NEBB Testing, Adjusting and Balancing Certified Professional (CP) study materials
NEBB Testing, Adjusting and Balancing Certified Professional (CP) study resources

NEBB Testing, Adjusting and Balancing Certified Professional (CP) flashcards

NEBB Testing, Adjusting and Balancing Certified Professional (CP) · Build recall with a focused review session.

32 cards. Read the term and the definition here. The deck at the top of this page is optional.

Fan law: flow vs speed
Airflow (cfm) varies directly with fan speed (rpm) when system resistance and air density remain constant; doubling speed doubles flow.
Fan law: pressure vs speed
Fan static or total pressure varies with the square of fan speed; doubling speed quadruples pressure, assuming constant density and system.
Fan law: power vs speed
Fan brake horsepower varies with the cube of fan speed; doubling speed increases power eightfold, so verify motor capacity before speed changes.
Pump affinity laws
For a centrifugal pump, flow varies directly with speed, head with speed squared, and power with speed cubed, similar to fan laws but for water.
Velocity pressure formula
Velocity pressure (in. w.c.) equals (velocity in fpm divided by 4005) squared for standard air at 0.075 lb/ft³ density; solve for velocity as 4005 times square root of VP.
Pitot tube traverse
A grid of velocity pressure readings across a duct cross-section, taken at equal-area points, averaged to determine average velocity and airflow; requires straight duct length.
Balancing hood
A flow capture device placed over an air terminal to measure cfm directly; accuracy typically ±3% of reading when properly sealed and sized.
Proportional balancing method
A systematic technique that adjusts dampers to achieve design flow ratios at each terminal without repeated full-system measurement, starting with the farthest terminal.
Air density correction
Velocity and static pressure readings must be corrected for actual air density using temperature and barometric pressure to obtain true airflow in cfm.
Fan total pressure
The algebraic difference between total pressure at the fan outlet and total pressure at the fan inlet; used to determine fan performance and motor load.
Fan static pressure
Fan static pressure equals fan total pressure minus velocity pressure at the fan outlet; it represents the static resistance the fan must overcome.
System effect
The loss of fan performance caused by adverse inlet or outlet conditions, such as elbows or obstructions near the fan, not accounted for in catalog ratings.
Duct leakage test
A pressure test of ductwork at a specified static pressure to measure leakage cfm; acceptance criteria are based on leakage class and duct surface area.
SMACNA leakage class
A standard classification of allowable duct leakage in cfm per 100 square feet of duct surface at a given test pressure, used to specify and verify duct tightness.
Terminal unit balance
Adjusting the damper or reheat coil of a terminal box to achieve design airflow; verify minimum and maximum settings and control sequence operation.
VAV box minimum flow
The lowest airflow setpoint for a variable air volume terminal, typically set to maintain ventilation and avoid coil freeze; measured during balancing.
Water flow measurement
Use a calibrated flow meter or pressure differential across a known device (valve, coil, orifice) to determine gpm; verify with pump curve and balance valve settings.
Balance valve
A valve with a calibrated orifice and pressure ports used to measure and set water flow; its setting is recorded and locked after balancing.
Coil pressure drop
The difference in water pressure across a coil, used with the manufacturer's curve to determine water flow; also indicates fouling or air binding.
Pump curve
A graph of pump head versus flow at a given speed; the operating point is where the pump curve intersects the system resistance curve.
System resistance curve
A curve showing pressure loss versus flow for a piping or duct system; it rises with the square of flow and determines the pump or fan operating point.
Static pressure setpoint
The duct static pressure maintained by a supply fan controller, typically measured two-thirds down the main duct; used to control fan speed in VAV systems.
Duct static pressure profile
A series of static pressure readings along a duct run used to locate restrictions, verify fan performance, and confirm design pressure at terminals.
Temperature difference test
Measurement of entering and leaving air or water temperatures across a coil to verify capacity and sensible/latent performance during TAB.
Outside air measurement
Determination of outdoor air intake airflow using pitot traverse, flow station, or hood; critical for ventilation compliance and building pressure control.
Building pressure control
Adjusting relief or exhaust airflow to maintain a slight positive pressure (typically 0.02–0.05 in. w.c.) relative to outdoors, preventing infiltration.
Exhaust fan balance
Setting exhaust airflow to design values by adjusting dampers or fan speed, while coordinating with makeup air to avoid negative building pressure.
Return air plenum
A ceiling cavity used as a return air path; balancing requires measuring return grille flows and ensuring plenum pressure does not cause leakage.
Test instrument calibration
Verification of measurement devices against a known standard before and after TAB; records must be traceable and within manufacturer's accuracy tolerance.
TAB report contents
Documentation of design versus measured values for airflow, water flow, pressure, and temperature, plus instrument calibration records and deficiency list.
Pre-balance checklist
Verification that fans run correctly, filters are clean, dampers open, controls operational, and design conditions exist before starting balancing measurements.
Proportional balance ratio
The ratio of measured airflow to design airflow at each terminal; dampers are adjusted so all ratios are equal, then the system is set to design.