Class A initiating circuit
An initiating device circuit with a return path to the control unit so a single open conductor does not disable any device. It is the survivability baseline for many high-rise and healthcare designs.
Class B initiating circuit
An initiating device circuit with no return path; a single open disables all devices beyond the break. T-taps are not permitted, and fault location must be found during troubleshooting.
Class X pathway
A pathway designation that supervises the communication path for integrity in addition to connectivity, so failure of the path itself is annunciated. It is used for critical network links between panels.
Proprietary supervising station
A receiving location owned and operated by the protected property, staffed and receiving signals from fire alarm systems on that property only. It cannot serve other properties or customers.
Central station
A listed, privately owned supervising station that monitors systems for many customers under contract, with listed operator staffing, redundancy, and retransmission to the fire department.
Auxiliary supervising station
A facility that receives alarm signals over a public fire alarm box or municipal circuit and forwards them to the fire department, without the full service scope of a central station.
Remote supervising station
A listed location, other than proprietary or central station, that receives and retransmits signals from protected premises. Staffing and retransmission requirements are specified by NFPA 72.
Smoke detector spacing 30 ft
Listed spot-type smoke detectors with a 30 ft (9.1 m) listed spacing are installed on a grid of 30 ft, with the nearest detector within 21 ft (6.4 m) of any wall per the spacing rule.
Public mode audibility
Notification must produce 15 dBA above the average ambient sound level, or 75 dBA at 10 ft, whichever is greater, measured in the occupied area during normal conditions.
Sleeping area audibility
Alarm signaling in sleeping areas must reach 75 dBA at the pillow with the door closed, and low-frequency 520 Hz signaling is required in many occupancies to reliably awaken occupants.
Visible notification spacing
Strobes are spaced per the manufacturer's listed candela rating and the room size and mounting height, with reduced spacing in corridors and higher candela where required by the listing.
Duct smoke detector
A detector installed in an air duct to detect smoke in the airstream and initiate fan shutdown or smoke control. Placement follows listed airflow and straight-duct requirements.
Supervising station retransmission
The time limit for a supervising station to retransmit an alarm to the fire department after receipt. The limit is specified in NFPA 72 and varies by station category.
Positive alarm sequence
A feature that delays notification for a set investigation period after an alarm, provided the signal is acknowledged and investigated within the allowed time; otherwise the alarm is processed normally.
Presignal
A feature that routes alarm signals to a constantly attended location for acknowledgement before general notification. It requires staffing and AHJ acceptance and is limited in some occupancies.
Annunciator
A remote display that shows device status, alarm, and trouble by zone or point. It supplements the control unit and does not replace required annunciation at the main panel.
NFPA 72 Chapter 14
The inspection, testing, and maintenance chapter. Its tables set the frequency and method for each device and system function, from monthly to 5-year and 10-year reacceptance tests.
Acceptance test record
Documentation of the initial acceptance test, including devices tested, results, and signatures of the installing contractor and witness. It is required before the system is placed in service.
Record of completion
A form documenting the installed system, its configuration, and the owner's responsibilities. It is required at acceptance and updated when the system is modified.
Impedance of a circuit
The total opposition to current flow, including resistance and reactance. It determines voltage drop on notification circuits and whether devices at the end operate within their listed range.
Voltage drop calculation
Voltage drop equals current times conductor resistance over the run. Notification appliance circuits must keep the voltage at the farthest appliance within its listed operating range at worst-case battery voltage.
Battery capacity calculation
Standby current times standby hours plus alarm current times alarm minutes, divided by the derating factor. The result sets battery size and must be documented in the submittal.
Secondary power supply
The battery or other backup source that powers the system when normal power fails. It must support standby and alarm loads for the durations required by code and listing.
Addressable device
A device with a unique address on the signaling line circuit, allowing point identification of alarms and troubles. Addressable does not by itself mean the circuit is Class A.
Signaling line circuit
The circuit connecting addressable devices to the control unit. It is supervised for opens, shorts, and ground faults, and its class determines survivability under fault conditions.
Ground fault
An unintended connection between a conductor and ground. It is supervised and annunciated as a trouble, and must be located and corrected before it causes false alarms or failures.
Supervisory signal
A signal indicating a change in a monitored condition, such as a closed valve or low air pressure, that could impair system performance. It is annunciated as a supervisory, not an alarm.
Trouble signal
A signal indicating a fault in the system, such as an open circuit, ground fault, or loss of power, that could impair operation. It must be annunciated audibly and visibly.
Alarm signal
A signal initiated by a manual pull station or automatic detector indicating fire. It takes priority over supervisory and trouble signals in the system's annunciation hierarchy.
Smoke control interface
The connection between the fire alarm system and smoke control equipment, such as fans and dampers. It must be supervised and tested to verify the intended sequence of operation.
Elevator recall
A sequence that, on alarm, returns elevators to a designated landing and prevents use. It requires supervised interfaces and testing of the recall sequence per code and AHJ requirements.
Documentation of sequence
The written cause-and-effect matrix describing what each input does to each output. It is the basis for programming, acceptance testing, and later modifications.
AHJ acceptance
The authority having jurisdiction's approval of the installed system against the adopted code and approved plans. It follows successful acceptance testing and complete documentation.