Ohm's Law
The voltage across a resistive circuit equals current times resistance (E = I × R); rearranged, I = E/R and R = E/I. It applies to DC and to the resistive component of AC circuits.
Power Formula
Electrical power in watts equals voltage times current (P = E × I). Substituting Ohm's law gives P = I²R and P = E²/R, useful when only current or voltage and resistance are known.
Series Circuit
A circuit with one path for current. Current is the same through every component, voltage drops add to the source voltage, and total resistance is the sum of individual resistances.
Parallel Circuit
A circuit with multiple current paths. Voltage is the same across each branch, branch currents add to total current, and total resistance is found from 1/RT = 1/R1 + 1/R2 + ...
Kirchhoff's Current Law
At any circuit node, the total current entering equals the total current leaving; the algebraic sum of currents at a junction is zero. This reflects conservation of charge.
Kirchhoff's Voltage Law
Around any closed loop, the algebraic sum of voltage rises and drops is zero. The source voltage equals the sum of the voltage drops across the loads in the loop.
Impedance
The total opposition to alternating current, combining resistance and reactance: Z = √(R² + X²). It is measured in ohms and determines current for a given AC voltage.
Power Factor
The ratio of true power in watts to apparent power in volt-amperes, equal to the cosine of the phase angle between voltage and current. Resistive loads have a power factor of 1.
Voltage Drop Rule
NEC 210.19(A) informational note recommends no more than 3% voltage drop on a branch circuit and 5% total for branch plus feeder, for reasonable efficiency of operation.
Continuous Load
A load expected to operate at maximum current for three hours or more. Per NEC 210.19(A)(1) and 210.20(A), branch-circuit and overcurrent sizing use 125% of the continuous load.
Standard Ampere Ratings
NEC 240.6(A) lists standard overcurrent device ratings, including 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, and 250 amperes.
Ampacity
The maximum current a conductor can carry continuously under specified conditions without exceeding its temperature rating. Ampacity depends on conductor size, insulation type, and ambient temperature.
Terminal Temperature Rating
NEC 110.14(C) requires conductor ampacity to be based on the lowest temperature rating of connected terminations. Equipment rated 100 A or less typically uses the 60°C column unless marked otherwise.
Equipment Grounding Conductor
The conductor that connects exposed non-current-carrying metal parts to the grounding system, providing a low-impedance fault path. It is green, green with yellow stripe, or bare.
Grounded Conductor
The intentionally grounded circuit conductor, commonly the neutral, identified by white or gray insulation. It carries normal return current but is not the equipment grounding conductor.
GFCI Protection
Ground-fault circuit-interrupter protection detects small current imbalances to ground and trips quickly. NEC 210.8 requires it in dwelling bathrooms, garages, outdoors, kitchens, and other listed areas.
AFCI Protection
Arc-fault circuit-interrupter protection detects arcing signatures in branch circuits and de-energizes them. NEC 210.12 requires it for dwelling branch circuits in bedrooms and other listed rooms.
Box Fill Calculation
NEC 314.16 assigns volume per conductor, such as 2.00 in³ for 14 AWG, 2.25 in³ for 12 AWG, and 2.50 in³ for 10 AWG. Total box volume must equal or exceed the sum.
Working Clearance
NEC 110.26 requires a clear space in front of electrical equipment at least 36 inches deep, 30 inches wide, and 6 feet 6 inches high, with depth increasing at higher voltages.
Branch Circuit
The circuit conductors between the final overcurrent device protecting the circuit and the outlet or outlets. Branch-circuit conductors are sized for load and protected against overcurrent.
Feeder
All circuit conductors between the service equipment, source of a separately derived system, or other power supply and the final branch-circuit overcurrent device. Feeders supply panelboards, not outlets directly.
Service Equipment
The necessary equipment, usually a switchboard or panelboard, connected to the load end of service conductors. It contains the main disconnecting means and service overcurrent protection.
Overcurrent
Any current in excess of the rated current of equipment or the ampacity of a conductor, including overloads, short circuits, and ground faults. Overcurrent devices protect conductors from damage.
Short Circuit
An unintentional low-resistance connection between two circuit points at different potentials, producing very high current. A short circuit bypasses the normal load and trips overcurrent protection.
Ground Fault
An unintentional connection between an energized conductor and ground or grounded equipment. It can energize metal enclosures and is the condition GFCI devices are designed to detect.
Bonding
The permanent joining of metallic parts to form an electrically conductive path that ensures electrical continuity and capacity to conduct safely any current likely to be imposed.
Insulation Resistance
The resistance of conductor insulation to current leakage, measured in megohms with a megohmmeter. Low readings indicate moisture, contamination, or insulation damage and require correction.
Voltage Divider
In a series circuit, the voltage across one resistor equals the source voltage times that resistance divided by total resistance. This follows from common current and Ohm's law.
Conductor Resistance Formula
Resistance equals resistivity times length divided by cross-sectional area (R = ρL/A). Doubling conductor length doubles resistance; doubling cross-sectional area halves it.
Alternating Current
Current that periodically reverses direction, typically 60 Hz in North America. AC allows voltage transformation and dominates utility power distribution over long distances.
Inductive Reactance
Opposition to AC current from inductance, calculated as XL = 2πfL. Reactance rises with frequency and inductance, causing current to lag voltage in an inductive circuit.
Capacitive Reactance
Opposition to AC current from capacitance, calculated as XC = 1/(2πfC). Reactance falls as frequency and capacitance rise, causing current to lead voltage in a capacitive circuit.