- Fixture unit definition
- A measure of the load-producing effect of a fixture on the drainage system. One fixture unit equals 1 cubic foot per minute, or about 7.5 gallons per minute, of flow.
- Developed length
- The total length of pipe measured along its centerline and through fittings from the stack or main to the fixture. Used to select pipe size from capacity tables.
- Building drain
- The lowest piping of a drainage system that receives soil and waste from inside the building and conveys it to the building sewer, which begins at the building wall.
- Minimum drainage slope
- Horizontal drainage pipe 2-1/2 inches and smaller must slope at least 1/4 inch per foot. Pipe 3 inches and larger may slope 1/8 inch per foot where permitted.
- Cleanout interval
- Cleanouts are required at the base of each stack, at the upper end of horizontal branches, at direction changes over 135 degrees, and at intervals not exceeding 100 feet.
- Trap arm length limit
- The distance from the trap weir to the vent connection is limited by pipe size and slope, for example about 5 feet for 2-inch pipe, to prevent self-siphoning of the trap.
- Vent stack termination
- A vent stack must extend at least 6 inches above the roof, be sized not smaller than the stack it serves, and terminate in open air with an approved fitting.
- Island vent
- A loop vent using a foot vent and a loop above the flood level rim, used to vent a fixture that cannot be vented conventionally. It requires a cleanout at the foot vent base.
- Trap seal depth
- Each fixture trap must maintain a liquid seal of not less than 2 inches and not more than 4 inches, must be self-cleaning, and must be accessible for service.
- Grease interceptor
- A device required for commercial kitchen fixtures discharging fats, oils, and grease. It must be sized by capacity, fitted with a flow-control fitting, and accessible for cleaning.
- Residual fixture pressure
- The minimum residual pressure at a fixture is generally 8 psi for flush tanks and 15 psi for flush valves. Inadequate street pressure requires a booster pump.
- Pressure-reducing valve
- A device required when street pressure exceeds the code limit, typically 80 psi. A closed system also needs a thermal expansion tank or relief device.
- Water heater T&P valve
- A temperature and pressure relief valve installed within the top 6 inches of the tank, piped full size to a safe discharge point without traps or reductions.
- Water closet clearance
- A water closet needs at least 15 inches from its centerline to a side wall and 21 inches in front. The minimum compartment width is 30 inches.
- Water-saving flush volume
- Water closets must be the water-saving type with a flush volume not exceeding 1.6 gallons per flush. Urinals are limited to 1.0 gallon per flush.
- Roof drain sizing
- Storm drainage pipe is sized from design rainfall intensity, roof area, and runoff coefficient. A roof drain sits at the low point, with overflow drainage where required.
- Backwater valve
- A device required on sanitary or storm drains where the building drain may be subject to backflow from the public sewer. It must be installed so it can be serviced.
- Drainage system test
- Drainage systems must be tested with water or air before concealment. The test pressure and duration are set by the code and witnessed by the inspector.
- Gas pipe support
- Fuel gas pipe must be supported at intervals not exceeding 6 feet for horizontal runs and at each change of direction, and protected from damage and corrosion.
- Gas sediment trap
- A sediment trap must be installed at each gas appliance, along with a shutoff valve ahead of the appliance and a union or flanged connection for service.
- Gas appliance connector
- A listed flexible connector must not be concealed, pass through a wall, floor, or ceiling, or exceed the code length limit, typically 6 feet.
- Air gap
- The only absolute backflow protection. It must be at least twice the diameter of the supply pipe and never less than 1 inch above the flood level rim.
- Reduced-pressure principle device
- An RPZ backflow preventer is required for high-hazard connections. It must be tested annually by a certified tester with results reported to the water purveyor.
- Backsiphonage
- A reversal of flow caused when negative pressure in the supply line draws contaminant into the potable system, as opposed to backpressure from downstream pressure.
- Hose bibb vacuum breaker
- A backflow device required on all hose connections. Backflow preventers are also required on boiler feed lines, irrigation systems, and pool fill lines.
- Master Plumber license
- A license required to contract for plumbing work in New Jersey. A Journeyman Plumber may perform work only under a licensed master, and a contracting business must employ one.
- Plumbing permit
- Approval obtained from the local enforcing agency before work begins. Ordinary minor repairs and exposed fixture replacement with no piping change generally do not require one.
- Certificate of approval
- Issued after the final plumbing inspection passes. A certificate of occupancy for a new building cannot issue until plumbing final approval is granted.
- Stack vent
- The extension of a soil or waste stack above the highest fixture, terminating in open air. A vent stack is a separate vertical vent line.
- Horizontal branch
- A drain pipe connecting fixtures to a stack. Horizontal drainage pipe is any pipe installed at a slope less than 45 degrees from horizontal.
- Pressure vacuum breaker
- A backflow device used for low-hazard connections where it can be installed above the highest downstream outlet, preventing backsiphonage.
- Sump pump discharge
- Where gravity drainage is not possible, a sump pit with a cover and ejector or pump is used, and the discharge must be piped to a legal point of disposal.