NCCER Floor Covering · Put your knowledge to work in context.

All case studies

Backer Board Joint Cracks a Bathroom Tile Floor

A 10 ft by 12 ft bathroom is being tiled with 12-in. by 12-in. porcelain tile over 1/4-in. cement backer board on a 3/4-in. plywood subfloor. The joists are 16 in. on center. The installer butts backer-board sheets tightly together, fastens them with 1-1/4-in. screws every 8 in. along edges and in the field, and does not tape the joints. The screws penetrate the plywood and enter the joists. The installer sets tile the same day with latex-modified thinset and grouts 24 hours later. Three weeks after turnover, a hairline crack runs in a straight line across four tiles about 4 ft from the wall. Tapping reveals hollow spots along the crack, and one tile is slightly tented. The owner says the floor was fine for two weeks. The installer blames the tile. The GC asks for a cause and a repair that will not recur.

1. Diagnose the likely cause of the crack and explain why the installer's claim that the tile is defective is weak.

Read the worked answer

The crack follows a backer-board joint, which points to the substrate, not the tile. The sheets were butted, so there is no gap for movement; the joints were not taped and bedded in thinset, so the joint is a weak plane. Fasteners long enough to enter the joists tie the backer board to two different structural members, and differential deflection concentrates stress at the joint. Tiling the same day may also have trapped moisture. The tile did not fail spontaneously; the installation created a straight crack path and hollow spots. A defect claim would require evidence of tile manufacturing problems across many pieces, not a crack aligned with a known joint.

2. Describe a repair method and the installation checks needed before tile is reinstalled.

Read the worked answer

Remove the cracked and hollow tiles and cut the backer board back at least one panel width along the failed joint. Install new backer board with 1/8-in. gaps between sheets, offset from the subfloor joints, and fasten only to the subfloor with the manufacturer's screw length and schedule. Tape joints with alkali-resistant mesh and embed them in thinset. Check flatness, then reinstall tile with the specified thinset, allow cure, and grout. If hollow spots are widespread, remove the whole floor rather than spot-repair.

3. What documentation and prevention steps should the contractor put in place for the rest of the project?

Read the worked answer

Revise the work sequence: fasteners must not penetrate joists; use the correct length; gap and tape all joints; allow thinset and grout cure before traffic. Inspect before tile. Document with photos and a signed checklist. Provide the owner a written repair scope and cause statement. Keep a sample of the backer board and fasteners for the record.