NIULPE Class 1 study materials
NIULPE Class 1 study resources

NIULPE Class 1 flashcards

NIULPE Class 1 · Build recall with a focused review session.

32 cards. Read the term and the definition here. The deck at the top of this page is optional.

Maximum allowable working pressure
The highest pressure at which a boiler component may legally operate, computed from shell thickness, allowable stress, joint efficiency, and corrosion allowance under ASME Section I rules.
Joint efficiency
A factor between 0.70 and 1.0 applied to allowable stress in shell calculations; it reflects the strength of a welded seam and whether full radiography was performed.
Postweld heat treatment
Controlled heating and cooling of a welded component to relieve residual stresses and reduce hardness, required for thick carbon steel and many alloy steel joints.
Safety valve accumulation
The pressure rise above set pressure allowed while the safety valve relieves full capacity; ASME limits accumulation to 10 percent above maximum allowable working pressure.
Stoichiometric air
The exact quantity of air needed to burn a fuel completely with no oxygen left over; excess air is supplied above this value to ensure complete combustion.
Flame failure response time
The maximum interval, typically 4 seconds, within which the burner management system must shut off fuel after loss of proven flame is detected.
Pre-purge
A forced-air purge of the furnace and passes, at least four volume changes, performed before light-off to remove combustible gases and prevent furnace explosion.
Low-water fuel cutoff
A safety device that stops burner firing when boiler water level falls below a safe limit; it is proven by a slow-drain evaporation test.
Three-element feedwater control
A drum level control strategy using steam flow, feedwater flow, and drum level signals together to anticipate load changes and hold level stable.
Deaerator
A feedwater heater that removes dissolved oxygen and other gases by heating water to saturation and venting; it limits oxygen pitting in the boiler.
Economizer
A heat exchanger that recovers heat from flue gas to preheat boiler feedwater, lowering stack temperature and improving overall boiler efficiency.
Induced-draft fan
A fan located after the boiler that pulls flue gas through the unit and maintains slightly negative furnace pressure; it starts before and stops after the forced-draft fan.
Turbine heat rate
The thermal energy input in Btu required to produce one kilowatt-hour of output; it equals 3,413 divided by cycle thermal efficiency and measures plant performance.
Overspeed trip
A protective device that stops steam admission when turbine speed reaches about 110 percent of rated speed, preventing catastrophic rotor and blade failure.
Reaction turbine stage
A stage in which steam expands and drops pressure across both stationary and moving blades, producing reaction force on the rotor in addition to impulse force.
Synchronous speed
The rotational speed of an AC generator set by frequency and pole count, calculated as 120 times frequency divided by the number of poles.
Latent heat of vaporization
The heat absorbed when water changes to steam at constant temperature and pressure; at atmospheric pressure it is about 970 Btu per pound.
Overall heat transfer coefficient
A combined value U that accounts for convection on both sides, conduction through the wall, and fouling resistance, used in Q equals U times area times temperature difference.
Thermal expansion
The change in length of a material caused by temperature change, calculated as the expansion coefficient times original length times temperature difference.
Boiler thermal efficiency
The ratio of heat absorbed by steam to heat released by fuel, usually based on higher heating value, expressed as a percentage.
Live zero
A 4–20 mA instrument signal in which 4 mA represents the zero measurement, allowing an open circuit or failed transmitter to be detected below 3.6 mA.
Programmable logic controller scan
The repeating cycle in which a controller reads inputs, executes its program, and updates outputs; scan time determines control response speed.
Power factor
The ratio of real power in kilowatts to apparent power in kilovolt-amperes; a low value means more current is needed for the same useful work.
Flame scanner
A sensor that verifies the presence of a stable flame by detecting ultraviolet or infrared radiation and signals the burner management system to permit or stop fuel.
Caustic embrittlement
Stress corrosion cracking of stressed steel caused by concentrated caustic in crevices; prevented by controlling boiler water pH and limiting caustic concentration.
Oxygen scavenger
A chemical such as sodium sulfite or hydrazine added to feedwater to remove residual dissolved oxygen and prevent pitting corrosion in the boiler.
Blowdown
The controlled removal of boiler water to limit dissolved solids and sludge; the rate is set by conductivity or chemical analysis to prevent carryover and foaming.
National Board Inspection Code
The standard governing inspection, repair, and alteration of in-service boilers; repairs require approval by an authorized inspector and documented records.
Lockout/tagout
A procedure under OSHA 1910.147 that isolates and de-energizes equipment, applies locks and tags, and verifies zero energy before maintenance begins.
Confined-space entry permit
A written authorization for entering a boiler drum or furnace that documents atmospheric testing, ventilation, attendant presence, and rescue provisions.
Selective catalytic reduction
A NOx control method that injects ammonia or urea into flue gas over a catalyst at about 600–750 degrees Fahrenheit, converting NOx to nitrogen and water.
Continuous emission monitoring
An instrument system that measures pollutants such as NOx, sulfur dioxide, carbon monoxide, and opacity in stack gas and records data for regulatory compliance.