- Design density
- The minimum discharge in gpm per square foot applied over the hydraulically most remote area; it is selected from the occupancy hazard table and multiplied by the protected area to get the remote-area demand.
- Remote area
- The hydraulically most demanding area of sprinkler operation used to compute system demand; it may be reduced for quick-response sprinklers or increased for dry pipe, sloped ceilings, and high-temperature conditions.
- Hazen-Williams formula
- An empirical friction-loss equation using flow, pipe inside diameter, pipe length, and a roughness coefficient C; it is the standard method for computing friction loss in water-based system layout.
- C-factor
- The Hazen-Williams roughness coefficient; higher values mean smoother pipe and less friction, so a change in C changes the calculated demand without any change in pipe size.
- Equivalent pipe length
- The added length of straight pipe that produces the same friction loss as a fitting, valve, or device; it is added to actual pipe length before the friction calculation.
- Most remote sprinkler
- The sprinkler farthest hydraulically from the supply, not necessarily the farthest physically; it sets the starting pressure and flow for the branch-line calculation.
- Minimum sprinkler pressure
- The lowest operating pressure permitted at a sprinkler, typically 7 psi for standard spray devices; extended-coverage and special sprinklers require the higher minimum stated in their listing.
- K-factor
- A discharge coefficient relating flow to pressure by Q = K times the square root of P; it lets the layout convert a required pressure into a flow for each sprinkler.
- Branch line balancing
- Adjusting assumed flows so that branch lines meeting at a cross main produce equal pressures; for identical orifices, flow varies as the square root of pressure.
- Hose allowance
- Additional gpm added to the sprinkler demand at specified points to account for fire department hose streams; the amount depends on occupancy and system type.
- Pump churn point
- The point of zero flow on a fire pump curve, where shutoff head is highest; the curve is plotted from churn through rated flow to maximum flow.
- Rated pump point
- The flow and head the pump is listed to deliver; the system demand must fall below the pump curve with the required margin at this point and beyond.
- Water supply curve
- A plot of available pressure versus flow derived from static, residual, and test-flow readings; available pressure at the riser base is read from it at the demand flow.
- Static pressure
- The pressure reading with no water flowing during a flow test; it establishes the baseline for constructing the supply curve but does not by itself show capacity.
- Residual pressure
- The pressure remaining at the test hydrant while water flows; together with the flow and static readings it defines the supply curve used in the hydraulic calculation.
- Pipe schedule method
- A table-based sizing method allowed only for limited wet, light-hazard steel systems within stated size and height limits; outside those limits hydraulic calculation is required.
- Occupancy classification
- The hazard category assigned to the protected space based on contents and combustibility; it drives density, remote area, sprinkler spacing, and water supply requirements.
- Sprinkler coverage area
- The floor area protected by one sprinkler, found from spacing along the branch line and between branch lines; it is multiplied by density to get flow per sprinkler.
- Maximum spacing
- The largest permitted distance between sprinklers and between a sprinkler and a wall or obstruction; it varies with hazard and sprinkler type and must be checked separately from area limits.
- Quick-response reduction
- A permitted reduction of the remote area when listed quick-response sprinklers are used in qualifying occupancies with adequate ceiling height and no obstructed construction.
- Dry pipe increase
- An increase applied to the remote area for dry pipe and preaction systems because water delivery is delayed and more sprinklers are expected to operate before the water arrives.
- Velocity limit
- A practical cap, commonly 20 ft/s, on calculated water velocity in supply and cross-main piping to control friction loss and noise; exceedance triggers review of pipe sizes.
- Alarm valve loss
- The friction loss through a wet alarm check valve, dry valve, or preaction valve; it is included in the calculation as a pressure loss or equivalent length.
- Test and drain
- An assembly used to flow-test alarm and waterflow devices and to drain the system; its fittings and piping add friction loss that must be accounted for in the layout.
- Hydraulic reference point
- The node on the calculation plate from which the supply curve is applied, usually the riser base or the point of connection to the public main.
- Safety margin
- The required gap between available supply pressure and calculated demand pressure at the reference point, ensuring the system works as installed with some degradation.
- Standpipe demand
- The flow and residual pressure required at the most remote standpipe outlet for the system class; it is calculated separately and combined with sprinkler demand where both apply.
- Seismic bracing spacing
- The maximum interval between lateral and longitudinal braces and the clearance required at building separation joints; these layout decisions affect pipe routing before hydraulics are finalized.
- Hanger spacing
- The maximum support interval for pipe based on diameter and material; hangers and sway bracing must be located so pipe alignment and sprinkler positions remain within tolerance.
- Design area shape
- The remote area is laid out as a rectangle on the most demanding branch lines, with its long dimension parallel to the branch lines and its length at least 1.2 times the square root of the area.
- Density-area curve
- A curve allowing reduced density at larger remote areas, or higher density at smaller areas, for a given hazard; it is used when the design area differs from the reference point.
- System demand point
- The total flow and pressure required at the reference point, including sprinklers, hose allowance, and standpipe demand; it is plotted against the supply and pump curves.
- Calculation plate
- The summary document showing node flows, pipe sizes, lengths, elevations, and pressures; it must match the plans and identify the hydraulic reference point for review.