This domain tests hanging, assembling, sealing, and testing duct in the field, plus coordination with other trades. Field conditions rarely match the drawings exactly.

Core rules

  • Supports: follow the project specification and code for hanger spacing and gauge. Rectangular duct needs trapeze or angle supports; round duct uses straps or saddles. Do not hang duct from sprinkler pipe, conduit, or other trades supports.
  • Fire and smoke dampers: install listed dampers in rated assemblies, with access doors and correct sleeves; never cut or modify the damper frame.
  • Sealing: match sealant to the SMACNA pressure class and seal class. Clean surfaces and seal joints, seams, and penetrations.
  • Clearances: maintain code clearances to combustibles and electrical equipment.
  • Testing: perform leakage tests before closing ceilings where required; then balance airflow with dampers.

Worked example

A 24 x 12 supply duct crosses a 1-hour rated wall. The correct detail is a listed fire damper in a sleeve, sealed to the rated assembly, with an access door on the accessible side and a fire-rated sealant. The reasoning: the wall fire rating must be maintained, and the damper must be inspectable and operable.

Traps

Supporting duct from another trades hangers; installing a fire damper where it cannot be accessed; sealing only the outside of a joint; and leaving flexible duct kinked or compressed.