NICET ITWBS · Build recall with a focused review session.

32 cards. Read the term and the definition here. The deck at the top of this page is optional.

NFPA 25
Standard for inspection, testing, and maintenance of water-based fire protection systems; it applies to existing systems and does not replace design requirements of NFPA 13 or 14.
NFPA 13
Standard for design and installation of sprinkler systems; used as a baseline for acceptance and for evaluating whether existing sprinkler arrangements meet design criteria.
NFPA 14
Standard for installation of standpipe and hose systems; covers classes, pipe sizing, outlets, pressure, and acceptance testing before NFPA 25 maintenance begins.
NFPA 20
Standard for stationary fire pumps; covers pump selection, installation, controllers, and acceptance testing; NFPA 25 then governs routine inspection and testing.
Lockout tagout
Procedure that isolates hazardous energy, locks controls, and verifies zero energy before servicing fire pumps, controllers, or electrical alarm circuits to prevent unexpected startup or shock.
Impairment fire watch
When fire protection is disabled, notify occupants and the authority having jurisdiction as required and provide a trained fire watch with extinguishing capability until systems are restored.
Confined space entry
Entry into pits, vaults, or tanks requires atmospheric testing, ventilation, an attendant, retrieval equipment, and authorization; oxygen deficiency or flammable gas can be fatal.
Stored energy hazard
Capacitors, springs, compressed air, and pressurized water can remain energized after isolation; release or block stored energy and verify before work begins.
Hot work permit
Written authorization for cutting, welding, or grinding near sprinkler equipment; requires area protection, fire watch, and checking for concealed combustibles before and after work.
Rated fire pump point
At 100 percent rated flow, a centrifugal fire pump must produce at least 100 percent of rated pressure; this point anchors the pump performance curve.
150 percent pump flow
At 150 percent of rated flow, a centrifugal fire pump must produce at least 65 percent of rated pressure; this confirms the curve has adequate overload capacity.
Churn pressure limit
Shutoff or churn pressure of a centrifugal fire pump generally must not exceed 140 percent of rated pressure; higher pressure can overstress system components.
Net pump pressure
Discharge pressure minus suction pressure, with gauge corrections; used to plot fire pump test results and compare performance with the rated curve.
Hydrant flow residual
During a hydrant flow test, residual pressure should not fall below about 20 psi; lower residual indicates supply limitation and possible cavitation or inadequate fire flow.
Main drain test
Full-flow test through the main drain; record static and residual pressures and compare with previous results to detect supply changes, closed valves, or obstructions.
Inspector test connection
Valve at the end of a sprinkler branch that simulates one sprinkler flow; opening it verifies waterflow alarm, pressure switch, and retard chamber operation.
Spare sprinkler inventory
Replacement sprinklers of correct type, temperature rating, and K-factor kept on site; inventory is checked during inspections and replenished after use.
Dry pipe trip test
Test that admits air or water to a dry pipe valve to verify the clapper trips, water reaches the system, alarms operate, and valve resets properly.
Gauge inspection monthly
System gauges are read monthly to compare normal supply and system pressures; unexplained changes can indicate leaks, closed valves, or water supply problems.
Class I standpipe
Standpipe system with 2.5-inch hose connections intended for fire department use; minimum residual pressure at the topmost outlet is generally 100 psi.
Class II standpipe
Standpipe system with 1.5-inch hose stations intended for occupant use; minimum residual pressure at the topmost outlet is generally 65 psi.
Standpipe hydrostatic
Pressure test of standpipe piping at 200 psi for two hours or 50 psi above maximum system pressure, whichever is greater, with no leakage.
Fire department connection
Connection where a pumper supplies a standpipe or sprinkler system; inspect caps, threads, gaskets, clappers, signage, and unobstructed access.
OS&Y valve position
Outside screw and yoke valve is open when the stem extends from the yoke and closed when the stem is retracted, with visual indication at the valve.
Alarm check valve
Check valve with trim that detects sprinkler water flow; the inspector test verifies retarding chamber, pressure switch, and alarm signaling operate correctly.
Dry pipe valve
Valve held closed by air pressure on the system side and water pressure on the supply side; it trips when air leaks reduce pressure, allowing water into piping.
Valve tamper switch
Supervisory device that signals an off-normal control valve position to the fire alarm panel; testing verifies the signal and restoration.
Pressure regulating valve
Device that reduces downstream pressure; verify inlet and outlet pressures, flow capacity, strainer condition, and that outlet pressure meets design.
ITM record content
Record includes date, system and component identification, tester, inspection or test results, deficiencies found, and corrective actions taken or recommended.
Impairment record
Document affected system, reason, start and end time, authority and occupant notifications, fire watch, and restoration; supports accountability during unprotected periods.
Acceptance baseline
Initial acceptance test data for pump curves, main drains, and alarm response provide the reference for detecting deterioration during later inspections.
Critical deficiency
Deficiency that compromises system performance and requires immediate correction or impairment procedures, such as a closed control valve or failed fire pump.