NETA ETT Level 3 study materials
NETA ETT Level 3 study resources

NETA ETT Level 3 flashcards

NETA ETT Level 3 · Build recall with a focused review session.

32 cards. Read the term and the definition here. The deck at the top of this page is optional.

Arc flash PPE category 2
Arc-rated PPE category corresponding to incident energy up to 8 cal/cm²; requires arc-rated shirt and pants or coverall plus face protection and hearing protection.
Restricted approach boundary
Boundary within which only qualified persons may work, requiring shock protection; distance depends on voltage and is closer than the limited approach boundary.
Electrically safe work condition
State achieved by identifying and disconnecting all sources, locking out, releasing stored energy, and verifying absence of voltage with a tested meter.
NETA ATS purpose
Acceptance Testing Specifications define inspections, electrical tests, and acceptable values for new equipment before it is placed into service.
IEEE C57.152 scope
Guide for diagnostic field testing of liquid-immersed power transformers, covering test methods and interpretation of results for in-service units.
IEEE 400.2 scope
Standard for field testing of shielded power cable systems using very low frequency (0.1 Hz) AC voltage, including withstand and diagnostic tests.
Meter counts error
Specification term added to percent-of-reading error; one count equals the smallest digit shown on the display at that range.
CAT III rating
Measurement category for distribution-level circuits and fixed installations; withstands higher transient overvoltages than CAT II but less than CAT IV.
True-RMS meter
Instrument that computes the root-mean-square value of a waveform, giving correct readings on distorted or non-sinusoidal signals where averaging meters err.
Polarization Index
Ratio of insulation resistance at 10 minutes to that at 1 minute; values of 2.0 or higher generally indicate dry, uncontaminated insulation.
Dielectric Absorption Ratio
Ratio of insulation resistance at 60 seconds to that at 30 seconds; below 1.25 is questionable and above 1.4 is good for Class A insulation.
Guard terminal use
Connection that shunts surface leakage current around the meter so the reading reflects volume resistance of the insulation rather than contamination on surfaces.
IR temperature correction
Insulation resistance roughly halves for each 10 °C rise; readings are corrected to a reference temperature such as 40 °C before comparison.
Kelvin four-wire method
Measurement technique using separate current and voltage leads so lead resistance is excluded; required for accurate readings below about 1 ohm.
Copper resistance correction
Formula R2 = R1 × (234.5 + T2)/(234.5 + T1) converts measured winding resistance to a reference temperature using the copper constant 234.5 °C.
Transformer turns ratio test
Verifies the voltage ratio and polarity between windings; deviation beyond about 0.5% from nameplate suggests shorted turns or tap errors.
SFRA test
Sweep frequency response analysis compares a transformer's impedance signature to a baseline; shifts in resonance peaks indicate winding deformation or core movement.
Dissolved gas analysis
Test of insulating oil for fault gases; acetylene indicates arcing, ethylene indicates thermal faults, and hydrogen indicates partial discharge or corona.
Doble power factor test
Insulation power factor test run in configurations CH, CL, CHL, and guarded variants; rising values indicate moisture or contamination in the insulation.
Breaker contact resistance
Micro-ohm measurement across closed contacts; rising values versus baseline indicate pitting, misalignment, or loosened connections in the current path.
Breaker motion analysis
Records contact travel, velocity, bounce, and damping during operation; slow closing or excessive bounce indicates worn linkages or incorrect spring adjustment.
Minimum trip voltage
Test confirming the breaker closes and trips within 70-110% of rated control voltage; failure indicates a weak coil or mechanism problem.
CT ratio and polarity
Test injecting primary current and measuring secondary output; P1-to-S1 is subtractive polarity, and reversed polarity causes differential relay misoperation.
CT saturation knee point
Point on the excitation curve where secondary current no longer rises proportionally; beyond it, ratio error grows rapidly during faults.
Relay pickup test
Slowly increasing current or voltage until the relay operates; the value is compared to the setting sheet to confirm correct calibration.
Differential relay slope test
Injects through-current and internal fault current to verify the restraint characteristic; through-current must not trip and internal faults must trip.
VLF cable testing
Very low frequency (0.1 Hz) AC withstand test per IEEE 400.2, preferred for aged XLPE cable because it limits space charge compared with DC testing.
Fall-of-potential method
Three-point grounding test placing the potential probe at 62% of the distance to the current probe to reduce mutual coupling error in the reading.
Time domain reflectometry
Cable fault location method sending a pulse and timing its reflection; distance equals velocity of propagation times time divided by two.
Surge comparison test
Applies a steep-front voltage pulse to each motor phase and compares waveforms; differences reveal turn-to-turn or coil-to-coil insulation faults.
Motor minimum IR
Per IEEE 43, minimum insulation resistance in megohms equals rated kV plus one, corrected to 40 °C; lower values require drying before energization.
Motor current signature analysis
Analyzes the stator current spectrum for sidebands around line frequency to detect rotor bar faults, eccentricity, and bearing problems without disassembly.