Six-Foot Sewer Trench With a Live Gas Service

NITC Journey Level Plumber · Put your knowledge to work in context.

All case studies

Six-Foot Sewer Trench With a Live Gas Service

You are the lead plumber on a sewer lateral replacement at a 1960s ranch house. The crew has excavated a 6 ft deep, 36 in wide trench in the front yard to expose a broken 4 in clay lateral. The soil is damp sand and gravel from previous fill, and the sides are sloughing in small chunks. The backhoe is parked 4 ft from the trench edge, with spoil piled along the same side. A worker is inside hand-digging beside a marked 1 in plastic gas service that runs parallel 18 in from the trench wall. The foreman wants the cut finished before the 2:00 p.m. inspection and tells you to get in the trench. A 5 ft tall steel trench box sits on the truck. The only ladder is 30 ft away. The gas locate ticket was issued 10 days ago.

1. Identify every hazard in this setup and state the immediate actions you would take before anyone re-enters the trench.

Read the worked answer

The hazards are cave-in, the live gas service, and the unsafe access/egress. A 6 ft depth crosses the 5 ft trigger for a protective system under OSHA 29 CFR 1926.652. Damp sand and gravel that is sloughing is likely Type C soil, and only a competent person can classify it. A worker inside is exposed to a sudden wall collapse. Immediate actions: order everyone out, stop the backhoe, establish an exclusion zone, and notify the competent person. Do not re-enter until the trench is sloped, shored, or boxed and inspected. Move the ladder within 25 ft of lateral travel, secure it, and extend it 3 ft above the edge. Re-confirm the gas locate and call the utility if marks are missing or the ticket is stale under local rules.

2. Assume the trench is made safe. What protective system, access, and inspection measures would you require for the 6 ft depth in this soil? Cite the thresholds.

Read the worked answer

For Type C soil, the maximum allowable slope is 1.5:1, about 34 degrees from horizontal. The alternative is a trench box, but it must be installed per the manufacturer, extend to the trench bottom, and be sized for the depth and soil. A 5 ft box in a 6 ft trench can leave an unprotected zone above the box unless the top is sloped back or a taller box is used. Spoil and equipment must be at least 2 ft from the edge. Provide a secured ladder within 25 ft lateral travel that extends 3 ft above the top. A competent person must inspect daily, after rain, and after any change. No worker may ride the box while it is being moved.

3. What is wrong with the utility and spoil/equipment placement, and how would you verify and protect the gas line before cutting?

Read the worked answer

The 1 in plastic gas service is an underground utility. The age of the locate ticket is a warning, not proof: verify the positive response and that the marks are still visible; if the ticket is stale or marks are disturbed, re-notify 811 and the gas utility. Hand-expose the line with soft tools within the tolerance zone; 18 in parallel is likely inside that zone. Support the exposed gas line and do not use the backhoe near it. The utility may require a standby. Spoil and the backhoe at 4 ft are too close; move them back at least 2 ft, and farther if the competent person requires. If the line is damaged, evacuate, eliminate ignition sources, and call the utility and emergency services.