NICET ITWBS flashcards
NICET ITWBS · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- NFPA 25
- Standard for inspection, testing, and maintenance of water-based fire protection systems; it applies to existing systems and does not replace design requirements of NFPA 13 or 14.
- NFPA 13
- Standard for design and installation of sprinkler systems; used as a baseline for acceptance and for evaluating whether existing sprinkler arrangements meet design criteria.
- NFPA 14
- Standard for installation of standpipe and hose systems; covers classes, pipe sizing, outlets, pressure, and acceptance testing before NFPA 25 maintenance begins.
- NFPA 20
- Standard for stationary fire pumps; covers pump selection, installation, controllers, and acceptance testing; NFPA 25 then governs routine inspection and testing.
- Lockout tagout
- Procedure that isolates hazardous energy, locks controls, and verifies zero energy before servicing fire pumps, controllers, or electrical alarm circuits to prevent unexpected startup or shock.
- Impairment fire watch
- When fire protection is disabled, notify occupants and the authority having jurisdiction as required and provide a trained fire watch with extinguishing capability until systems are restored.
- Confined space entry
- Entry into pits, vaults, or tanks requires atmospheric testing, ventilation, an attendant, retrieval equipment, and authorization; oxygen deficiency or flammable gas can be fatal.
- Stored energy hazard
- Capacitors, springs, compressed air, and pressurized water can remain energized after isolation; release or block stored energy and verify before work begins.
- Hot work permit
- Written authorization for cutting, welding, or grinding near sprinkler equipment; requires area protection, fire watch, and checking for concealed combustibles before and after work.
- Rated fire pump point
- At 100 percent rated flow, a centrifugal fire pump must produce at least 100 percent of rated pressure; this point anchors the pump performance curve.
- 150 percent pump flow
- At 150 percent of rated flow, a centrifugal fire pump must produce at least 65 percent of rated pressure; this confirms the curve has adequate overload capacity.
- Churn pressure limit
- Shutoff or churn pressure of a centrifugal fire pump generally must not exceed 140 percent of rated pressure; higher pressure can overstress system components.
- Net pump pressure
- Discharge pressure minus suction pressure, with gauge corrections; used to plot fire pump test results and compare performance with the rated curve.
- Hydrant flow residual
- During a hydrant flow test, residual pressure should not fall below about 20 psi; lower residual indicates supply limitation and possible cavitation or inadequate fire flow.
- Main drain test
- Full-flow test through the main drain; record static and residual pressures and compare with previous results to detect supply changes, closed valves, or obstructions.
- Inspector test connection
- Valve at the end of a sprinkler branch that simulates one sprinkler flow; opening it verifies waterflow alarm, pressure switch, and retard chamber operation.
- Spare sprinkler inventory
- Replacement sprinklers of correct type, temperature rating, and K-factor kept on site; inventory is checked during inspections and replenished after use.
- Dry pipe trip test
- Test that admits air or water to a dry pipe valve to verify the clapper trips, water reaches the system, alarms operate, and valve resets properly.
- Gauge inspection monthly
- System gauges are read monthly to compare normal supply and system pressures; unexplained changes can indicate leaks, closed valves, or water supply problems.
- Class I standpipe
- Standpipe system with 2.5-inch hose connections intended for fire department use; minimum residual pressure at the topmost outlet is generally 100 psi.
- Class II standpipe
- Standpipe system with 1.5-inch hose stations intended for occupant use; minimum residual pressure at the topmost outlet is generally 65 psi.
- Standpipe hydrostatic
- Pressure test of standpipe piping at 200 psi for two hours or 50 psi above maximum system pressure, whichever is greater, with no leakage.
- Fire department connection
- Connection where a pumper supplies a standpipe or sprinkler system; inspect caps, threads, gaskets, clappers, signage, and unobstructed access.
- OS&Y valve position
- Outside screw and yoke valve is open when the stem extends from the yoke and closed when the stem is retracted, with visual indication at the valve.
- Alarm check valve
- Check valve with trim that detects sprinkler water flow; the inspector test verifies retarding chamber, pressure switch, and alarm signaling operate correctly.
- Dry pipe valve
- Valve held closed by air pressure on the system side and water pressure on the supply side; it trips when air leaks reduce pressure, allowing water into piping.
- Valve tamper switch
- Supervisory device that signals an off-normal control valve position to the fire alarm panel; testing verifies the signal and restoration.
- Pressure regulating valve
- Device that reduces downstream pressure; verify inlet and outlet pressures, flow capacity, strainer condition, and that outlet pressure meets design.
- ITM record content
- Record includes date, system and component identification, tester, inspection or test results, deficiencies found, and corrective actions taken or recommended.
- Impairment record
- Document affected system, reason, start and end time, authority and occupant notifications, fire watch, and restoration; supports accountability during unprotected periods.
- Acceptance baseline
- Initial acceptance test data for pump curves, main drains, and alarm response provide the reference for detecting deterioration during later inspections.
- Critical deficiency
- Deficiency that compromises system performance and requires immediate correction or impairment procedures, such as a closed control valve or failed fire pump.