NICET Special Hazards II key terms
NICET Special Hazards II · Get comfortable with the vocabulary.
- Clean agent
- Related: Halocarbon agent, Inert gas agent, Total flooding system
An electrically nonconductive, volatile extinguishing agent that evaporates after discharge, leaving no residue, and is used where water or powder would damage sensitive equipment or contaminate the space.
- Halocarbon agent
- Related: Clean agent, Inert gas agent, Design concentration
A clean agent built from carbon plus halogens such as fluorine, which suppresses fire mainly by absorbing heat from the flame rather than by depleting oxygen in the room.
- Inert gas agent
- Related: Clean agent, Halocarbon agent, Design concentration
A clean agent made of naturally occurring gases such as nitrogen, argon, or blends, which extinguishes fire chiefly by lowering the oxygen level in the protected space below the point that supports combustion.
- Design concentration
- Related: Cup burner extinguishing concentration, Class C fire, Total flooding system
The agent concentration, expressed as a percentage by volume in air, that a total flooding system must achieve and hold to reliably extinguish the hazard, set above the cup burner value by a safety margin.
- Cup burner extinguishing concentration
- Related: Design concentration, Class B fire
The minimum agent concentration, determined by a standardized small-scale flame test, that extinguishes a liquid fuel flame; it is the baseline from which the design concentration is calculated.
- No-observed-adverse-effect level (NOAEL)
- Related: Lowest-observed-adverse-effect level (LOAEL), Design concentration, Egress time
The highest tested agent concentration at which no measurable harmful physiological effect appears in test animals; it caps the concentration allowed in normally occupied spaces.
- Lowest-observed-adverse-effect level (LOAEL)
- Related: No-observed-adverse-effect level (NOAEL), Egress time, Predischarge alarm
The lowest tested concentration at which a harmful physiological effect is observed; it governs whether occupants may remain in a space during discharge and how quickly they must leave.
- Total flooding system
- Related: Enclosure integrity test, Design concentration, Clean agent
A fixed system that discharges agent into and holds it within an enclosed volume so the entire protected space reaches the design concentration, rather than applying agent to a specific object.
- Enclosure integrity test
- Related: Hold time, Total flooding system, Ventilation shutdown
A door fan or blower door test that measures leakage from the protected room to confirm it can retain the agent at design concentration for the required hold time.
- Hold time
- Related: Enclosure integrity test, Total flooding system, Discharge nozzle
The period during which a total flooding system must keep the agent concentration at or above the design value after discharge, allowing responders time to control the source of the fire.
- Predischarge alarm
- Related: Egress time, Time delay, Cross-zoning
An audible and visual warning that sounds before agent release, giving occupants time to evacuate and trained staff time to investigate the alarm before the system discharges.
- Time delay
- Related: Predischarge alarm, Abort switch, Egress time
A programmed interval between the alarm and agent discharge, required to give occupants time to leave the space and to allow manual abort where the hazard proves minor.
- Egress time
- Related: Time delay, Predischarge alarm, No-observed-adverse-effect level (NOAEL)
The time needed for occupants to travel from the protected space to a safe location, used to justify the time delay and to judge whether a space may be occupied during discharge.
- Abort switch
- Related: Time delay, Predischarge alarm, Manual release
A manually operated device that interrupts the discharge sequence after an alarm, allowing a trained operator to stop release when the signal is false or the hazard is small.
- Manual release
- Related: Abort switch, Cross-zoning, Discharge nozzle
A hand-operated station that lets a person start agent discharge on demand, bypassing automatic detection, typically installed at the exit of the protected space.
- Cross-zoning
- Related: Manual release, Predischarge alarm, Detection zone
A detection arrangement requiring two independent signals, usually from detectors in different zones, before the system releases agent, reducing discharges caused by a single faulty detector.
- Detection zone
- Related: Cross-zoning, Discharge nozzle
A defined portion of the protected area served by its own detectors, used in cross-zoning logic and to identify where within the space an alarm has originated.
- Discharge nozzle
- Related: Pipe sizing, Total flooding system, Hold time
An engineered orifice that distributes agent into the protected space at a designed flow rate and pattern so the required concentration mixes uniformly within the required time.
