During a routine inspection of a 4,000-square-foot restaurant with a posted occupancy of 120, you find the rear exit door padlocked and chained, a stack of cardboard boxes blocking the side exit, two portable heaters in the dining room, and a fire extinguisher with a 2019 service tag. The sprinkler system has a contractor's red tag dated three months ago noting the main control valve is closed. The manager says the rear door is locked "for security" and the valve was closed for repairs. The dining room is set for 90 seats and it is 18:30 on a Friday.

1. What immediate actions do you take, and what is your authority?

Read the worked answer

This is an imminent life-safety hazard, not a paperwork finding. I order the rear door unlocked and unchained and the side exit cleared immediately, and I confirm both are operable before I leave the area. If the manager will not comply, I escalate to the fire marshal or chief officer with authority to close the occupancy or require an immediate fire watch.

Authority: as an inspector I act under the adopted fire code and the authority having jurisdiction. I do not need the manager's permission to abate an exit obstruction that places 90 seated occupants at risk. I document the condition as found, with the time and the manager's statements, and I do not accept "for security" as a reason to defeat a required exit. The sprinkler valve issue is handled the same way: it is restored or a fire watch is posted until it is.

2. How do you prioritize these hazards, and which is most life-safety critical?

Read the worked answer

The blocked and locked exits are the top priority, followed closely by the closed sprinkler control valve. Both affect the ability of a full dining room to survive a fire tonight. The cardboard blocking the side exit and the chained rear door reduce two means of egress; the closed valve removes the automatic suppression system. Together they are a compounded hazard, not two separate minor findings.

The portable heaters and the expired extinguisher service tag matter, but they are secondary: they increase ignition risk or reduce a first-aid fire capability, while the exits and sprinkler affect the entire occupant load at once. I address the exit obstruction first because it can be corrected in minutes, then the valve because restoration may require a contractor and a fire watch.

3. What follow-up, documentation, and re-inspection do you require?

Read the worked answer

I write a notice of violation with each item, the code section, the location, and a correction deadline, and I give a copy to the manager and the owner. I photograph the locked rear door, the blocked side exit, the red tag, and the heaters. I require the valve to be restored by a qualified contractor and the system returned to service, with a fire watch posted in the interim if the occupancy stays open.

Re-inspection: I return unannounced within the correction period, verify the exits operate and the valve is open, and check that the fire watch log exists if one was required. I notify the fire marshal of the imminent hazard and any refusal to comply. If the owner repeats the violation, I escalate to citations or occupancy closure rather than issuing another routine notice.