NC Water/Wastewater Operator study materials
NC Water/Wastewater Operator study resources

NC Water/Wastewater Operator flashcards

NC Water/Wastewater Operator · Build recall with a focused review session.

32 cards. Read the term and the definition here. The deck at the top of this page is optional.

CT value
The product of disinfectant residual concentration in mg/L and effective contact time in minutes, used to demonstrate the required inactivation of Giardia and viruses.
Jar test
A bench-scale procedure that mixes raw water with different coagulant doses and pH values to find the dose giving the lowest filtered turbidity.
Alum alkalinity demand
Each mg/L of alum applied consumes roughly 0.45 to 0.5 mg/L of alkalinity as CaCO3, so low-alkalinity waters may need lime addition.
Filter loading rate
Flow through a filter in gallons per minute divided by the filter surface area in square feet; rapid sand filters typically operate at 2 to 4 gpm/ft².
Combined filter effluent turbidity
Regulatory limit of 0.3 NTU or less in at least 95 percent of monthly samples, and never more than 1 NTU, under the surface water treatment rule.
Chlorine demand
The amount of chlorine consumed by microorganisms, ammonia, and other reducing substances during contact; dose equals demand plus the residual you want to maintain.
Pounds formula
Pounds of chemical = concentration in mg/L times 8.34 times volume in million gallons; used to convert a dose into the weight of chemical needed.
Langelier Saturation Index
A calculated index that predicts calcium carbonate behavior: positive values indicate scale-forming water, negative values indicate corrosive water, and near zero is balanced.
Head to pressure conversion
Pressure in psi equals feet of head multiplied by 0.433; conversely, divide psi by 0.433 to find feet of head.
Hazen-Williams C factor
A roughness coefficient in the Hazen-Williams head loss formula; higher values mean smoother pipe and less friction loss for the same flow.
Water hammer
A pressure surge caused by a rapid change in flow velocity, such as fast valve closure; prevented with slow closure, surge tanks, and air valves.
Minimum distribution pressure
North Carolina requires at least 20 psi at all points in the distribution system, while normal service pressures are typically 35 to 60 psi.
Backflow prevention methods
Air gaps provide the highest protection, followed by reduced-pressure zone assemblies and double check valves; selection depends on the degree of hazard.
Pipe volume formula
Gallons in a pipe equal 0.785 times the diameter in feet squared times the length in feet times 7.48 gallons per cubic foot.
Main flushing velocity
Flushing should move water through mains at 2.5 feet per second or faster to scour and carry away sediment and stale water.
Elevated tank pressure
Each foot of water elevation produces 0.433 psi, so a tank 100 feet above a service point delivers about 43.3 psi.
Food-to-microorganism ratio
Pounds of BOD5 applied per day divided by pounds of MLSS under aeration; conventional activated sludge runs about 0.2 to 0.5.
Sludge volume index
Settled sludge volume in mL/L after 30 minutes times 1000, divided by MLSS in mg/L; values of 80 to 150 mL/g indicate good settling.
Mean cell residence time
The pounds of solids in the aeration system divided by the pounds of solids leaving each day; also called solids retention time.
Surface overflow rate
Clarifier flow in gallons per day divided by clarifier surface area in square feet; a key design and performance measure for settling tanks.
Nitrification alkalinity demand
Oxidizing ammonia consumes about 7.14 mg/L of alkalinity as CaCO3 per mg/L of ammonia nitrogen, so alkalinity can limit nitrification.
Aeration basin dissolved oxygen
Operators typically maintain about 2 mg/L of dissolved oxygen to support carbon oxidation and nitrification without wasting blower energy.
Mesophilic digester temperature
Anaerobic digesters in the mesophilic range are held near 95 degrees Fahrenheit, usually between 90 and 100 degrees, for stable digestion.
Wasting rate control
Increasing waste activated sludge lowers mean cell residence time and MLSS; decreasing wasting raises both and can overload clarifiers.
Manning's equation
Velocity equals 1.486 divided by roughness n, times hydraulic radius to the two-thirds power, times slope to the one-half power, in English units.
Minimum sewer velocity
Gravity sewers should flow at 2 feet per second or more at design flow to keep solids moving and prevent deposition.
Maximum sewer velocity
Flow above about 10 to 15 feet per second can erode pipe walls and manholes, so steep grades need drop structures or energy dissipation.
Infiltration versus inflow
Infiltration is groundwater that enters through defective pipes and joints; inflow is storm water entering through manholes, roofs, and direct connections.
Confined space oxygen range
Acceptable entry oxygen is 19.5 to 23.5 percent; below or above this range requires ventilation and reassessment before entry.
Hydrogen sulfide exposure limit
The permissible exposure limit for hydrogen sulfide is 10 ppm; it is immediately dangerous to life at 100 ppm and deadens smell at high levels.
Eight-inch sewer minimum slope
North Carolina requires at least 0.4 percent grade (0.004 ft/ft) for 8-inch gravity sewer; larger diameters may use flatter slopes.
Lift station wet well
A wet well stores wastewater so pumps can cycle within their run and rest times; undersized wells cause short cycling and premature pump wear.