- Pipe sizing
- Related: Discharge nozzle, Manifold, Discharge time
The hydraulic calculation of agent piping so each nozzle receives the flow and pressure assumed in the design, keeping discharge within the time limit and avoiding excessive pressure at the nozzles.
- Manifold
- Related: Pipe sizing, Agent cylinder, Discharge nozzle
A header that connects multiple agent cylinders to a common supply pipe, allowing them to discharge together as one system while each cylinder keeps its own valve and actuation.
- Agent cylinder
- Related: Manifold, Discharge time, Clean agent
A pressure vessel storing the extinguishing agent, fitted with a valve, actuation device, and often a pressure gauge and safety relief, sized so the system holds enough agent for the design.
- Discharge time
- Related: Pipe sizing, Agent cylinder, Design concentration
The maximum period allowed for a system to deliver its full agent quantity, set short enough to knock down the fire before it grows but long enough to limit turbulence and pressure surges.
- Ventilation shutdown
- Related: Enclosure integrity test, Hold time, Total flooding system
The automatic stopping of fans and closing of dampers serving the protected space before discharge, so agent is not exhausted and the design concentration is not diluted.
- Class B fire
- Related: Class C fire, Cup burner extinguishing concentration, Class K fire
A fire in flammable or combustible liquids and gases, such as solvents, fuels, and cooking oils, where the hazard is a fuel surface rather than glowing solid material.
- Class C fire
- Related: Class B fire, Clean agent, Class K fire
A fire involving energized electrical equipment, where the primary concern is shock risk until power is removed, after which the fire is treated according to the burning material.
- Class K fire
- Related: Wet chemical system, Class B fire, Class C fire
A fire in cooking appliances involving combustible cooking media such as vegetable or animal oils and fats, requiring a wet chemical agent that saponifies the surface.
- Wet chemical system
- Related: Class K fire, Fusible link, Manual pull station
A pre-engineered system that discharges an alkaline solution onto cooking media, reacting with the fat to form a soap-like layer that smothers the fire and cools the surface.
- Fusible link
- Related: Wet chemical system, Manual pull station, Detector
A heat-sensitive device that separates at a rated temperature to actuate detection or release, commonly used over cooking appliances and in pre-engineered system piping.
- Manual pull station
- Related: Manual release, Fusible link, Wet chemical system
A hand-operated device that mechanically or electrically actuates a special hazard system when a person discovers fire, required as a backup to automatic detection.
- Carbon dioxide system
- Related: Total flooding system, Predischarge alarm, Clean agent
A system using carbon dioxide, which extinguishes mainly by displacing oxygen, and is permitted only in spaces not normally occupied because of its severe asphyxiation hazard.
- Foam system
- Related: Class B fire, Deluge system, Discharge nozzle
A system that blankets a flammable liquid surface with a foam blanket, separating fuel from air and cooling it, used for storage tanks, spill areas, and aircraft hangars.
- Deluge system
- Related: Foam system, Detector, Water spray system
A sprinkler system with open nozzles and a control valve that opens on detection, applying water over an entire area at once rather than only where a sprinkler has fused.
- Water spray system
- Related: Deluge system, Discharge nozzle, Foam system
A fixed system using nozzles that produce a directed, finely divided water pattern onto specific equipment or hazards, often for cooling tanks or protecting transformers.
- Detector
- Related: Cross-zoning, Detection zone, Fusible link
A device that senses a fire signature such as smoke, heat, or flame and sends a signal to the control panel, initiating alarm and, through the panel, discharge logic.
- Pre-engineered system
- Related: Wet chemical system, Fusible link, Pipe sizing
A packaged special hazard system whose components and piping are designed and tested as a unit by the manufacturer, with limits on pipe length, nozzle count, and layout.
- Plan review
- Related: Acceptance test, Enclosure integrity test, Pipe sizing
The examination of submitted drawings, calculations, and specifications against applicable standards before installation, confirming agent quantity, pipe sizing, and detection are adequate.
- Acceptance test
- Related: Plan review, Enclosure integrity test, Ventilation shutdown
The documented on-site verification after installation that the system operates as designed, including detection, alarm, actuation, and, where applicable, enclosure integrity.