The requested SSI exam-information page returned a 404 error during retrieval, so no exam outline, domain weighting, item count, time limit, passing score, fee, eligibility requirement, recertification cycle, or delivery format could be confirmed from an official page. Candidates who need those details should treat any figure they encounter elsewhere as unverified until it is confirmed against NICET's own SSI program page, the Exams section, and the Fees page linked from the site navigation. The NICET SSI case studies are 5 cases and about 4,921 words.

1

Door Release Through a Polled Software Gateway

A nine-story Class B office tower is being commissioned with 38 electromagnetic door holders and 22 card-reader doors fitted with magnetic locks. The fire alarm is a networked system with four nodes; the access control system is a separate head-end that polls the fire panel every 60 seconds through a Modbus TCP gateway.

912 words, about 5 min
2

Voice System Riding the Campus Core Network

A four-building university campus runs one networked emergency voice/alarm communication system: 96 nodes, 1,200 speakers, and a single system-wide operator console in the police dispatch center. The IT department requires the fire alarm to ride the shared campus core as a VLAN with DHCP addressing, arguing that a private fiber plant would duplicate infrastructure.

924 words, about 5 min
3

Smoke Control Driven by the Building Automation System

An 11-story hotel with a six-story atrium uses the building automation system to drive smoke control: 14 rooftop units, 62 smoke dampers, six stairwell pressurization fans on variable-frequency drives, and relief dampers, all on a BACnet MS/TP trunk at 19.2 kbps with a 10-second polling interval. The written sequence of operations says that on any alarm in a smoke zone, the associated rooftop units stop, the stairwell fans start, and the dampers in the zone open.

1,030 words, about 5 min
4

Priority Conflict Between Fire Alarm and Mass Notification

A suburban school district operates three K-12 buildings and an outdoor athletics stadium on one combined emergency communication system. The fire alarm voice panels and the district's mass notification system share amplifier racks and speaker circuits; the stadium has a 24-speaker outdoor array.

988 words, about 5 min
5

Remote Supervision and Dealer Remote Access Across 30 Sites

A 30-store retail chain monitors all locations from one central station. Each store has an addressable fire panel, an IP communicator on the store's broadband circuit, and a cellular radio that was specified as a redundant path.

1,067 words, about 5 min