- Article 760
- The NEC article that governs fire alarm systems, dividing requirements into general provisions, non-power-limited fire alarm circuits, and power-limited fire alarm circuits.
- NPLFA conductor minimum
- Non-power-limited fire alarm conductors must be at least 18 AWG copper, rated 600 volts, and installed using Chapter 1-4 wiring methods.
- PLFA separation rule
- Power-limited fire alarm conductors must be separated from non-power-limited and power conductors by at least 2 inches or a barrier, unless an exception applies.
- Class 2 ampacity limit
- Table 725.144 limits 18 AWG copper Class 2 or 3 conductors to 7 amperes, 16 AWG to 10 amperes, and 14 AWG to 15 amperes.
- Class A versus Class B
- Class A circuits continue operating through a single open or ground fault, while Class B circuits do not and must annunciate a trouble condition instead.
- Smoke detector spacing
- Spot-type smoke detectors on smooth ceilings are spaced at 30 feet, with 21 feet to walls, covering a maximum of 900 square feet per detector.
- Trouble annunciation time
- A single open or ground fault on a supervised initiating device circuit must produce a trouble signal at the control unit within 200 seconds.
- Alarm activation time
- Notification appliances must activate within 10 seconds of alarm initiation, and waterflow alarms must activate within 90 seconds of water flow.
- High ceiling derating
- For ceilings above 10 feet, smoke detector spacing is reduced by 4 inches per foot of ceiling height, or a 0.7 multiplier may be applied.
- Duct detector threshold
- Duct smoke detectors are required for air handling units exceeding 2,000 cubic feet per minute and must be installed per NFPA 90A and the listing.
- Public mode audibility
- Public mode audible appliances must produce at least 15 dBA above ambient, or 5 dBA above ambient when ambient exceeds 105 dBA, measured at 10 feet.
- Sleeping area low frequency
- Sleeping areas require low-frequency 520 Hz sounders producing at least 75 dBA at the pillow to reliably awaken occupants.
- NAC voltage drop formula
- Voltage drop equals 2 times one-way length times current times conductor resistance per 1000 feet; total drop must stay within the listed appliance range.
- Dedicated fire alarm circuit
- The fire alarm panel must be supplied by a dedicated branch circuit labeled FIRE ALARM CIRCUIT CONTROL with a lockable disconnect or breaker lock.
- Standby battery duration
- Commercial fire alarm systems require secondary battery power sized for 24 hours of standby followed by 5 minutes of full alarm load.
- Battery sizing formula
- Required amp-hours equal standby current times 24 hours plus alarm current times 0.083 hours, multiplied by a 1.2 derating factor.
- Battery recharge requirement
- The battery charger must restore the battery to at least 85 percent capacity within 24 hours after a full discharge.
- Ground fault annunciation
- The control unit must detect and annunciate a distinct ground fault trouble signal on any supervised circuit of the fire alarm system.
- Smoke detector test frequency
- Smoke detectors require an annual functional test, and a sensitivity test at installation and at least every 2 years thereafter.
- Notification appliance testing
- Notification appliances must be functionally tested semiannually, while initiating device and notification appliance circuits are tested annually.
- Waterflow switch test
- Waterflow switches require semiannual testing, and valve supervisory switches require quarterly testing to confirm proper signal transmission.
- Test record retention
- Inspection, testing, and maintenance records must be retained for at least 1 year, or for the life of the system if the authority having jurisdiction requires.
- NJ UCC citation
- The New Jersey Uniform Construction Code is codified at N.J.A.C. 5:23 and adopts the International Building Code and International Fire Code with state amendments.
- Fire subcode official
- The local fire subcode official reviews fire alarm plans and issues permits under the fire protection subcode of the New Jersey Uniform Construction Code.
- Permit application contents
- A New Jersey fire alarm permit application includes sealed plans, specifications, and a completed UCC application form submitted to the local enforcing agency.
- Certificate of occupancy
- A certificate of occupancy is issued after final inspection and approval, and is required before a building may be legally occupied.
- Riser diagram contents
- A riser diagram shows all initiating devices, notification appliances, control equipment, and power supplies with their circuit connections and ratings.
- NFPA 170 symbols
- NFPA 170 provides standard symbols for fire safety and emergency systems used on plans, though project legends may supplement them.
- Record of completion
- The record of completion documents the installed system configuration, device locations, and acceptance test results, and is submitted at project closeout.
- As-built drawings
- As-built drawings reflect the final installed configuration and are submitted at closeout along with operation and maintenance manuals and test records.
- Lockout tagout
- Lockout/tagout procedures de-energize and secure circuits before work, and the panel must be placed in test mode to prevent false alarms.
- Fall protection threshold
- Fall protection is required when working at heights above 6 feet, and ladders must be inspected before each use.