Sprinkler discharge formula
Q = K times the square root of p, where Q is flow in gpm, K is the sprinkler discharge coefficient, and p is pressure in psi at the sprinkler.
Hazen-Williams friction loss
Friction loss per foot of pipe equals 4.52 times Q to the 1.85 power, divided by C to the 1.85 power times d to the 4.87 power, with Q in gpm and d in inches.
Light hazard density
Minimum design density of 0.10 gpm per square foot over a 1,500 square foot remote area, with maximum sprinkler spacing of 15 feet and 225 square feet per head.
Ordinary Hazard Group 1
Design density of 0.15 gpm per square foot over a 1,500 square foot remote area, with maximum spacing of 15 feet and 130 square feet per sprinkler.
Ordinary Hazard Group 2
Design density of 0.20 gpm per square foot over a 1,500 square foot remote area, with maximum spacing of 15 feet and 130 square feet per sprinkler.
Extra hazard spacing limit
Maximum sprinkler spacing of 12 feet and 100 square feet per sprinkler, with densities starting at 0.30 gpm per square foot over a 2,500 square foot remote area.
Remote area reduction
A 25 percent reduction in remote area is allowed only with listed quick-response sprinklers under ceilings 10 feet or less, and never reduces the required density.
Schedule 40 pipe limits
Pipe schedule method caps 1 inch at 2 sprinklers, 1.5 inch at 5, 2 inch at 10, 2.5 inch at 30, 3 inch at 60, and 4 inch or larger at 100.
C factor values
Hazen-Williams roughness coefficient C is 120 for black steel and galvanized steel, 150 for cement-lined ductile iron, and 140 for copper tubing.
Balancing a sprinkler
Increase the flow of a lower-pressure head until its pressure equals the junction pressure, using Q new equals Q old times the square root of pressure new over pressure old.
Wet-pipe valve arrangement
A wet-pipe riser requires a main control valve, a check valve, and an alarm check valve, plus a waterflow switch or pressure switch that activates the alarm.
Dry-pipe air pressure
Air pressure in a dry-pipe system is typically maintained about 20 psi above the trip pressure of the dry-pipe valve, and a quick-opening device is needed above 500 gallons.
Design area definition
The hydraulically most demanding area of sprinkler operation, measured in square feet, whose size depends on hazard class and sprinkler type.
Density definition
The minimum flow rate in gpm per square foot that must be delivered over the design area, set by the occupancy hazard classification and commodity.
Sprinkler K factor
A number expressing the discharge coefficient of a sprinkler; a larger K means more flow at the same pressure, and K is listed on the sprinkler.
Hydraulic junction point
The node where two or more pipe paths meet; the most demanding path sets the pressure, and other paths are adjusted to match it.
Supply curve
A plot of available pressure versus flow at the base of the riser, derived from a flow test and adjusted for elevation and friction losses.
Demand curve
A plot of required pressure versus flow for the sprinkler system, plotted from the hydraulically most remote sprinkler back to the water supply.
Safety margin
The difference between available supply pressure and system demand pressure at the same flow; a positive margin is required for the design to be acceptable.
Elevation pressure change
Pressure changes by 0.433 psi per foot of elevation, added when flowing downward and subtracted when flowing upward in a hydraulic calculation.
Flow test data
Static pressure, residual pressure, and pitot flow measured at a hydrant; these three values define the water supply curve for the calculation.
Velocity limit in pipe
Design velocity in sprinkler piping should not exceed 20 feet per second in most branch lines and 32 feet per second in mains and risers.
Branch line maximum length
The distance from the cross main to the most remote sprinkler on a branch line; longer branch lines increase friction and pressure demand.
Sprinkler coverage area
The floor area protected by one sprinkler, calculated as spacing along the branch times spacing between branch lines, and limited by hazard class.
Deflector distance
Sprinkler deflectors must be a minimum of 1 inch below the ceiling for standard spray sprinklers, and closer for concealed or recessed types.
Dry-pipe design area increase
Dry-pipe and preaction systems require the remote area to be increased by 30 percent because of the larger volume of gas to be expelled.
Pump churn pressure
The maximum pressure a fire pump produces at zero flow; it must not exceed the rated pressure by more than 140 percent for the system components.
Standpipe flow requirement
Class I standpipes require 500 gpm for the most remote riser and 250 gpm for each additional riser, up to a total of 1,250 gpm.
Hose stream allowance
Additional flow in gpm added to the sprinkler demand for manual hose lines, set by hazard class and duration, and included in the supply calculation.
Water supply duration
The time the supply must sustain the demand, typically 30 to 120 minutes depending on hazard, and longer for extra hazard occupancies.
Pipe schedule method
A prescriptive sizing method that limits the number of sprinklers per pipe size; it is not permitted for new systems above certain sizes without hydraulic calculation.
Hydraulic calculation report
A document listing each node, flow, pressure, pipe size, length, and fitting equivalent length, plus the supply and demand curves and the safety margin.
Equivalent length of fittings
The friction loss of a fitting expressed as a length of straight pipe of the same size, added to the actual pipe length in the calculation.