity reduction; Manual D is the ACCA residential duct design standard.

  • Friction rate for residential duct design commonly ranges 0.06–0.10 in. w.c. per 100 ft of equivalent length.

  • Equivalent length adds fitting losses: each 90° elbow can add 20–30 ft; each 45° elbow adds roughly 10 ft of straight duct.

  • Total external static pressure available equals supply static plus return static; typical residential blower ratings are 0.5 in. w.c. total.

  • Return air sizing should generally match supply capacity; undersized returns increase static pressure and reduce airflow.

  • Duct leakage in unconditioned space should be sealed with mastic or UL 181 tape; North Carolina energy code limits duct leakage in tested systems.

  • Flexible duct must be supported at intervals not exceeding 4 ft and cannot be compressed more than 20% of its diameter.

  • Air balancing uses a manometer and balancing dampers to achieve design CFM at each terminal; total system airflow should be within ±10% of design.

Quick reference

Electrical and Controls

  • Ohm's law: V = I × R; power: P = V × I × PF for AC circuits; single-phase watts = volts × amps × power factor.

  • Motor full-load amps are read from the nameplate; conductor sizing uses 125% of FLA for continuous loads per NEC Article 440.

  • Locked-rotor amps (LRA) exceed running amps by roughly 5–6 times; hard-start kits add a capacitor to improve starting torque.

  • A run capacitor improves motor efficiency by shifting phase; a failed run capacitor causes high current draw and overheating.

  • Thermostat wiring: R (24 VAC power), C (common), W (heat), Y (cooling compressor), G (fan), O/B (reversing valve).

  • A heat pump reversing valve is energized in cooling on most brands (O terminal); B terminal configurations energize in heating.

  • Defrost controls initiate defrost based on coil temperature and time; demand defrost uses sensors to reduce unnecessary cycles.

  • Control transformers step 240/208 V or 120 V down to 24 VAC; a shorted control circuit often blows the low-voltage fuse.

Quick reference

Fuel Gas and Combustion Safety

  • Complete combustion of natural gas requires approximately 10 cubic feet of air per cubic foot of gas; 15 ft³ is used for design safety margin.

  • Combustion products include CO₂, water vapor, and CO; carbon monoxide is produced by incomplete combustion and is lethal.

  • A properly adjusted natural gas flame is blue with a slight yellow tip; a yellow, lazy flame indicates insufficient primary air.

  • Gas piping sizing uses the longest-run method and the NFPA 54 / International Fuel Gas Code tables based on BTU/h input and specific gravity.

  • Sediment trap (drip leg) must be installed on the gas line upstream of the appliance controls to protect the gas valve.

  • Combustion air: a confined space requires two permanent openings sized per code; a 50 ft³ per 1,000 BTU/h standard applies to unconfined spaces.

  • Flue venting for Category I appliances requires a minimum vertical rise and proper termination; Category IV condensing appliances use PVC and positive pressure venting.

  • Gas leak testing uses a manometer or bubble solution; never use a flame to test for leaks, and purge lines before ignition.

Quick reference

North Carolina Building and Mechanical Codes and Licensing Regulations

  • North Carolina adopts the International Residential Code and International Mechanical Code with state amendments; the NC Building Code is enforced by local code officials.

  • The North Carolina State Board of Examiners of Plumbing, Heating, and Fire Sprinkler Contractors licenses heating contractors; a license is required to contract for HVAC work.

  • HVAC license classifications include H-1 (unlimited), H-2, and H-3, with H-3 limited in scope; licensing requires examination and continuing education.

  • North Carolina requires a permit before installation or replacement of HVAC equipment; inspections occur at rough-in and final stages.

  • The NC Energy Conservation Code references the IECC with state amendments, including duct leakage and equipment efficiency requirements.

  • Refrigerant handling requires EPA Section 608 certification; North Carolina enforces federal refrigerant rules through licensed technicians.

  • Changeout permits must match equipment sizing to the load calculation; equipment replacement cannot increase capacity without justification.

  • License renewal requires continuing education hours per the Board's current rules; verify current cycle requirements directly with the Board.

Quick reference

Business, Contract, and Project Management

  • Gross profit margin = (price − cost) ÷ price; markup = (price − cost) ÷ cost; a 30% margin equals a 42.9% markup.

  • Break-even volume = fixed costs ÷ contribution margin per job; contribution margin = price minus variable cost.

  • A written contract should specify scope, price, payment schedule, change-order procedure, warranty terms, and dispute resolution.

  • North Carolina mechanics' lien rights must be perfected by filing within the statutory period after last furnishing labor or materials.

  • Change orders must be documented in writing and signed before performing out-of-scope work to preserve payment rights.

  • Job costing tracks labor, material, equipment, and overhead per job; comparing estimated to actual cost identifies profit leakage.

  • Retainage is commonly 5–10% withheld until substantial completion; track it as a receivable, not as collected revenue.

  • Warranty obligations should be defined separately from manufacturer equipment warranties, which typically cover parts only.

Quick reference

Safety and Environmental Practices

  • Personal protective equipment for HVAC work includes safety glasses, gloves, hearing protection, and steel-toe boots; lockout/tagout is required before servicing energized equipment.

  • Refrigerant exposure causes frostbite and asphyxiation; use a refrigerant monitor in confined spaces and ventilate before entering.

  • Never vent refrigerant to the atmosphere; recover, recycle, or reclaim per EPA Section 608 requirements.

  • Carbon monoxide alarms should be installed outside sleeping areas and on each level of a dwelling per code.

  • Confined-space entry requires atmospheric testing for oxygen, CO, and combustible gas, plus an attendant and permit.

  • Ladder safety: maintain a 4:1 ratio of working height to base distance and maintain three points of contact.

  • Electrical safety: verify de-energization with a meter, treat all circuits as live until tested, and use GFCI protection on temporary power.

  • Refrigerant cylinders must be stored upright, secured, and away from heat; never heat a cylinder with an open flame to speed transfer.