Clean agent total flooding
A clean agent system discharges gaseous extinguishing agent into an enclosed space to achieve a design concentration that suppresses fire without leaving residue.
CO2 total flooding hazard
Carbon dioxide total flooding reduces oxygen and cools; because design concentrations can be lethal, it is generally limited to unoccupied spaces or spaces with strict safeguards.
Wet chemical kitchen system
Wet chemical systems use an alkaline solution sprayed on cooking oils and fats, causing saponification to form a soapy blanket that cools and smothers the fire.
Dry chemical extinguishing
Dry chemical agents are finely divided powders that interrupt the combustion chain reaction; they are effective on flammable liquid and gas fires but leave residue.
Foam blanket principle
Foam extinguishes flammable liquid fires by forming a blanket that separates the fuel surface from oxygen and suppresses vapor release, while water content provides cooling.
Water mist system
Water mist systems discharge fine droplets that cool the fire, displace oxygen, and wet surfaces; they use less water than conventional sprinklers and are covered by NFPA 750.
Water spray system
A water spray system uses fixed nozzles to apply water in a specified pattern and direction to protect a specific hazard such as a transformer or tank.
Foam-water system
A foam-water system combines foam concentrate with water and discharges through sprinklers or nozzles to blanket flammable liquids while providing cooling.
Total flooding agent quantity
The required clean agent quantity depends on enclosure volume, design concentration, agent properties, temperature, and altitude; calculations follow NFPA 2001 and manufacturer data.
Enclosure integrity test
A door-fan or pressurization test measures enclosure leakage to verify the space can hold the design concentration for the required hold time.
Cross-zoning detection
Cross-zoning requires two independent detectors to operate before agent discharge, reducing false discharges while maintaining rapid detection.
Discharge delay
A time delay before clean agent discharge allows occupants to evacuate and can be coordinated with alarms, doors, and HVAC shutdown.
Nozzle placement rules
Nozzles must be installed at listed spacing, height, and orientation for the hazard, following manufacturer coverage limits and the approved design.
Wet chemical nozzle coverage
Wet chemical nozzles are arranged to cover cooking appliances, hood plenums, and exhaust ducts, with listed spacing and aim points for each hazard.
Foam application rate
Foam application rate is the flow of foam solution per unit area, selected from NFPA 11 based on fuel type, foam concentrate, and hazard.
Water mist pressure classes
NFPA 750 classifies water mist systems by operating pressure: low pressure up to 175 psi, intermediate from 175 to 500 psi, and high pressure above 500 psi.
Monthly visual inspection
A monthly inspection checks gauges, agent cylinder condition, valve position, alarms, and obvious damage without discharging agent.
Cylinder hydrostatic testing
Agent cylinders must be hydrostatically tested or requalified at intervals set by NFPA and DOT, which vary by agent, cylinder type, and service.
Wet chemical semiannual service
NFPA 17A requires inspection and maintenance of wet chemical systems at least semiannually, including nozzles, cartridge pressure, and actuation components.
Dry chemical semiannual service
NFPA 17 requires dry chemical systems to be inspected and maintained at least semiannually, checking agent quantity, expellant gas, nozzles, and controls.
Enclosure integrity retest
Enclosure integrity should be retested after modifications to the enclosure, HVAC, or openings, and at intervals required by the adopted standard or authority.
Foam proportioning test
Foam proportioning tests verify the concentrate is mixed at the design percentage by measuring solution conductivity or refractivity during a flow test.
Trip test
A trip test verifies that a deluge or pre-action valve operates on detection signal and that alarms and interlocks function correctly.
ITM record retention
Inspection, testing, and maintenance records document dates, results, deficiencies, and corrective actions and must be retained for the period required by the code or AHJ.
NFPA 2001
NFPA 2001 is the standard for clean agent fire extinguishing systems, covering design, installation, commissioning, inspection, testing, and maintenance.
NFPA 12
NFPA 12 is the standard for carbon dioxide extinguishing systems, including total flooding and local application design and safety requirements.
NFPA 17 and 17A
NFPA 17 covers dry chemical systems, while NFPA 17A covers wet chemical systems; both address design, installation, maintenance, and testing.
NFPA 11 and 16
NFPA 11 covers foam extinguishing systems, and NFPA 16 covers foam-water sprinkler and spray systems for flammable liquid hazards.
NFPA 750 and 15
NFPA 750 covers water mist systems, and NFPA 15 covers water spray fixed systems for fire protection.
Sequence of operations
A sequence of operations describes detection, alarm, shutdown, discharge, and ancillary actions in the order they occur during a fire event.
As-built documentation
As-built drawings reflect the installed system, including pipe routing, nozzle locations, cylinder sizes, and device addresses, and support future maintenance.
Authority having jurisdiction
The AHJ is the organization or individual responsible for approving equipment, installations, and procedures under the adopted code.