NICET Fire Alarm flashcards
NICET Fire Alarm · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- NFPA 72
- The National Fire Alarm and Signaling Code, which governs design, installation, inspection, testing, and maintenance of fire detection and alarm systems and is commonly adopted into law.
- NEC Article 760
- The National Electrical Code article covering fire alarm system wiring, including permitted cable types, installation methods, and requirements for power-limited and non-power-limited fire alarm circuits.
- Record of Completion
- An NFPA 72 form completed by the installing contractor that documents the system as installed and certifies the equipment was tested and operates as described in the approved plans.
- Authority Having Jurisdiction
- The organization or individual, such as a fire marshal, empowered to enforce code requirements and to approve equipment, installations, and testing procedures for a fire alarm system.
- UL 864
- The product safety standard under which fire alarm control units and accessory equipment are listed, confirming that minimum performance and reliability requirements are met.
- As-built drawings
- Drawings updated after installation to show actual device locations, addresses, and circuit routing, retained with the record of completion as part of required system documentation.
- NFPA 101
- The Life Safety Code, which sets occupancy-based requirements for detection, notification, and egress that a fire alarm design must satisfy along with NFPA 72.
- Shop drawings
- Submittal documents prepared before installation showing device locations, circuit routing, and supporting calculations; they require review and approval before installation begins.
- Smoke detector spacing
- On a smooth ceiling, detectors are placed at the listed spacing, commonly 30 ft, and no ceiling point may be more than 0.7 times that spacing from a detector.
- Wall-mounted detector position
- A smoke detector installed on a wall must have its top edge between 4 in and 12 in below the ceiling so it stays out of the dead-air space.
- Manual pull station height
- Manual fire alarm boxes are mounted 42 in to 48 in above the finished floor and within 5 ft of the exit door they serve.
- Public mode audibility
- In public mode, alarm signals must be at least 15 dBA above average ambient sound, or 5 dBA above maximum ambient sound lasting 60 seconds or more.
- Sleeping area audibility
- Notification in sleeping areas must produce at least 75 dBA at the pillow or 15 dBA above ambient sound, whichever is greater, measured with a sound level meter.
- Visible appliance mounting
- Wall-mounted visible notification appliances are installed with the lens 80 in to 96 in above the finished floor and at least 6 in below the ceiling.
- Waterflow alarm time
- A waterflow alarm must be annunciated within 90 seconds after flow begins, and alarm signals generally must be processed within 10 seconds of activation.
- Positive alarm sequence
- An alarm-handling feature allowing 15 seconds to acknowledge an alarm signal and up to 180 seconds of investigation by trained personnel before general evacuation.
- Class B circuit
- An initiating or notification circuit that does not survive a single open fault; an end-of-line device lets the panel annunciate that open condition as a trouble.
- End-of-line resistor
- A device placed at the end of a Class B circuit that allows the control unit to supervise conductors and detect open or short circuit faults.
- Voltage drop formula
- Vd = (2 x K x I x L) / CM, where K is 12.9 ohm-circular mils per foot for copper, I is current in amperes, and L is one-way length in feet.
- Battery aging factor
- NFPA 72 requires the calculated standby plus alarm battery capacity to be multiplied by 1.20 to account for battery aging over the life of the system.
- Standby battery duration
- Commercial fire alarm systems typically require 24 hours of standby operation followed by 5 minutes of alarm load, with the battery sized to the calculated current.
- FPLR cable
- A listed fire alarm cable rated for risers and vertical shafts; the FPLP rating is the equivalent required for fire alarm cables installed in plenum spaces.
- Cable support interval
- Power-limited fire alarm cable must be supported at intervals not exceeding 4.5 ft and within 12 in of boxes, unless it is installed in raceway.
- Separation from power conductors
- Fire alarm power-limited cables are kept at least 2 in from electric light and power conductors or separated by a barrier, crossing at right angles where possible.
- Acceptance test
- A post-installation test in which 100 percent of initiating devices and notification appliances are operated to verify the system works as designed before approval.
- Smoke detector sensitivity testing
- Detector sensitivity is checked within 1 year of installation and then every alternate year, unless the manufacturer's published instructions require more frequent testing.
- Duct detector testing
- Duct smoke detectors are tested annually using smoke or approved aerosol while confirming correct airflow and sampling tube installation, and the alarm is verified at the control unit.
- Impairment procedure
- A documented process used when a system or portion is taken out of service, requiring notification of the monitoring company and occupants and, where required, a fire watch.
- Test records retention
- Inspection, testing, and maintenance records must be documented, retained, and made available to the authority having jurisdiction on request for review.
- Battery capacity replacement
- Batteries are replaced when measured capacity falls below 80 percent of rated capacity, as determined by a load test performed on the secondary supply.
- Reacceptance testing
- Testing required after any modification, repair, or addition, covering the affected components and verifying that interfaces with other systems still operate correctly.
- Smoke detector test method
- Detectors are tested with smoke, approved aerosol, or the manufacturer's listed method; simply disabling a detector to avoid nuisance alarms is not an acceptable test.