Ohm's law
E = I × R, where E is voltage in volts, I is current in amperes, and R is resistance in ohms. In AC circuits impedance Z replaces R.
Three-phase power formula
For a balanced three-phase load, P = √3 × E_line × I_line × power factor. This gives real power in watts when line voltage and line current are used.
Conductor resistance formula
R = K × L / CM, where K is the resistivity constant (12.9 for copper, 21.2 for aluminum), L is length in feet, and CM is circular mils.
Voltage drop single phase
VD = 2 × K × I × L / CM for a single-phase circuit, where the factor 2 accounts for the outgoing and return conductors. Three-phase uses √3 instead of 2.
NM-B cable use
Nonmetallic-sheathed cable is permitted in one- and two-family dwellings and normally dry locations. It must be protected from physical damage and cannot be embedded in masonry.
EMT support interval
Electrical metallic tubing must be supported within 3 ft of each box or fitting and at intervals not exceeding 10 ft along the run.
Liquidtight flex limit
Liquidtight flexible metal conduit is limited to 6 ft between a box or fitting and the equipment it supplies unless the circuit is protected by the tap rules.
Direct burial cable
Type UF cable is suitable for direct burial at the depths specified in the burial table and requires supplemental protection where it emerges from the ground.
Grounding electrode conductor size
The grounding electrode conductor to a rod, pipe, or plate electrode is not required to be larger than 6 AWG copper or 4 AWG aluminum.
Main bonding jumper
The main bonding jumper connects the grounded conductor to the equipment grounding conductor at the service disconnect and is sized per the service conductor table.
Equipment grounding conductor sizing
Equipment grounding conductors are sized from the EGC table based on the rating of the overcurrent device protecting the circuit, not solely on conductor ampacity.
Separately derived system bonding
A separately derived system requires a system bonding jumper and a grounding electrode conductor connected to a grounding electrode at the source location.
Standard OCPD ratings
Standard overcurrent device ratings include 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, and 400 A.
Next-higher-size rule
Where conductor ampacity does not match a standard OCPD rating, the next higher standard rating may be used only if it does not exceed 800 A.
Continuous load OCPD rule
The overcurrent device must be at least 125% of the continuous load plus 100% of the noncontinuous load for the circuit it protects.
Series-rated system
A series-rated combination requires the downstream overcurrent device to be listed and marked for use with the specific upstream device, establishing the equipment short-circuit current rating.
Small-appliance branch circuits
A dwelling kitchen requires at least two 20 A small-appliance branch circuits, and these circuits may not supply lighting outlets.
General lighting load dwelling
The general lighting load for a dwelling unit is 3 VA per square foot of floor area, with demand factors applied to the portion above 3,000 VA.
Receptacle spacing dwelling
In dwelling units, no point along the floor line may be more than 6 ft from a receptacle, and any wall space 2 ft or wider requires a receptacle.
Service calculation steps
Compute general lighting, small-appliance, laundry, and fixed appliance loads; apply demand factors; add the largest motor at 25%; then size service and feeder conductors.
Motor branch-circuit conductors
Motor branch-circuit conductors must have an ampacity of at least 125% of the motor full-load current taken from the motor tables.
Motor disconnecting means
The motor disconnecting means must be within sight of the motor and controller, capable of being locked open, and rated at least 115% of motor full-load current.
Motor overload protection
Overload protection is sized from the motor nameplate current and protects the motor from overload, while the branch breaker protects conductors from short circuits.
HVAC nameplate ratings
HVAC equipment nameplates give minimum circuit ampacity and maximum overcurrent protection, which govern conductor sizing and breaker selection for the unit.
Transformer primary protection
Transformer primary overcurrent protection is typically sized at 125% of primary current per the transformer table, with secondary protection sized at 125% of secondary current.
Hazardous location classification
Hazardous locations are classified by Class, Division, and Group, and equipment must be listed and marked for the specific class, division, and group.
Class I seal requirement
In Class I locations, conduit seals are required at boundaries and within specified distances, and wiring methods include threaded rigid metal conduit and listed MC cable.
Box fill calculation
Box fill is determined from the box volume in cubic inches, with each conductor counted per the box fill table and grounding conductors counted as one.
Raceway fill 40 percent
For three or more conductors, the sum of conductor cross-sectional areas must not exceed 40% of the raceway internal cross-sectional area.
Conductor ampacity adjustment
Ampacity is adjusted for ambient temperature and for the number of current-carrying conductors in a raceway or cable, applying the adjustment factors to table ampacity.
Nebraska electrical licensing
Nebraska electrical licensing is administered by the State Electrical Division, which adopts the electrical code and enforces licensing through the State Electrical Board.
Nebraska journeyman supervision
A Nebraska journeyman electrician must work under the supervision of a licensed master electrician or contractor, and a contractor license is required to offer electrical contracting services.