NFPA CFI-I flashcards
NFPA CFI-I · Build recall with a focused review session.
33 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Authority having jurisdiction (AHJ)
- The organization, office, or individual responsible for approving equipment, installations, or procedures under the adopted code; the inspector acts as or on behalf of the AHJ.
- Adopted code edition
- The specific edition of a code formally adopted into law by the jurisdiction; inspections are judged against that edition, and later editions do not apply retroactively.
- Notice of violation
- A written document stating the code section violated, the condition observed, the required corrective action, and a compliance deadline; it also states appeal rights and procedures.
- Imminent hazard
- A condition presenting an immediate threat to life or property that permits the AHJ to order immediate correction or restrict occupancy without waiting for the normal appeal period.
- Right of entry
- The inspector's legal authority to enter and examine premises, derived from statute or ordinance; entry without consent generally requires an administrative warrant or statutory authority.
- Occupancy classification
- The category assigned to a building or space under NFPA 101 based on its use and occupant characteristics; it determines egress, sprinkler, and alarm requirements.
- Occupant load
- The total number of persons a space is designed to hold, computed by dividing floor area by the occupant load factor for the use; it drives egress width and exit requirements.
- Egress width per occupant
- The code allowance used to size egress components, commonly 0.2 inches per occupant on level surfaces and 0.15 inches per occupant on stairs and ramps.
- Exit access, exit, exit discharge
- The three components of a means of egress: the path to the exit, the protected exit itself, and the route from the exit to the public way.
- Travel distance
- The measured length of the natural path of travel from the most remote point in a space to the nearest exit, limited by occupancy and sprinkler protection.
- Exit remoteness
- The required separation between two exits, measured diagonally so that exits are separated by at least one-half the diagonal of the room or area served.
- Single-motion egress door
- Egress door hardware that releases with one operation without a key, special knowledge, or effort; required where the occupant load or hazard triggers panic hardware.
- Emergency lighting duration
- The required period that emergency illumination must be maintained, commonly 90 minutes, verified by monthly 30-second tests and an annual full-duration test.
- Illuminated exit sign
- A sign marked EXIT that is illuminated and visible from any point in the path of travel, with power-source and testing requirements set by the adopted code.
- NFPA 25
- The standard for inspecting, testing, and maintaining water-based fire protection systems; it sets frequencies for gauges, alarms, main drains, and valve exercises.
- Supervised control valve
- A sprinkler control valve that is electronically supervised or locked open so that closure is detected; an unsupervised closed valve is a critical violation.
- Fire department connection
- The exterior connection used by firefighters to supplement the water supply; it must be accessible, unobstructed, capped, and marked with signage identifying the system served.
- Fire pump churn test
- A weekly no-flow run of a fire pump to verify automatic starting and operation; annual flow testing verifies performance against the pump curve.
- Hydrant flow test
- A test measuring static and residual pressure at a known flow to estimate the water supply available for fire protection at the required residual pressure.
- NFPA 72
- The National Fire Alarm and Signaling Code, which sets inspection and testing requirements for initiating devices, notification appliances, and monitoring of fire alarm systems.
- NFPA 10
- The standard for portable fire extinguishers; it requires monthly inspections, annual maintenance, proper mounting, and selection of extinguishers rated for the hazard present.
- Flammable liquid classification
- Classification of liquids by flash point and boiling point under NFPA 30; the class sets allowable container sizes, cabinet limits, and storage requirements.
- Flammable storage cabinet limit
- The maximum quantity a single cabinet may hold, commonly 60 gallons of Category 1-3 flammable liquids or 120 gallons of Category 4 combustible liquids.
- Hot work permit
- A written authorization for welding, cutting, or grinding that specifies a fire watch, clearance of combustibles, and post-work monitoring before the area is released.
- Compressed gas cylinder storage
- Requirements that cylinders be secured upright, separated from oxidizers, kept away from heat and exits, and stored within permitted quantities with proper signage.
- Combustible dust hazard
- A deflagration risk from accumulated combustible particulate solids; inspection focuses on housekeeping, ignition control, and dust collection under NFPA 652.
- Fire resistance rating
- The period in hours that a structural element or assembly resists fire; it depends on construction type and occupancy and is verified against approved plans.
- Construction Type I
- A construction type with noncombustible structural elements and high fire resistance, defined by combustibility and rating in NFPA 220.
- Fire wall versus fire barrier
- A fire wall divides a building into separate buildings and must be structurally independent; a fire barrier subdivides one building and must be continuous floor to deck.
- Opening protectives
- Rated fire doors and windows installed in rated walls; they must be self-closing or automatic-closing and unobstructed, and propping them open is a violation.
- Through-penetration protection
- A listed system used to seal a pipe or cable passing through a rated assembly so the assembly retains its fire resistance rating; unsealed penetrations are serious deficiencies.
- Flashover
- The transition from a growing fire to full compartment involvement, driven by heat release rate and ventilation, marking the shift to the fully developed stage.
- Inspection report documentation
- A contemporaneous, factual record of observed conditions including location, date, measurements, photographs, and the code basis, which serves as evidence in enforcement actions.